Hitachi RAC-08CH9 Service Manual Download Page 51

– 54 –

While cooling, the
compressor sometimes stops
abruptly.

Q1

Check whether frost sticks
on the heat exchanger of in-
door unit or not.
Wait for 3 – 4 minutes until
the frost melts.

A1

If cooling is performance
when the room temperature
is low, frost may stick on the
heat exchanger of indoor
unit.

Cooling operation

The fan speed does not
change during a
dehumidifying operation.

Q2

Dehumidifying operation

The fan speed is always LO
at a dehumidifying operation.

A2

Cold air comes out during a
dehumidifying operation.

Q3

To improve the dehumidi-
fication efficiency, LO fan
speed operation is
performed. Therefore the air
is cold. This is not a trouble.

A3

The operation does not stop
even by raising the room
temperature setting of remote
control at a dehumidifying
operation.

Q4

At a dehumidifying operation,
the actual room temperature is
compared with the room tem-
perature setting when starting
the operation and the opera-
tion is as follows.
1) When actual room tem-

perature > room tempera-
ture setting.
The operation is according
to the room temperature
setting on the remote con-
troller.

2) * When actual room tem-

perature < room tempera-
ture setting
Regardless of the room
temperature setting, the
temperature is automati-
cally set slightly lower than
the room temperature.

In this case, the status is as 2)
and, therefore, the operation
by the room temperature
control is impossible. Turn off
the On / OFF switch, set the
room temperature to a new
value and turn on the opera-
tion by the On / Off switch.

A4

In the dehumidifying mode,
the temperature set by
remote controller is set
slightly higher than the room
temperature but the
operation starts.

Q5

This is the status in 2) of
(A4). The temperature is set
a little lower than the room
temperature to carry out a
dehumidifying operation as
far as possible.

A5

SERVICE CALL Q & A

Summary of Contents for RAC-08CH9

Page 1: ...PTION OF MAIN CIRCUIT OPERATION 49 AUTO SWING FUNCTION 53 SERVICE CALL Q A 54 PARTS LIST AND DIAGRAM 63 RAS 08CH9 RAS 08CH9 B RAC 08CH9 RAS 10CH9 RAS 10CH9 B RAC 10CH9 RAS 14CH9 RAS 14CH9 B RAC 14CH9 COOLING HEATING INDOOR UNIT RAS 08CH9 RAS 08CH9 B 780 280 220 9 0 After installation RAS 08CH9 RAS 08CH9 B RAS 10CH9 RAS 10CH9 B RAS 14CH9 RAS 14CH9 B RAC 14CH9 RAC 08CH9 RAC 10CH9 OUTDOOR UNIT RAC 8C...

Page 2: ... be accurately calibrated in advance 7 In installing the unit having been repaired be careful to prevent the occurence of any accident such as electrical shock leak of current or bodily injury due to the drop of any part 8 To check the insulation of the unit measure the insulation resistance between the power cord plug and grounding terminal of the unit The insulation resistance should be 1MΩ or m...

Page 3: ...of parts Even rejected goods should be handled in the same way Fig 1 Conductive Container 2 When any part is handled uncovered in counting packing and the like the handling person must always use himself as a body earth Make yourself a body earth by passing one M ohm earth resistance through a ring or bracelet 3 Be careful not to touch the parts with your clothing when you hold a part even if a bo...

Page 4: ...the screwed part using a rag plate Soldering iron Grounding wire Fig 4 Grounding a soldering iron Use a high insulation mode 100V 10M or higher when ordinary iron is to be used 7 In checking circuits for maintenance inspection or some others be careful not to have the test probes of the measuring instrument shortcircuit a load circuit or the like Metal plate of aluminium stainless steel etc Staple...

Page 5: ...n and re start in a moment there is occasion that the cooling and heating operation does not start for 3 minutes it is not abnormal and this is the result of the operation of IC delay circuit This IC delay circuit ensures that there is no danger of blowing fuse or damaging parts even if operation is restarted accidentally 5 This room air conditioner should not be used at the cooling operation when...

