Notes:
(1) Hot dash is engaged if the difference between the room temperature and set temperature is equal to that between the room temperature, at which the compressor reaches maximum speed, and set temperature (△TWMAX), and the room and outdoor
temperatures are less than 10℃; when the fan speed is "auto", operation is started at "Hi", or the fan speed is changed to "Hi" during heating.
(2) The maximum compressor speed period during hot dash is finished ① when the room temperature reaches the heating set temperature (including heating shift) plus SFTDSW or ② when the thermo is off.
(3) The thermo OFF temperature during hot dash is heating set temperature (including heating shift) plus 3℃. After thermo OFF, hot dash finishes, and fuzzy control starts.
(4) The compressor minimum ON time and minimum OFF time is 3 minutes.
(5) The time limit for which the maximum compressor speed (WMAX) or (WMAX2) during normal heating (except for hot dash) can be maintained is less than 120 minutes when the room temperature is 18℃ or more; it is not provided when the room
temperature is less than 18℃ and outdoor temperature is less than 2℃.
(6) The operation indicator blinks every second during initial cycle operation, preheating, defrosting (including balance time after defrosting is finished), or auto fresh defrosting.
(7) For preheating judgment, preheating starts if the heat exchange temperature is lower than YNEOFC and is cancelled if the heat exchange temperature is YNEOF plus 0.33℃ or higher at the start of operation using the START / STOP button.
(8) During the operation at the fan speed of "Lo" or "Silent", the compressor speed is set to WBEMAX or below. It is restricted to WJKMAX or below when the fan speed is "Med".
(9) If the outdoor temperature (data from outdoor unit) is 6℃ or more, the maximum compressor speed is WSTD.
(10) If the room temperature falls to less than 18℃ in the "Ultra-Lo" mode, the indoor fan stops. When the room temperature is 18℃+0.33℃ or more, the ultra-Lo operation restarts. However, the ultra-Lo operation during preheating or preheating after
defrosting does not stop if the room temperature is less than 18℃.
(11) WMAX2 is used as the maximum compressor speed during hot dash, when the outdoor temperature is less than -5℃.
(12) With thermo OFF or in approximately 1 minute after operation is stopped using the remote controller, the fan operates in the "Ultra-Lo" mode.
This operation is for discharging heat from the indoor unit.
%^$%kk
%]^$
]&?]`^
]&?]`^
– 57 –
Summary of Contents for RAC-35NX2
Page 2: ... JZ Z DANGER ...
Page 39: ... q q _ q C O N T R O L P W B q G J q Z q q q j J G q G G RAF 35NX2 RAC 35NX2 OUTDOOR UNIT 38 ...
Page 49: ... 48 button MODEL RAF 35NX2 BASIC MODE 29 31 31 31 35 33 ...
Page 57: ... k k k kQ Q Q Q Q k k k k Q Q k k Q Q Q Q Q Q Q Q 56 ...
Page 59: ... k k re re Q Q Q Q k kQ k kQ k k Q Q Q Q Q Q k k k kQ k k Q k kQ Q Q Q Q k k k k k k 58 ...
Page 62: ...SUCTION TANK SUCTION TANK 61 ...
Page 63: ... 2 6 ...
Page 64: ... 63 ...
Page 66: ... 8 0 5 5 5 7 78 65 ...
Page 67: ... 9 B D D 5 7 78 66 ...
Page 68: ... E G E G E G 8 5 5 8 5 5 7 67 ...
Page 69: ... JE DK JE DK JE DK 5 5 L 8 5 5 7 68 ...
Page 70: ... 5 5 7 D 69 ...
Page 71: ... 5 5 7 Q B Q B 70 ...
Page 72: ...D 8 T 7 D W T 71 ...
Page 73: ... 5 T X 5 X Y X 7 X W 5 T Z X 0 Z 9 8 72 ...
Page 130: ... Z Z _Z Z _Z Z RA RAC F 35NX2 35NX2 129 ...
Page 131: ... Z _Z Z _Z RA RAC F 35NX2 35NX2 130 ...
Page 132: ... Z 131 ...
Page 133: ... Z 132 ...
Page 134: ... Z 133 ...
Page 135: ... 134 ...
Page 136: ... 135 ...
Page 137: ... 136 ...
Page 142: ... 141 ...
Page 143: ... _ 14 2 ...
Page 144: ... 1 RAF 35NX2 143 ...
Page 150: ... ª CN11A CN6 CN4 CN3 CN1 CN10 CN7 CN16 561 820 MODEL RAF 35NX2 RAC 35NX2 149 ...
Page 154: ... 0 45 6 65 0 1 45 5 450 1 0 69 0 153 ...
Page 155: ... 0 45 6 65 8 5 8 0 5 8 8 5 5 5 45 5 4 50 0 6 9 7 7 7 7 7 7 7 7 154 ...
Page 156: ... 0 9 0 1 0 0 45 65 5 4 6 4 6 0 6 澎 潦 2 3 4 155 ...
Page 157: ... 0 9 0 5 5 0 0 4 5 6 5 5 5 7 7 7 4 6 4 6 0 7 6 7 7 7 8 8 澎 潦 2 3 4 156 ...
Page 159: ... 0 5 5 8 7 9 0 5 30 6 5 0 5 8 0 4 5 5 4 5 4 5 6 5 7 7 7 7 7 158 ...
Page 160: ... 4 7 7 0 7 77 0 7 7 0 4 8 0 7 7 4 0 7 7 7 0 7 7 0 7 9 7 0 159 ...
Page 161: ...9 8 4 9 7 0 9 9 77 0 9 0 9 8 4 8 0 9 9 4 0 9 9 9 9 0 9 0 8 8 8 8 0 8 8 160 ...
Page 194: ...AW NO 0035EF RAF 35NX2 RAC 35NX2 ...