– 36 –
DEFROST
●
Reversing valve defrost system is employed: it consists of balancing period
→
reversing cycle period
→
balancing period.
(1) Defrost start condition
●
When all the following conditions are established, defrost is executed:
1
Normal operation
2
Heat exchange temperature is within defrost range specified by outdoor temperature and heat exchange
temperature.
3
Defrost inhibit period linked to outdoor temperature has passed.
(2) Defrost release condition
●
If any one of the following conditions is established, defrost is released:
1
Heat exchange temperature returns (heat exchange temperature
⭌
DEFOFF).
2
Defrost max time of 12 minutes has elapsed.
●
Released by condition
1
during balancing period: When remaining balancing period has elapsed, returned
to initial condition (ASTUS = 0).
●
Released by condition
1
or
2
during reversing cycle period: Shifted to balancing period.
(3) Outputs during defrost
●
Indoor defrost request: Transmitted to all units being operated in heating mode.
●
Compressor: Balancing period for [TDF414] seconds
→
Starting of reversing cycle period by [SDRCT2]
min
–1
for [TSKTM2] seconds
→
Accelerating by [DFCTEP] min
–1
/ [TDFSPT] seconds in
remaining reversing cycle period until defrost MAX speed [DEFMAX] is reached
→
Balancing period for [TDF415] seconds
●
Electric expansion valve
Unit being stopped :
[FULL CLOSE] 30 seconds after balancing period has passed
→
[FULL CLOSE] during reversing cycle period
→
[PCLOSH] 15 seconds
before balancing period is finished.
Unit being operated :
[DFCTPS] 30 seconds before balancing period is finished
→
Synchronized with step-up of rotation speed of compressor, opened
by [DFSPPS] pulses and reaches MAX opening degree [DEFSMX]
when rotation speed of compressor reaches [DEFMAX].
Summary of Contents for RAM-18QH5E
Page 9: ... 8 ...
Page 10: ... 9 RAM 18QH5E MODEL RAM 18QH5E ...
Page 11: ... 10 ...
Page 12: ... 11 AC 220V 240V ONLY L N INDOOR 1 C1 D1 C2 D2 INDOOR 2 RAM 18QH5E ...
Page 13: ... 12 RAM 18QH5E ...
Page 21: ... 20 MODEL RAM 18QH5E WIRING DIAGRAM OUTDOOR UNIT ...
Page 23: ...PRINTED WIRING BOARD LOCATION DIAGRAM MODEL RAM 18QH5E 23 MOUNTING PCB SET TYPE ...
Page 25: ... 27 heating ff BASIC MODE MODEL RAM 18QH5E ...
Page 28: ... 33 Table 6 Table 7 ...
Page 29: ... 35 ...
Page 31: ... 37 ...
Page 56: ... 62 Fig 11 2 ...
Page 69: ... 75 1 Outdoor unit does not operate remote control signal can be received RAM 40QH5 ...
Page 71: ... 77 Lighting mode self diagnosis lamp 2 RAM 18QH5E ...
Page 72: ... 78 TROUBLESHOOTING OF THE SYSTEM POWER MODULE ...
Page 73: ... 79 ...
Page 74: ... 80 ...
Page 75: ... 81 ELECTRIC EXPANSION VALVE PIPE THERMISTOR POSITION CHARTS MODEL RAM 18QH5E ...
Page 78: ...HITACHI PM NO 0276E Printed in Malaysia RAM 18QH5E ...