CHECKING THE INDOOR/OUTDOOR UNIT ELECTRICAL PARTS AND REFRIGERATING CYCLE
Model RAK-25NH4 / RAC-25NH4
RAK-35NH4 / RAC-35NH4
RAK-50NH4 / RAC-50NH4
Does the timer lamp on the indoor unit blink?
Is the compressor in the outdoor unit operating?
Does the operation lamp on the indoor unit
start to light or blink?
Remove the outdoor unit cover and
electrical parts cover, and check
self-diagnosis lamp LD301
Does LD301 blink one time ?
* Repeats 0.25-second on and
2-second off.
Blinking other than
one time
One-time blinking
Yes
Yes
Yes
Yes
No
No
No
Normal
No
No
Timer
lamp
Press the service switch for 1 sec.
Does the compressor operate?
(After checking, be sure to press
the service switch to stop the
operation).
Check the refrigerating cycle.
Check the outdoor electrical parts.
Check the indoor electrical parts.
Check to see whether the F-
cable is connected incorrectly
or disconnected
See “Out door unit self-diagnosis lamp
lighting mode”.
See “Troubleshooting when the timer lamp
blinks”.
Is approx. DC 33 to 37V being generated? Is the
polarity correct?
Remove the terminal cover and check the voltage
between terminal (C) and terminal (D)
Service switch
P.W.B
Self diagnosis lamps
(LD303, 302, 301)
CN17
IC3
022527
Terminal C
(+35V)
Terminal D
(0V)
Summary of Contents for RAC25NH4
Page 37: ...CIRCUIT DIAGRAM MODEL RAK 25NH4 RAK 35NH4 RAK 50NH4 37 ...
Page 38: ...CIRCUIT DIAGRAM MODEL RAC 25NH4 RAC 35NH4 RAC 50NH4 39 ...
Page 40: ... 42 MODEL RAC 25NH4 RAC 35NH4 RAC 50NH4 MAIN P W B Marking on P W B COMPONENT SIDE ...
Page 90: ... 100 SELF DIAGNOSIS LIGHTING MODE MODEL RAC 25NH4 RAC 35NH4 RAC 50NH4 ...