– 97 –
TROUBLE SHOOTING
Model
RAK-25NH5 / RAC-25NH5
RAK-35NH5 / RAC-35NH5
PRECAUTIONS FOR CHECKING
Power source
+
~
+
–
~
A
CT Module
+
–
+
–
N
C
D
L
Compressor motor
System power module 2
Indoor unit
electric parts
Control
P.W.B.
DC35V
0V
(0V)
MAIN P.W.B.
P
o
w
er module
a
b
M
1. Remember that the
0V line is biased to
155-170V in
reference to the
ground level.
2. Also note that it takes
about 10 minutes
until the voltage fall
after the power switch
is turned off.
DANGER
Across a – b (0V line)....................
Across a – ground..........................
Across b (0V line)– ground............
approx 260-360V
approx 155-170V
approx 155-170V
When using an
oscilloscope, never
ground it. Don't forget
that high voltages as
noted above may
apply to the
oscilloscope.
DANGER
Always keep your hands
and metallic things away
from the enclosure of the
oscilloscope.
DANGER!
Don’t install
the ground
line.
Oscilloscope
Outdoor unit P.W.B.
Summary of Contents for RAC-25NH5
Page 31: ... 29 MODEL RAK 25NH5 RAK 35NH5 ...
Page 37: ...CIRCUIT DIAGRAM MODEL RAK 25NH5 RAK 35NH5 37 ...
Page 38: ...CIRCUIT DIAGRAM MODEL RAC 25NH5 RAC 35NH5 39 ...
Page 40: ... 42 MODEL RAK 25NH5 RAK 35NH5 RECEIVING P W B Marking on P W B ...
Page 41: ... 43 MODEL RAC 25NH5 RAC 35NH5 MAIN P W B Marking on P W B COMPONENT SIDE ...
Page 53: ... 64 ...
Page 54: ... 65 ...
Page 55: ... 66 ...
Page 56: ... 67 ...
Page 90: ... 101 SELF DIAGNOSIS LIGHTING MODE MODEL RAC 25NH5 RAC 35NH5 ...
Page 92: ... 103 2 Outdoor unit does not operate but receives remote infrared signal ...
Page 94: ... 105 6 Check the main P W B power circuit ...
Page 95: ... 106 CHECKING THE REMOTE CONTROLLER ...
Page 100: ... 111 ...
Page 106: ... 117 PARTS LIST AND DIAGRAM INDOOR UNIT MODEL RAK 25NH5 RAK 35NH5 ...
Page 112: ...HITACHI PM NO 0324E Printed in Malaysia RAK 25NH5 RAC 25NH5 RAK 35NH5 RAC 35NH5 ...