Hitachi RAC-112SQB Installation Manual Download Page 6

(Unit: mm) 

Two or More Units   

(over and under) 

Two or More Units   

(over and under) 

Two or More Units   

(side by side and over and under)

Two or More Units   

(side by side and over and under)

No obstruction on sides 

and above 

 

Obstruction in front of the 

air outlet 

 

No obstruction on sides and 

above 

Obstruction in front of the air 

outlet 

 

(2) Installation locations 

…

1)  Dry and well-ventilated locations. 

…

2)  Do not expose the unit under direct sunlight and to heat sources. Use a shade when direct sunlight is unavoidable.   

…

3)  Make sure the noise from unit operation does not disturb neighbors (noise at the back (air inlet) is about 3dB higher). 

…

4)  Do not directly ventilate air from the unit to ornamental plants or the window of neighbors. 

…

5)  Do not install the heat exchanger in places where dust or scrap paper can enter easily. Add a wind guard (see below) 

as necessary to deflect wind. 

…

6)  Avoid installing the unit in places with headwind. Add a wind guard when installing in places with strong wind. 

…

7)  Pay attention to the following items during installation: 

1.

 

To prevent the outdoor unit from falling, shaking, and producing noise in a strong wind or an earthquake, install 
the unit using appropriate methods. Determine the required installation strength by calculating the seismic strength. 
Do not install the unit at locations where strong wind may blow off the roof or wall. Secure the unit with steel wire 
if necessary. 

2.

 

Add rubber cushions to the four legs of the unit stand. 

3.

 

The location should be convenient for draining rainwater and condensate from defrosting. For good drainage, the 
outdoor unit should be installed in places with draining facilities. (When installing under roofs where condensate 
drips, this may wet the floor to cause fall in winter.) Also, using central draining pipes is easier. (In frigid zones, 
condensate from defrosting may freeze easily in winter, do not use central draining pipes.) 

4.

 

Legs of the unit must be installed on a robust stand of about 100-300mm tall. 

 

  Installation in Places with Strong Winds   

 
Follow the instructions below when installing the unit on the roof with strong winds in the absence of obstruction. 
 
•  Do not face the air outlet toward 

headwinds. This will interfere with air 
ventilation from the unit and damage 
the unit. 
 

 

 

Attention 

When strong winds continuously blow 
toward the air outlet, the ventilation fan 
will rotate in reverse and become 
damaged. 

•  When installing the unit 

with the air outlet facing 
headwinds. 
1. When add a wind guard

 

 

 
Optional wind guard 

Model Q’ty 

WSP-160A 1 

 

 

2.  When there is a wall 

Keep at least 600mm from the wall.

 

 
 

 

400+

250+

400+ 

1000+

400+

250+

250+

400+

1000+

Strong wind

Strong wind

Wall

Wind direction 

Air out 

Air inlet   
 
Face the air outlet 
toward the wall or 
wind shelter. 

Optional wind guard

Summary of Contents for RAC-112SQB

Page 1: ...or animals directly under the airflow as it is bad for them As light will affect signal receiving of the remote control keep the signal receiver at least one meter away from lights to ensure signal receiving of the wireless remote control Temperature Ranges of Use Condition Function Indoor Unit Air Temperature Outdoor Unit Air Temperature Air conditioning 5ºC DB to 43ºC DB 21ºC DB 15ºC WB to 32ºC ...

Page 2: ...lso always wear leather gloves before handling refrigerant to prevent frostbite of the hand or the body Clean up refrigerant with non flammable non toxic cleaning agents only Use of flammable cleaning agents may cause explosion or fire Ensure adequate ventilation when working in confined spaces to prevent oxygen insufficiency When cleaning agents are exposed to sparks at a high temperature toxic g...

Page 3: ...ench y 2mm larger than the Φ12 7 or Φ15 88 wrenches for use on R410A pipes Not suitable for use on the pipes of currently used refrigerants For locking cap nuts y Φ6 35 and Φ9 53 wrenches can also be used Welder y Weld pipes as instructed flame adjustment welding temperature and choice of welding materials For welding refrigerant pipes Nitrogen y Strictly prevent dust from entry Following the nitr...

Page 4: ...7 0 8 O 0 8 O 0 8 O Φ15 88 1 0 O 1 0 O 1 0 O Φ19 05 1 0 O 1 0 O 1 0 1 2H Φ22 2 1 2 O 1 15 O 1 0 1 2H Φ25 4 1 2 O 1 0 1 2H 1 0 1 2H Φ28 6 1 4 O 1 0 1 2H 1 0 1 2H Φ31 75 1 4 O 1 1 1 2H 1 1 1 2H Φ38 1 1 65 O 1 15 1 2H 1 35 1 2H Connector Selection The wall thickness of connectors elbows and tubing must be changed according to the design pressure change As 1 2H parts cannot be bend or expanded select ...

Page 5: ...PSW3 switches on the mainboard of outdoor unit for three seconds 2 3 Outdoor unit installation 1 Installation space Retain maintenance space for the outdoor unit as shown below unit mm Standalone Standalone Standalone Two or More Units side by side No obstruction above No obstruction on sides and above Obstruction in front of the air outlet Even both sides are clear of obstruction maintain at leas...

