background image

   Preparation of Pipe

1

Use a pipe cutter to cut the copper pipe.

Jagged edge will cause leakage.

Point the side to be trimmed downwards during trimming to prevent copper chips from entering the pipe.

Before flaring, please put on the hexagon screw cap.

   Pipe Connection

2

INST

ALLA

TION OF REFRIGERA

TING PIPES AND AIR REMO

VA

L

CAUTION

!

Outer

diameter

of pipe (ø)

6.35 (1/4")

9.52 (3/8")

Valve head cap

Valve core cap

Torque N.m

(kgf 

 cm)

13.7 – 18.6 (140 – 190)

34.3 – 44.1 (350 – 450)

19.6 – 24.5 (200 – 250)

12.3 – 15.7 (125 – 160)

Outer

Diameter (ø)

6.35 (1/4")

9.52 (3/8")

Imperial flaring tool

0.8 – 1.5

1.0 – 1.8

Rigid flaring tool

0 – 0.5

0 – 0.5

A (mm)

Small diameter side

Big diameter side

Please be careful when bending the copper pipe.

Applied frozen grease to the connection points and then screw in manually.
After that, use a torque wrench to tighten the connection.

Hexagon Screw Nut

Spanner

Torque Wrench

A

   Installation Of Drain Hose

2

CAUTION

!

You are free to choose the side (left or right) for the installation of drain hose. Please ensure the
smooth flow of condensed water of the indoor unit during installation. (Carelessness may result in water
leakage.)

!

CAUTION

Be sure that the drain
hose is not loosely
connected or bent.

OUTDOOR UNIT

Please mount the Outdoor unit on stable ground to prevent vibration and increase of noise level.

Decide the location for piping after sorting out the different types of pipe available.

Procedure to remove the cover of wiring terminals

Remove the screw (1 piece).

Hold the projected part at the lower left of the cover and push the cover
upwards to remove it.

To close the cover, insert the upper part of the cover into the body of outdoor
unit, then be sure that the hook below the cover is plugged in before screwing.

Please Face This Side
(suction side) Of The
Unit To The Wall

Please Remove The Cover For Wire Connection

Hook

   Removal Of Air From The Pipe And Gas Leakage

1

AIR REMO

V

A

L

Gas Leakage Inspection

Please use gas leakage detector to check if leakage occurs at the
connection of Hexagon screw nut as shown on the right.

If gas leakage occurs, further tighten the connection to stop leakage.

Procedures of using Vacuum Pump for Air Removal

As shown in figure on the right, remove
the cap of valve head and valve core
and then connect them to the vacuum
pump and sub-division valve.

Fully tighten the “Hi” shuttle of the sub-
division valve and completely unscrew
the “Lo” shuttle. Run the vacuum pump
for about 10–15 minutes, then completely
tighten the “Lo” shuttle and switch off
the vacuum pump.

2

Completely unscrew the spindle of the
service valve (at 2 places) in anti-
clockwise direction to allow the flow of
coolant (using Allen key).

3

Remove the connection pipe and tighten
the cap of valve head. The task is then
completed.

4

1

The Body Of
Service Valve

Cap Of Valve
Core

Allen Key

Cap Of Valve Head

Cap Of Valve Head

CONNECTION OF PO

WER CORD

The naked part of the wire core should be 14 mm and the insulated part of the wire must be push into
the terminal for 3 – 4 mm. Then try to pull the individual wire to check if the contact is tight. Improper
insertion may burn the terminal.

Be sure to use only wire specified for the use of air-conditioner.

Please refer to the installation manual for wire connection and the wiring technique should meet the
standards of electrical installation.

There is a AC voltage drop between the A, B terminals if the power is on. Therefore, be sure to remove
the plug from its socket.

THIS APPLIANCE MUST BE EARTHED.

WARNING

!

WARNING

!

Power supply shall be connected at the rated voltage, otherwise the unit will be broken or could not reach the
specified capacity.

Procedures of Wiring

Detail of cutting the connecting cord

To remove the connecting wires for the
indoor unit, please remove the low cover
panel in front of the unit.

 

 

Brown (L)

Blue (N)

Green & Yellow

Line Cord

Indoor Unit

Outdoor Unit

AC 220-240V

Connecting Cord

Thermistor Wire

Indoor Unit

Outdoor Unit

GRN + YEL

GRN + YEL

Strip Wires

Trimming Tool

Copper Pipe

Mould

Mould

Copper Pipe

Bending
Upwards

Condensed
Water Pond

Ditch

Condensed Water
Pond

<

I719: A 

>

When the meter reaches - 101KPa
(-76cmHg) during pumping, fully tighten
the shuttle.

Meter showing pressure

Closed

Manifold valve

Vacuum pump

Valve

Charge hose

Valve

Vacuum
pump
adapter

When pumping starts, slightly loosen the flare
nut to check of air sucked in. Then tighten the
flare nut.

Lo

Hi

Summary of Contents for RAC-R10EX

Page 1: ...power wireless systems The installation height of indoor unit must be 2 3m or more CAUTION Do not expose the unit under direct sunshine or rain Besides ventilation must be good and clear of obstruction The air blown out of the unit should not point directly to animals or plants The clearances of the unit from top left right and front are specified in figure below At least 2 of the above sides must...

Page 2: ...he possibility of damaged by mouse CAUTION 2 5mm Protection pipe Outdoor Indoor Seal with putty Sleeve of protection pipe WALL INDOOR UNIT Transform the piping while holding down the lower portion of pipe support by hand Drain Hose Drain Cap Wrap With The Tape Hanger Refrigerating Pipe Projection Pipe Drain Hose Two Way Air Exchange Hose Connecting Cord Hanger Projection Drain Hose Visible Outline...

Page 3: ...e connection to stop leakage Procedures of using Vacuum Pump for Air Removal As shown in figure on the right remove the cap of valve head and valve core and then connect them to the vacuum pump and sub division valve Fully tighten the Hi shuttle of the sub division valve and completely unscrew the Lo shuttle Run the vacuum pump for about 10 15 minutes then completely tighten the Lo shuttle and swi...

Page 4: ...ap Please tie the pipe and power line together with plastic tape as shown in the figure of installation of both the indoor and outdoor units Then fix their position with holders To enchance the heat insulation and to prevent water condensation please cover the outdoor part of the drain hose and pipe with insulation pipe Completely seal any gap with putty Insulation Material For Pipe Connection Sle...