Page 6: ...Y FUSE THERMOSTAT REMOTE CONTROL SWITCH LIQUID CRYSTAL RAS 08CH9 RAS 08CH9 B RAS 10CH9 RAS 10CH9 B RAS 14CH9 RAS 14CH9 B 20 W NO NO NO NO NO 3 15A G4A YES YES YES NO 450NR YES IC YES 20 W 30 W 1 5µF 450 VAC 2 5µF 450VAC NO 20µF 450 VAC 30µF 450 VAC YES NO NO NO NO NO NO NO NO 10 A 15 A NO NO 1000g 10m UNIT MAX PIPES REFRIGERANT CHARGING VOLUME Refrigerant R22 RAC 08CH9 RAC 14CH9 RAC 10CH9 2RS127 2...

Page 7: ...learance as wide as possible above 50mm when installed on the ceiling of balcony above 200mm The indoor piping should be insulated with the enclosed insulation pipe If the insulator is insufficient please use commersial products The difference in height between the indoor and outdoor unit should be kept max 5m The connecting pipe no matter big or small should all be insulated with insulation pipe ...

Page 8: ...above 0 45m above 300mm must not bend above 100mm 2 300mm or more 1 2 Plug The difference in height between the indoor and outdoor unit should be kept max 5m The connecting pipe no matter big or small should all be insulated with insulation pipe and then wrapped with vinyl tape The insulator will deteriorate if it is not wrapped with tape The connection of insulated drain hose Please use insulated...

Page 9: ... outdoor unit may catch fire if flammable gas leaks around it Please ensure smooth flow of water when installing the drain hose CAUTION PRECAUTIONS DURING SHIFTING OR MAINTENANCE Should abnormal situation arises like burning smell please stop operating the unit and turn off the circuit breaker Contact your agent Fault short circuit or fire may occur if you continue to operate the unit under abnorm...

Page 10: ... amount of heat in the room is above the cooling or heating capability of the unit for example more people entering the room using heating equipments and etc the preset room temperature cannot be achieved This appliance is not intended for use by young children or infirm persons unless they have been adequately supervised by a responsible person to ensure that they can use the appliance safely You...

Page 11: ... pipe Condensed water drain to outside Connecting cord and insulation pipe for piping Air inlet Back Left side Air outlet Drain pipe Condensed water drain to outside Connecting cord and insulation pipe for piping Air inlet Back and Left side Air outlet WIDTH mm 780 700 750 MODEL RAS 08CH9 10CH9 14CH9 RAS 08CH9 B 10CH9 B 14CH9 B RAC 08CH9 10CH9 RAC 14CH9 HEIGHT mm 280 570 570 DEPTH mm 220 210 280 M...

Page 12: ...evice is operated for a total of about 100 hours the FILTER lamp lights to indicate that it is time to clean the filter The lamp goes out when the POWER SWITCH set to OFF and ON again OPERATION LAMP This lamp lights during operation The OPERATION LAMP flashes in the following cases during heating 1 During preheating For about 2 3 minutes after starting up 2 During defrosting Defrosting will be per...

Page 13: ...set the sleep timer TEMPERATURE buttons Use these buttons to raise or lower the temperature setting Keep pressed and the value will change more quickly TIME button Use this button to set and check the time and date RESET buttons FUNCTION selector Use this button to select the operating mode Every time you press it the mode will change from AUTO to HEAT to DEHUMIDIFY to COOL and to FAN cyclically F...

Page 14: ...tton Operation starts with a beep Press the button again to stop operation You can raise or lower the temperature setting as necessary by maximum of 3 C Press the temperature button and the temperature setting will change by 1 C each time The preset temperature and the actual room temperature may vary somewhat depending on conditions The display does not indicate the preset temperature in the AUTO...

Page 15: ... has been reached HI Economical as the room will become warm quickly But you may feel a chill at the beginning MED Quiet LOW More quiet Set the desired room temperature with the TEMPERATURE buttons the display indicates the setting The range of 18 22 C is recommended as the room temperature for heating If the temperature setting is 20 C the room temperature will be controlled at around 20 C The te...

Page 16: ...rdless of the temperature setting The function will stop the indoor unit will stop emitting air as soon as the room temperature becomes lower than the setting temperature Set the desired room temperature with the TEMPERATURE button the display indicates the setting The range of 20 26 C is recommended as the room temperature for dehumidifying Press the START STOP button Dehumidifying operation star...

Page 17: ...ATURE button the display indicates the setting The range of 25 28 C is recommended as the room temperature for cooling If the temperature setting is 27 C the room temperature will be controlled at around 27 C The temperature setting and the actual room temperature may vary some how depending on conditions Press the START STOP button Cooling operation starts with a beep Press the button again to st...