Page 6: ... Do not install the unit at locations where strong wind may blow off the roof or wall Secure the unit with steel wire if necessary 2 Add rubber cushions to the four legs of the unit stand 3 The location should be convenient for draining rainwater and condensate from defrosting For good drainage the outdoor unit should be installed in places with draining facilities When installing under roofs wher...

Page 7: ...on A when using this type of anchor bolts Otherwise it will be difficult to remove the pipe cover 5 Securely fix the outdoor unit on the foundation to prevent collapse in a strong wind or an earthquake or noise due to loss of level leaning aside 6 When using ordinary frames whose legs are narrower than the legs of the outdoor unit add a board under the legs of the outdoor unit as shown in the figu...

Page 8: ... When the outdoor unit is higher than the indoor unit 30 30 When the outdoor unit is lower than the indoor unit 20 20 2 Refrigerant pipe size Indoor unit Outdoor unit Capacity Level Refrigerant Pipe Size mm Gas Side Liquid Side 112 125 140 160 Φ15 88 Φ6 35 Φ9 53 Refrigerant Pipe Size mm Gas Side Liquid Side Φ15 88 Φ9 53 The diagram shows one outdoor unit with four indoor units In this example only...

Page 9: ...ceptor valve on the pipe union Ⓐ in the right diagram of the gas interceptor valve Follow the instructions below Operation Air Conditioner Pipe union Ⓐ on the gas interceptor valve Low pressure Pipe union Ⓑ on the liquid interceptor valve Filling refrigerant after evacuation or repair Note After removing the filling hose prevent refrigerant and refrigeration oil from contaminating the electrical p...

Page 10: ...ing the unit put back the pipe cover afterwards Wrap pipes with insulation sheets prepare on site before penetrating pipes through the cap hole to ensure it is seamless Make sure that there is adequate space for putting back the pipe cover Panel removal direction Rear piping Pipe cover Front piping Right piping Bottom piping cover y As shown in the left diagram pipes can be installed in four locat...

Page 11: ...wards 5 Make sure to check leakage with a leakage detector and bubbles Do not use bubble liquids containing NH3 Recommended bubble liquids for the leakage test tabulated below Do not use general household detergents in the bubble test 2 Refrigeration filling 1 The unit has been equipped with refrigerant before shipping If pipes are longer than the design range add suitable amount of refrigerant on...

Page 12: ...below W additional refrigerant L l x P L Pipe length l Standard pipe length 30m P Compensational value 60g m Example L 34m L l 34 30 4m Additional quantity of refrigerant W L l x P 4m x 60 g m 240g 3 Fill in the additional quantity of refrigerant W calculated in 2 3 5 Recovering Refrigerant Follow the steps below to recover refrigerant from the outdoor unit before relocating the indoor and or outd...

Page 13: ...VVS KPEV S are used for connecting the operation circuit of the indoor and outdoor units earth with shielded wires Precautions for H LINK system connection y The factory setting of unit terminal impedance DSW5 1 ON is shown on the right diagram When more than two outdoor units are connected to the H LINK disabled the terminal impedance DSW5 1 OFF from the second outdoor unit onward Make sure that ...

Page 14: ... Selection Determine the rated current of the ELCB based on the total wiring capacity shown in the right table Determine the ELCB model sensed current and trip current based on the information shown in the right table Use high sensitivity high speed trip time 0 1 second ELCB Confirm the ELCB rated current sensitivity and trip time and protective coordination of the upper part Rated Current A ELCB ...

Page 15: ...ing the electrical panel for wiring or service to prevent electric shock Warning When installing the panel cover avoid jamming wires together to prevent electric shock and fire L1 1 L2 2 N Upper Right Panel Cover Earth cable Main power cable Operation circuit cable Keep an appropriate distance among terminals Insulate terminals with plastic tapes or bushings Plastic tapes or bushings Note Do not u...

Page 16: ...ubleshooting in p 19 Contact a service technician for help if the situation persists When the operation light blinks every 2 seconds repeatedly this means there is a signal transfer error between the indoor unit and the remote control wires are loosened or disconnected broken incorrect wiring etc y A giggle sound also comes out from the mechanical chamber of the outdoor unit after compressor start...

Page 17: ...igerant temperature Fluid pipe temperature ºC Compressor out temperature ºC 8 Refrigerant pressure Delivery pressure MPaG Intake pressure MPaG 9 Voltage Rated voltage V Operating voltage L1 N V L1 L2 V Start voltage V 10 Compressor input power and current Power kW Current A 11 Refrigerant filling level Correct Incorrect 12 Remote control functions Correct Incorrect 13 Protective device functions C...

Page 18: ... Settings of each input terminal should be different The value of settings greater than the default value is invalid Not in use Not in use Heating Mode Operation Signal Cooling Mode Alarm Signal Stop Request Compressor ON Signal Force Stop Defrost Signal Current Control 60 Current Control 70 Current Control 80 Current Control 100 Input Setup 1 CN1 Code 1 2 Input Setup 2 CN1 Code 2 3 Input Setup 3 ...

Page 19: ...t capacity mismatch Indoor unit capacity is 100 130 higher than the outdoor unit capacity 35 Indoor unit number setup error Repeated number setting or the number is greater than the connected number of indoor units 38 Protection check circuit error outdoor unit Error of the outdoor unit protection check circuit 41 Cooling overload high pressure switch activated When the outdoor unit protection act...

Page 20: ...66MP1382 RAC AG C ...

Reviews: