Table 8-3 LED lighting mode at the thermistors troubled
When the connectors of the thermistors are disconnected or the thermistors is open or short, LD301 (red) lights and
LD302 (red) blinks so that they indicate troubled parts. Combinations of LD301 and LD302 are set up for indicating troubled
thermistors. The correspondences between the number of blink time and troubled parts are shown as Table 8-3. Look in the
table (LD301 and LD302 blink) for troubled parts, and if the disconnections of them are checked out, they are replaced.
If you can see two or more troubled thermistors, a small number of blink takes precedence of others.
The electric expansions valve thermistor is put togrther with 3 pieces, when replacing the thermistor, replace one set of 3 pieces
as taking care of positioning. If you don’t do so, the unit may not operate normally and its cooling and heating performance
may drop.
Be ware that only an open-circuit for OH thermistor has to be checked in 5 minutes after the compressor starts.
If the unit operates abnormally after replacing the thermistor, replace the control P.W.B. because it malfunctions.
LED lighting mode
Lights
Lights
Lights
Lights
Lights
Lights
Lights
Lights
Lights
OH thermistor
DEF thermistor
Outdoor temperature thermistor
Electric expansion value thermistor (narrow pipe 1)
Electric expansion value thermistor (wide pipe 1)
Electric expansion value thermistor (narrow pipe 2)
Electric expansion value thermistor (wide pipe 2)
Electric expansion value thermistor (narrow pipe 3)
Electric expansion value thermistor (wide pipe 3)
1 blink
2 blinks
3 blinks
4 blinks
5 blinks
6 blinks
7 blinks
8 blinks
Lights
Lights
Electric expansion value thermistor (narrow pipe 4)
Electric expansion value thermistor (wide pipe 4)
10 blinks
11 blinks
Lights
Lights
Electric expansion value thermistor (narrow pipe 5)
Electric expansion value thermistor (wide pipe 5)
12 blinks
13 blinks
9 blinks
LD301
LD302
0.04V or less
Open
4.96V or more
Short
Troubled thermistor
Judgement
Summary of Contents for RAM-90QH5
Page 13: ... 12 ...
Page 14: ... 13 ...
Page 15: ... 14 ...
Page 19: ... 18 BASE DRAIN PIPE A DRAIN PIPE BUSH 100 mm ABOVE 10 11 ...
Page 21: ... 20 CONSTRUCTION AND DIMENSIONAL DIAGRAM MODEL RAM 90QH5 Service space ...
Page 26: ...CIRCUIT DIAGRAM MODEL RAM 90QH5 27 ...
Page 28: ... 31 ...
Page 31: ... 37 ...
Page 32: ... 39 ...
Page 33: ... 41 ...
Page 34: ... 43 ...
Page 36: ... 45 90 23 ...
Page 42: ... 51 REFRIGERATING CYCLE DIAGRAM MODEL RAM 90QH5 ...
Page 51: ... 60 3 System power Module Circuit ...
Page 60: ... 69 Electric expansion valve thermistor NARROW PIPE 5 5 5 5 8 8 8 ...
Page 72: ... 85 ...
Page 76: ... 90 Lighting mode self diagnosis lamp Location of self diagnosis lamp 1 RAM 90QH5 ...
Page 77: ... 91 Lighting mode self diagnosis lamp 2 RAM 90QH5 ...
Page 83: ...HITACHI PM NO 0371E Printed in Malaysia RAM 90QH5 ...