Page 18: ... and setting temperature is large fan starts to run at HI speed After room temperature reaches the preset temperature the cooling operation which changes the fan speed and room temperature to obtain optimum conditions for natural healthful cooling will be performed For the cooling operation FAN OPERATION You can use the device simply as an air circulator Use this function to dry the interior of th...

Page 19: ...EL button The RESERVED sign goes out with a beep and the TIMER lamp turns off on the indoor unit 1 Set the current month and day with the TIMER control button 1 Press the OFF TIMER button The OFF mark blinks on the display 1 Press the ON TIMER button the ON mark blinks on the display 2 Set the turn off time with the TIMER control button Press the RESERVE button 3 Press the ON TIMER button so that ...

Page 20: ...now complete Example The device will turn off at 11 00p m Example The device will automatically turn on earlier so that the preset temperature can be reached at 7 00 a m The setting of the turn on time is now complete 4Set the turn on time with the TIMER control button 5 Point the signal window of the remote controller toward the indoor unit and press the RESERVE button The ON mark starts lighting...

Page 21: ...roller The TIMER lamp lights with a beep from the indoor unit When the sleep timer has been set the display indicates the turn off time Example If you set 3 hours sleep time at 11 38 p m the turn off time is 2 38 a m 2 Press the SLEEP button and set the sleep timer The device will be turned off by the sleep timer and turned on by on timer How to Cancel Reservation Point the signal window of the re...

Page 22: ... temperature will be controlled 5 C below the temperature and the FAN SPEED will be set to LOW setting 60 minutes after the setting of the sleep timer Operation with the sleep timer Sleep timer set 60 minutes later 3 hours later 7 hours later 2 hours later 5 C If date or current time is not set sleep timer can not be set If you set the sleep timer after the off on off or off on timer has been set ...

Page 23: ...ion where the air outlet closes Vertical Vertical about 15 about 60 about 45 about 30 When cooling dehumidifying When heating CAUTION In Cooling operation do not keep the horizontal air deflector swinging for a long time Some dew may form on the horizontal air deflector and dew may drop RESET Adjustment of the conditioned air in the upward and downward directions The horizontal air deflector is au...

Page 24: ...t the old batteries 2 Install the new batteries The direction of the batteries should match the marks in the case 1 Do not use new and old batteries or different kinds of batteries together 2 Take out the batteries when you do not use the remote controller for 2 or 3 months CAUTION Push and pull to the direction of arrow ...

Page 25: ...with your wake up time in the morning This will enable you to enjoy a comfortable room temperature Please use the timer effectively Dusty air filter will reduce the air volume and the cooling efficiency To prevent from wasting electric energy please clean the filter every 2 weeks Please pay attention to the room temperature and air flow direction when operating the unit for baby children and old f...

Page 26: ...event interference place at least 1m away TV UV LED UV LED will be ON when the START STOP button is pressed except for FAN only operation During selected operation this UV LED will be ON and OFF Light UV glare is visible when the UV LED is ON and this is normal not malfunction Product Operating Life This term is valid only for the products being purchased on the territory of Russian Federation In ...

Page 27: ...nd maintenance must be carried out only by qualified service personal Before cleaning stop operation and switch off the power supply CAUTION Do not bend the air cleansing filter as it may cause damage to the structure NOTE In case of removing the air cleansing filters please follow the above procedures The cooling capacity is slightly weakened and the cooling speed becomes slower when the air clea...

Page 28: ...and gently brush it with soft bristle brush Allow filters to dry in shade 3 Re insert the air cleansing filter to the filter frame Set the filter with FRONT mark facing front and slot them into the original state After attaching the filters push the front panel at three arrow portions as shown in figure and close it CAUTION Do not wash with hot water at more than 40 C The filter may shrink When wa...

Page 29: ...ators or signal receiver of indoor unit it causes trouble Method of removing the front panel Be sure to hold the front panel with both hands to detach and attach it CAUTION Do not splash or direct water to the body of the unit when cleaning it as this may cause short circuit Never use hot water above 40 C benzine gasoline acid thinner or a brush because they will damage the plastic surface and the...

