– 37 –
Operation mode
Control function
Cooling
Sensor dehumidi
cation
Circulation
1
ON / OFF switch,
basic mode
2
Timer
operation
ON timer
OFF timer
Automatic
MED
LO
HI
O
Operation in “HI” mode
●
Operation in “MED” mode
●
Operation in “LO” mode
●
Same as on the left.
●
Same as on the left.
●
Same as on the left.
●
Only circulation with cut velocity
is executed, independent of the
thermostat signal.
(1) Strong
3
Fan speed
mode
Thermostat operation
H
A
HI
M
A
MED
L
A
LO
●
The power relay is
delayed by 2 seconds
from the start of
thermostat.
(1) In case of “Automatic” mode
Note:
●
The min. ON time of the power relay is 3
minutes, and the min. OFF time also is
3 minutes.
(2) In other modes than “Automatic”
Same as above (but operation is made
with the velocity set at the time of operation
start).
●
“HI”, “MED”, or “LO” operation is executed
according to the thermostat signal. (Refer to
“Thermostat operation”.)
●
“LO” and “Stop” are repeated according to the thermostat signal, independent
of the setting.
Notes:
●
Forced operation by ON / OFF
button ON is executed even
with thermostat OFF.
●
The room temperature 30 sec
after operation start, minus
0.66 deg, becomes the set
temperature.
●
When the room temperature
is 16°C or lower, 16°C
becomes the set temperature.
●
The other operations are the
same as for (1).
●
Repetition of “HI” and “Stop” by means of thermo signal and time.
●
Repetition of “MED” “Stop” by means of thermo signal and time.
●
Repetition of “LO” “Stop” by means of thermo signal and time.
(2) Set temperature is higher than room temperature.
(1) When the set temperature is lower than the room temperature.
4
BASIC MODE
MODEL RAS-18G5/RAC-18G5
Notes:
●
The min. ON time of the power relay is 3 minutes, and the min. OFF time
also is 3 minutes.
●
The indoor fan is not delayed with operation start by ON / OFF button.
No.
K
Both operation lamp during Sensor dehumidi
cation at
operation mode.
Summary of Contents for RAC-18G5
Page 29: ... 27 MODEL RAC 18G5 ...
Page 33: ... 31 CIRCUIT DIAGRAM Remote Control ...
Page 34: ... 33 PRINTED WIRING BOARD LOCATION DIAGRAM MODEL RAS 18G5 ...
Page 35: ... 35 BLOCK DIAGRAM MODEL RAS 18G5 RAC 18G5 ...
Page 39: ... 43 REFRIGERATING CYCLE DIAGRAM MODEL RAS 18G5 RAC 18G5 ...
Page 51: ... 55 PARTS LIST AND DIAGRAM OUTDOOR UNIT MODEL RAC 18G5 ...
Page 53: ...PM NO 0485E Made in Malaysia RAS 18G5 RAC 18G5 ...