< Troubleshooting by using the self-diagnosis memory function>
·
By using the self-diagnosis memory function, you can check the failure mode (
Ć
1) occurring in the outdoor electrical
ǂ
parts on the indoor unit side.
Steps
1. Clear the troubleshooting data.
2. Run the product for several minutes under the conditions where the compressor runs.
3. Redisplay and check the data written in the self-diagnosis memory.
·
The self-diagnosis memory function can also be used to catch sporadic failure phenomena.
Steps
1. Clear the troubleshooting data.
2. Have the user use the product as usual until a failure phenomenon occurs.
ǂ
(The period depends on the incidence of the phenomenon.)
3. At a later date, redisplay and check the data written in the self-diagnosis memory.
·
For the outdoor self-diagnosis display (OH thermistor heat-up, overload lower limit cut) stemming from the freezing cycle
ǂ
or operating condition, the time lag is long from operation startup to the emergence of the phenomenon.
ǂ
Moreover, it is affected by the temperature, sunshine, operating hours, and other factors of the day, so that the
phenomenon may not be able to be identified at the time of a repair service visit. In that case too, use the self-diagnosis
memory function (
Ć
2).
·
The outdoor self-diagnosis display "overload lower limit cut" and "OH thermistor heat-up" can be identified only when you
are using the self-diagnosis lamp of the outdoor unit and the self-diagnosis memory function of the indoor unit.
Note that this will not be automatically displayed on the indoor unit side.
Initiating troubleshooting
Yes
Perform troubleshooting according to the
self-diagnosis display.
No
No
No
No
Ć
Ć
Ć
Are the "timer lamp" (orange) of the indoor unit
blinking?
The product will begin to run in response to a remote
control setting: "cooling mode, temperature setting 16
ć
"
(summer) or "heating mode, temperature setting 32
ć
"
(winter).
Has the "operation lamp" been turned on?
Yes
Yes
Yes
Check the indoor electrical parts.
Is the compressor running?
Turn off the power and turn on the power and
press the "forcible cooling" switch to operate the
product.
Has the compressor started to run?
Check the freezing cycle.
Check the outdoor electrical parts.
Diagnosis and troubleshooting of indoor electric parts, outdoor electric parts and refrigerating cycle
Summary of Contents for RAC-10WECI
Page 2: ... DANGER ...
Page 9: ... ...
Page 10: ... ...
Page 11: ... ...
Page 13: ... ...
Page 14: ... ...
Page 15: ... ...
Page 26: ...MODEL RA C 18 25 35 W EC RAC 10 14WECI ...
Page 27: ...MODEL RAC 50WEC RAC 20WECI ...
Page 41: ... MODEL RAK 50PEC RAK 20PECI RAC 50WEC RAC 20WECI 1 2 1 2 1 2 1 2 RAK 50PECC ...
Page 53: ...L N 300 330 Main parts C021 C022 375 420V L N 15 MODEL RAC 18 25 35WEC RAC 10 14WECI ...
Page 57: ...5 5 1 10 11 12 74 74 70 70 74 75 5 1 HIC P W B 74 70 75 ...
Page 59: ...2A Fuse DC300 330V 7 7 1 ...
Page 60: ...2A DC300 330V ...
Page 61: ...L N 300 330 L N MODEL RAC 50WEC RAC 20WECI ...
Page 62: ...300 330 C021 C023 500 450V 16V R249 33 ACT IP CUT 30 ...
Page 66: ...5 5 1 74 74 70 70 74 75 5 1 HIC P W B 40 41 42 74 70 75 ...
Page 68: ...2A Fuse DC300 330V 7 1 7 ...
Page 69: ...2A DC300 330V ...
Page 79: ...SELF DIAGNOSIS LIGHTING MODE MODEL RAC 18 25 35WEC RAC 10 14WECI ...
Page 80: ...SELF DIAGNOSIS LIGHTING MODE MODEL RAC 50WEC RAC 20WECI ...