Page 30: ...nals in your plug proceed as follows The wire which is coloured green and yellow must be connected to the terminal in the plug which is marked with the letter E or by the earth symbol or coloured green or green and yellow The wire which is coloured blue must be connected to the terminal which is marked with the letter N or coloured black The wire which is coloured brown must be connected to the te...

Page 31: ...of refrigerant in the refrigerating cycle 2 Slight rubbing noise from the fan casing which is cooled and then gradually warmed as operation stops The odor will possibly be emitted from the room air conditioner because the various odor emitted by smoke foodstuffs cosmetics and so on sticks to it So the air filter and the evaporator regularly must be cleaned to reduce the odor Please contact your sa...

Page 32: ...Supply Companies are to be observed Minimum Maximum Minimum Maximum Indoor Dry bulb C 21 32 20 27 Wet bulb C 15 23 12 19 Outdoor Dry bulb C 21 43 2 21 Wet bulb C 15 26 1 15 Note Avoid to use the room air conditioner for cooling operation when the outside temperature is below 21 C 70 F The recommended maximum and minimum operating temperatures of the hot and cold sides should be as below Cooling He...

Page 33: ... pipes 3 Piping length is within 15m RAS 14CH9 RAS 14CH9 B 10m RAS 14CH9 RAS 14CH9 B RAS 10CH9 RAS 10CH9 B 4 Height different of the piping between the indoor unit and the outdoor unit should be within 5m 5 Power supply cord length is about 2m 6 Connecting cable 2 5mm dia x 3 AB Line 1 6mm dia x 2 CD Line is used for the connection D C B A L N D C B A Indoor Unit Outdoor Unit Connecting Cord ø1 6 ...

Page 34: ...AC 14CH9 Air outlet Handle Air inlet 18 490 Handle Viewed from P 157 245 225 8 10 500 35 12 16 55 570 428 700 243 53 236 210 10 482 517 135 75 77 P 500 12 37 124 57 165 56 28 750 852 76 570 95 166 559 26 16 280 195 280 15 10 340 340 10 320 ...

Page 35: ... 6 77 8 ON 33 3 91 9 34 0 93 2 OFF 32 7 90 9 34 6 92 2 MODEL RAS 08CH9 10CH9 14CH9 RAS 08CH9 B 10CH9 B 14CH9 B RAC 08CH9 10CH9 14CH9 PHASE RATEDVOLTAGE SINGLE RATED FREQUENCY DC35V 220 240V TEMPERATURE C F OUTPUT POLE NUMBER 6 20 W 20W 30W 30W 50 Hz 35V 5V RED YELLOW BLUE M BLACK CAPACITOR RA RED INTERNAL THERMAL FUSE GRAY RM RESISTANCE VALUE 20 C 75 C RM 344 2 RA 245 3 RM 263 0 RA 165 5 RM 250 0 ...

Page 36: ...E CAUTION When the Air Conditioner has been operated for a long time with the capillary tubes clogged or crushed or with too little coolant check the color of the refrigerant oil inside the compressor If the color has been changed conspicuously replace the compressor RM 4 794 RA 5 217 EXTERNAL OVERLOAD RELAY INTERNAL PROTECTOR YES NO ORANGE RM WHITE RA RED CAPACITOR R ORANGE S RED C WHITE RM 2 454...

Page 37: ... 34 WIRING DIAGRAM MODEL RAS 08CH9 10CH9 14CH9 RAS 08CH9 B 10CH9 B 14CH9 B RAC 08 10 14CH9 RAS 63CHA1 RAC 63CHA1 C1 C2 M1 M2 CN7 CN20 UV LED BOARD HEAT EXCHANGER THERMISTOR ...

Page 38: ...SEG1 SEG0 SEG43 SEG42 SEG41 SEG40 P40 P41 P42 P43 P00 P01 P02 P03 P10 P11 P12 P13 D0 D1 D2 D3 D4 D5 D6 D7 D8 D9 BEEP P20 P30 P31 NCVL C1 VL C2 VL C3 XC IN XC OUT VDD X OUT X IN RESET CARR P23 P22 P21 VSS IC 1 M3455OM6A 504FP LCD 1 C8 50v 1u K 1 D3 RB425D 1 2 K2K3 K4 K5 P10 P11 P12 K6 K7 K8 K8 K10 K11K12 K18 K17 K15 K16 K13 K14 D0 D1 D2 D3 R1 100k SW1 R2 P 100k R3 100k R4 100k R5 Q1 2SC3443 or 2SC2...

