10
The number of indoor units that can be connected to an outdoor unit is as defined in the following table:
Table 2.2 System Combination
Outdoor Unit Type
Rated
Capacity
(kW)
Min. Total Capacity
of the indoor units
can be connected
(kW)
Max. Total Capacity
of the indoor units
can be connected
(kW)
Numbers of the
indoor units can
be
connected(Q’ty)
Min. Capacity
at Individual
Operation (kW)
RAS-3.0HNSKQ
8.0
4
10.4
2~4
1.8
RAS-3.5HNSKQ
10.0
5
13
2~5
1.8
RAS-4.0HNSKQ
11.2
5.6
14.56
2~5
1.8
RAS-4.5HNSKQ
12.5
6.25
15.6
2~5
1.8
RAS-5.0HNSKQ
14.0
7
18.2
2~6
1.8
RAS-6.0HNSKQ
16.0
8
20.8
2~6
1.8
RAS-6.5HNSKQ
18.0
9
23.4
2~9
1.8
RAS-7.0HNSKQ
20.0
10
26
2~10
1.8
NOTE:
◆
The connectable indoor unit capacity ratio can be calculated as follows:
Connectable Indoor Unit Capacity Ratio = Total Indoor Unit Capacity / Total Outdoor Unit Capacity.
◆
For the same system, if the connectable indoor unit capacity ratio is over than 100%, and which all the
indoor units operate simultaneously, the capacity of every indoor unit should be less than its rated capacity.
◆
Indoor unit and outdoor unit connected to the total capacity of indoor units for the outdoor unit rated capacity of
50% to 130%.