Page 39: ... 37 PRINTED WIRING BOARD LOCATION DIAGRAM MODEL RAS 08CH9 10CH9 14CH9 RAS 08CH9 B 10CH9 B 14CH9 B RAC 08CH9 10CH9 14CH9 ...

Page 40: ...LER ROOM TEMPERATURE THERMISTOR HEAT EXCHANGER THERMISTOR WIRELESS RECEIV ING CIRCUIT INDOOR FAN MOTOR OUTDOOR UNIT COMPRESSOR OUTDOOR FAN MOTOR RELAY POWER RELAY STICK RELAY REVERSING VALVE RELAY EXTERNAL FAN RELAY BUZZER CIRCUIT OPERATION TIMER FILTER INDICATION LAMP AUTO SWEEP MOTOR MICROCOMPUTER CLOCK CIRCUIT INITIALIZING CIRCUIT RESET CIRCUIT MICROCOMPUTER AX 3U M FM M F M REVERSING VALVE R V...

Page 41: ...utomatic L XL HI MED LO and Stop are repeated according to the thermostat signal and time HI MED LO and Stop are repeated according to the thermostat signal and time MED LO and Stop are repeated according to the thermostat signal and time LO and Stop are repeated according to the thermostat signal and time The Automatic speed mode for each operation mode is used independent of the setting Week at ...

Page 42: ... Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No Yes Yes Cooling Heating Item Operation switching Temporary switch Service switch Nice temperature reservation Automatic fresh defrosting Defrosting Pd cut 1 Pd cut 2 Pd cut 3 Heating load reduction External fan relay Reversing valve relay Reversing valve lock protection Sleep circuit Heater operation at the time of sensor dehumidification Automatic b...

Page 43: ... up time depending on the temperature difference from the table below 10 NICE TEMPERA TURE reservation Heating Cooling Setting temp Room temp Time min Setting temp Room temp Time min 00 01 00 00 00 00 02 00 00 01 25 03 00 10 02 25 05 00 15 03 25 07 00 20 05 25 08 00 30 07 25 10 00 30 08 25 11 00 45 10 25 13 00 40 11 25 60 13 25 16 00 50 16 25 19 00 60 19 25 22 00 60 22 25 The preset temperature va...

Page 44: ...CAPILLARY STRAINER CHARGING PIPE CONDENSER 3S VALVE EVAPORATOR THERMISTOR POSITION COMPRESSOR SUCTION TANK REVERSING VALVE MODEL RAS 10CH9 RAS 10CH9 B RAC 10CH9 CONDENSER 3S VALVE COMPRESSOR REVERSING VALVE 2S VALVE THERMISTOR POSITION STRAINER HEATING COOLING CAPILLARY STRAINER CHARGING PIPE EVAPORATOR ...

Page 45: ...MODEL RAS 14CH9 RAS 14CH9 B RAC 14CH9 COMPRESSOR SUCTION TANK REVERSING VALVE 4S VALVE ACCUMULATOR CONDENSER 2S VALVE THERMISTOR POSITION STRAINER HEATING COOLING CAPILLARY STRAINER CHARGING PIPE EVAPORATOR ...

Page 46: ...ion independently Their operations are shown in Fig 1 1 ON OFF button Timer reserve button Sleeping Operation lamp Timer lamp When OFF timer sleeping is set Start Stop Start OFF time When ON timer is set ON time ON OFF button Timer reserve button Operation lamp Timer lamp Stop Start Fig 1 1 Timer operation ...

Page 47: ...is turned ON the potential of Q511 s base rises and Q511 is turned ON Since Q511 s collector is set to LO at this time Q512 is turned OFF and the reset input of the micro computer is set to Lo The DC 5V line voltage has already become 5V at this time and the micro computer starts operation When the power is turned OFF the voltage of the DC 12V line decreases When it becomes about 7V ZD511 is turne...

Page 48: ...put 4kHz sound 4 Initial setting IC301 The pre heating operation start value ratings of the compressor maximum rotation speed etc are preset in the micro computer 5 Receive circuit Infrared signals from the wireless remote controller are received by the light receiving unit and output after being amplified and shaped 8 7 IC301 E 2PROM 6 5 5V 0V R302 Micro computer AX 3U 3 4 R305 5V C301 C302 D304 ...

Page 49: ...e room temperature turn on and off the disconnect switch To protect the compressor wait at least 3 minutes before turning on again The fan speed is MED Does not operate is 12V is not generated in the control circuit When the service switch is used for operation each change switch is overridden Setting the service switch to Cooling turns on the Stick relay and Power relay Micro computer AX 3U FORCE...

Page 50: ...MODE ONE SWING CLOSING AIR DEFLECTOR 1 DOWNWARD 2 UPWARD INITIALIZE 1 DOWNWARD INITIALIZE 1 DOWNWARD 2 UPWARD STOP AT THE MOMENT START SWINGING 1 DOWNWARD 2 UPWARD 3 DOWNWARD STOP AT THE MOMENT START SWINGING 1 DOWNWARD 2 UPWARD 3 DOWNWARD STOP AT THE MOMENT ONE SWING CLOSING AIR DEFLECTOR 1 DOWNWARD 2 UPWARD INITIALIZE AT NEXT OPERATION INITIALIZE AT NEXT OPERATION STOP DURING ONE SWING STOP DURI...

Page 51: ...the actual room temperature is compared with the room tem perature setting when starting the operation and the opera tion is as follows 1 When actual room tem perature room tempera ture setting The operation is according to the room temperature setting on the remote con troller 2 When actual room tem perature room tempera ture setting Regardless of the room temperature setting the temperature is a...

Page 52: ...peed followed by MED fan speed for 30 seconds and then by HI fan speed A8 Q7 The operation stops during a heating operation while the room temperature is set at 30 Q9 If a heating operation is per formed when the exterior temperature is high the op eration may stop to protect the equipment A9 The outdoor fan does not move at a heating operation by the service switch It is not a trouble When heatin...

Page 53: ... The room temperature cannot be controlled at an automatic operation Q14 It is automatically set as follows At cooling Set at 27 C At dehumidifying Set slightly lower than room temperature The room temperature setting can be raised 3 C by or lowered 3 C by V A14 When changing the room temperature setting in an automatic operation the next automatic operation mode is determined by new room temperat...

Page 54: ...ing the time setting A16 In the Automatic fan speed mode the indoor fan changes to MED and LO fan speed Q17 It is not a trouble The cold wind preventive function operates A17 Set the temporary switch normal In case of ON timer the operation does not start at a preprogrammed time but a little earlier Q18 Nice temperature reservation The Nice temperature reservation functions The operation starts ea...

Page 55: ...2 pressing causes no transmission either Q21 The room temperature is settable within the range of 16 32 and not beyond A21 The timer cannot be set Q22 Is the current time set The timer cannot be set unless the clock is adjusted correctly A22 V The current time disap pears soon Q23 The current time disappears soon and the timer settting indication takes a precedence A23 When setting the current tim...

Page 56: ...the time over the pre programmed time As soon as the prepro grammed time is reached the time setting disappears A24 After selecting a Dehumidifying operation mode the fan speed mode remains LO fan speed Q25 At a Dehumidifying operation the LO fan speed is forcibly selected A25 ...

Page 57: ...no continuity check the electric parts and replace if abnormal 5 Thermal fuse for Terminal board 2 Before checking the varistor detach a terminal NO Operates by setting the service switch to forced cooling Return the service switch to Normal Set the remote controller to an operation status and press the ON OFF button Is the level LO approx 0 5V between driver IC701 pin 11 power relay and 0V NO NO ...

Page 58: ...or indicator lamp Fan Speed RAS 08CH9 RAS 08CH9 B RAC 08CH9 3 Replace faulty part 4 Wait for 3 minutes before forced re operation by the service switch CN6 BLUE RED V Cool Heat 20 8 17 2 14 1 11 0 20 8 17 9 15 0 13 0 HI MED LO SLEEP MODE RAS 10CH9 RAS 10CH9 B RAC 10CH9 RAS 14CH9 RAS 14CH9 B RAC 14CH9 Cool Heat 21 3 19 0 15 6 11 9 23 0 19 7 16 6 15 0 Cool Heat 26 5 22 2 18 0 13 0 28 4 23 6 19 3 15 ...

Page 59: ...peration Unit is under forcible operation or under balancing after forcible operation Check force cooling switch at indoor electrical IC 401 Data read wrongly In case that data read from IC401 is wrong IC401 data is not in order Heat exchanger thermistor error Heat exchanger thermistor open or short circuit detected 1 Thermistor 2 Indoor control circuit board Room thermistor error Room thermistor ...

Page 60: ... 63 PARTS LIST AND DIAGRAM INDOOR UNIT MODEL RAS 08CH9 RAS 10CH9 RAS 14CH9 RAS 08CH9 B RAS 10CH9 B RAS 14CH9 B 1 12 15 14 20 21 25 11 10 7 19 18 12 16 17 6 22 8 5 4 3 9 2 13 23 24 ...

Page 61: ...H4 S29 1 AUTO SWEEP MOTOR 12 PMRAS 08CH9 R02 1 FRONT COVER ASSY 13 PMRAS S10CY 004 1 FRONT PANEL 14 PMRAS 08CH8 008 1 AIR FILTER R 15 PMRAS 08CH8 009 1 AIR FILTER L 16 PMRAS 51CHA1 R11 1 REMOTE CONTROL ASSEMBLY 17 PMRAS 10C3M 003 1 REMOTE CONTROL SUPPORT 18 PMRAS 25YH4 S15 1 SPRING 19 PMRAS 260GHA R01 1 THERMISTOR 20 PMRAS 08CH9 R01 1 P W B MAIN AND INDICATION 21 PMRAS 07GH4 R04 1 P W B POWER SW S...

Page 62: ...H4 S29 1 AUTO SWEEP MOTOR 12 PMRAS 08CH9 R02 1 FRONT COVER ASSY 13 PMRAS S10CY 004 1 FRONT PANEL 14 PMRAS 08CH8 008 1 AIR FILTER R 15 PMRAS 08CH8 009 1 AIR FILTER L 16 PMRAS 51CHA1 R11 1 REMOTE CONTROL ASSEMBLY 17 PMRAS 10C3M 003 1 REMOTE CONTROL SUPPORT 18 PMRAS 25YH4 S15 1 SPRING 19 PMRAS 260GHA R01 1 THERMISTOR 20 PMRAS 10CH9 R01 1 P W B MAIN AND INDICATION 21 PMRAS 07GH4 R04 1 P W B POWER SW S...

Page 63: ...H4 S29 1 AUTO SWEEP MOTOR 12 PMRAS 08CH9 R02 1 FRONT COVER ASSY 13 PMRAS S10CY 004 1 FRONT PANEL 14 PMRAS 08CH8 008 1 AIR FILTER R 15 PMRAS 08CH8 009 1 AIR FILTER L 16 PMRAS 51CHA1 R11 1 REMOTE CONTROL ASSEMBLY 17 PMRAS 10C3M 003 1 REMOTE CONTROL SUPPORT 18 PMRAS 25YH4 S15 1 SPRING 19 PMRAS 260GHA R01 1 THERMISTOR 20 PMRAS 14CH9 R01 1 P W B MAIN AND INDICATION 21 PMRAS 07GH4 R04 1 P W B POWER SW S...

Page 64: ...YH4 S29 1 AUTO SWEEP MOTOR 12 PMRAS 08CH9B R01 1 FRONT COVER ASSY 13 PMRAS 08CH9B R02 1 FRONT PANEL 14 PMRAS 08CH8 008 1 AIR FILTER R 15 PMRAS 08CH8 009 1 AIR FILTER L 16 PMRAS 51CHA1 R11 1 REMOTE CONTROL ASSEMBLY 17 PMRAS 10C3M 003 1 REMOTE CONTROL SUPPORT 18 PMRAS 25YH4 S15 1 SPRING 19 PMRAS 260GHA R01 1 THERMISTOR 20 PMRAS 08CH9 001 1 P W B MAIN AND INDICATION 21 PMRAS 07GH4 R04 1 P W B POWER S...

Page 65: ...YH4 S29 1 AUTO SWEEP MOTOR 12 PMRAS 08CH9B R01 1 FRONT COVER ASSY 13 PMRAS 08CH9B R02 1 FRONT PANEL 14 PMRAS 08CH8 008 1 AIR FILTER R 15 PMRAS 08CH8 009 1 AIR FILTER L 16 PMRAS 51CHA1 R11 1 REMOTE CONTROL ASSEMBLY 17 PMRAS 10C3M 003 1 REMOTE CONTROL SUPPORT 18 PMRAS 25YH4 915 1 SPRING 19 PMRAS 260GHA R01 1 THERMISTOR 20 PMRAS 10CH9 R01 1 P W B MAIN AND INDICATION 21 PMRAS 07GH4 R04 1 P W B POWER S...

Page 66: ...YH4 S29 1 AUTO SWEEP MOTOR 12 PMRAS 08CH9B R01 1 FRONT COVER ASSY 13 PMRAS 08CH9B R02 1 FRONT PANEL 14 PMRAS 08CH8 008 1 AIR FILTER R 15 PMRAS 08CH8 009 1 AIR FILTER L 16 PMRAS 51CHA1 R11 1 REMOTE CONTROL ASSEMBLY 17 PMRAS 10C3M 003 1 REMOTE CONTROL SUPPORT 18 PMRAS 25YH4 S15 1 SPRING 19 PMRAS 260GHA R01 1 THERMISTOR 20 PMRAS 14CH9 R01 1 P W B MAIN AND INDICATION 21 PMRAS 07GH4 R04 1 P W B POWER S...

Page 67: ... 70 6 8 7 9 4 3 13 12 15 16 10 14 5 19 17 18 21 20 11 2 1 PARTS LIST AND DIAGRAM INDOOR UNIT MODEL RAC 08CH9 RAC 10CH9 22 ...

Page 68: ...HANDLE 10 PMRAC 09CHA1 903 1 D GRILL 11 PMRAC 07CH5 901 1 COMPRESSOR 12 PMRA 08GF 904 3 COMPRESSOR RUBBER 13 PMRA 08GF S05 3 COMPRESSOR NUT 14 PMRAC 07CH6 902 1 CONDENSER 15 PMRAC 10CXT 902 1 2S VALVE 16 PMRAC 10CXT 901 1 3S VALVE 17 PMRAC 05CV S15 1 FAN MOTOR CAPACITOR 18 PMRAC 25NH4 S13 1 TERMINAL BOARD 4P 19 PMRAC 07GH4 S06 1 COMPRESSOR CAPACITOR 20 PMRAC 260GHA S01 1 REVERSING VALVE 21 PMRAC 2...

Page 69: ...HANDLE 10 PMRAC 09CHA1 903 1 D GRILL 11 PMRAC 10C8 901 1 COMPRESSOR 12 PMRA 08GF 904 3 COMPRESSOR RUBBER 13 PMRA 08GF 905 3 COMPRESSOR NUT 14 PMRAC 09GH4 S02 1 CONDENSER 15 PMRAC 10CXT 902 1 2S VALVE 16 PMRAC 10CXT 901 1 3S VALVE 17 PMRAC 63CHA2 S08 1 FAN MOTOR CAPACITOR 18 PMRAC 25NH4 S13 2 TERMINAL BOARD 4P 19 PMRAC 10C8 904 1 COMPRESSOR CAPACITOR 20 PMRAC 260GHA S01 1 REVERSING VALVE 21 PMRAC 0...

Page 70: ... 73 5 4 8 9 15 7 6 18 14 16 10 11 12 17 22 3 1 23 20 24 21 2 19 13 PARTS LIST AND DIAGRAM OUTDOOR UNIT MODEL RAC 14CH9 ...

Page 71: ...L BOARD 4P 11 PMRAC 10C8 904 1 COMPRESSOR CAPACITOR 12 PMRAC 10C7 S04 1 FAN MOTOR CAPACITOR 13 PMRAC 14GH4 902 1 HANDLE 14 PMRAC 14CH9 S02 1 CABINET 15 PMRAC 09CHA1 903 1 D GRILL 16 PMRAC 14GH4 S05 1 SIDE PLATE R 17 PMRAC 25NH4 921 1 SV COVER 18 PMRAC 51CA1 909 1 TOP COVER 19 PMRAC 10C8 909 1 OVERLOAD PROTECTOR 20 PMRAC 18GH4 S06 1 REVERSING VALVE COIL 21 PMRAC 07GH4 S03 1 REVERSING VALVE 22 PMRAC...

Page 72: ...HITACHI PM NO 0446E Printed in Malaysia RAS 08CH9 RAS 08CH9 B RAC 08CH9 RAS 10CH9 RAS 10CH9 B RAC 10CH9 RAS 14CH9 RAS 14CH9 B RAC 14CH9 ...

Reviews: