background image

8.  Test Running by Controller

ATTENTION:

Test running by the controller can not be performed in case that the wired remote control switch 

is used together; in case that multiple units are operated simultaneously (SET-FREE and UTOPIA 

Series).  In such cases, perform the test running by the wired remote control switch.

1)  Perform the test run after the installation work is completed. 

(1)  Set the batteries for the controller.

(2)  Turn ON the power supply for the indoor and outdoor units.

(3)  “ 

 ” lamp (yellow) on the receiver of the indoor unit flashes (0.25 seconds ON 

 0.25 seconds 

OFF), and then turns OFF.  While the lamp is flashing, the unit will not operate because it is 

initializing.

2)  Set the test run mode by pressing “SET” and 

“OFF TIME” switch simultaneously for more than 

3 seconds.  The LCD should be as shown in the 

figure on the right.

3)  Set the operation mode by pressing the “MODE” 

switch.

OFF

TIMER

COOL

OFF

°

C

Me

TIMER

COOL

Test Run Mode is under suspension.

Test Run Mode is under operating.

ATTENTION:

When the commands are sent by the controller hooked onto the wall, the receiver of the indoor 

unit may not receive the commands depending on the installation place.

2)  Pay attention to the following points in case that the controller is installed in a place where there is 

medical equipment radiating electromagnetic waves.

(1)  Install the controller in a place where electromagnetic waves are not radiated directly toward the 

electrical box of the indoor unit and the controller.

(2)  Keep a distance more than 3 meters away from the equipment radiating electromagnetic waves, the 

receiver of the radio, etc. for prevention of the noise through the air.

(3)  In case that there is electric noise at the power source for the indoor unit, the treatment such as 

providing a noise filter is required.

3)  Do not install the controller in a place where generation, flowing, staying or leaking of flammable gas is 

detected.

4)  Install the controller in a place where there is a distance more than 30cm from the power supply cable 

when installing the controller onto the wall.

5)  Install the holding bracket (accessory) onto the wall by using screw (accessory) and attach the controller 

to the holding bracket.

7.  Installing onto the Wall or Pillar

1)  Select the suitable place for handling and install the controller with the customer’s acceptance.

 

Do not install the controller at the places as follows.

   *  where children can touch

   *  where the air from the air conditioner is directly discharged

   *  where there is oil vapor and the oil is dispersed

   *  where the humidity is high

6

Summary of Contents for PC-LH3A

Page 1: ...m the test run whether there is abnormality or not after the installation work is completed The usage and the maintenance should be explained to a user according to Installation Maintenance Manual of the indoor unit Describe to keep this installation manual also l It is assumed that this kit will be installed and serviced by English speaking people If this is not the case the customer should add s...

Page 2: ...the contents and the number of the parts Name Q ty Remark Wireless Remote Control Switch Controller 1 For Operation Control Holding Bracket 1 For Controller Battery AAA 1 5V Dry Cell 2 For Power Source of Controller Screw 2 For Fixing Holding Bracket onto Wall Slide the cover in the arrow direction with pushing AAA Batteries 2 Do not turn ON the power source unless the preparation for test running...

Page 3: ...g actual operation Run Stop Switch Operation of the unit can be started or stopped by pressing this switch Fan Speed Switch Press this switch to select the fan speed By repeatedly pressing the button the setting will change sequentially through HIGH2 HIGH MED and LOW Fan speed is fixed at Low for dry operation O Available X Not available HIGH2 is not indicated on PC LH3A Mode Selection Switch By r...

Page 4: ...g gets half when the transmitting angle is 50o and also get shorter in case that an electronic type light is used in the room NOTE The above figure shows the case of a 4 way cassette type indoor unit The figures for other models are different partially LCD Liquid Crystal Display Indication When viewed from certain angles the LCD can be difficult to read The viewing angle ranges from an optimal of ...

Page 5: ...oor Units Installed Side by Side NOTE This function is required to set at the receiver side It shall be set according to the installation manual of the receiver kit or the indoor unit Setting of Identifying of Indoor Units Installed Side by Side 1 Press and hold ON TIME switch and OFF TIME switch of the wireless remote control switch simultaneously for 3 seconds The b is indicated on the liquid cr...

Page 6: ...tion to the following points in case that the controller is installed in a place where there is medical equipment radiating electromagnetic waves 1 Install the controller in a place where electromagnetic waves are not radiated directly toward the electrical box of the indoor unit and the controller 2 Keep a distance more than 3 meters away from the equipment radiating electromagnetic waves the rec...

Page 7: ...In the test run mode the red lamp RUN of the receiver is turned ON and the green lamp TIMER flashes 0 5 seconds ON 0 5 seconds OFF 2 And then set off timer for 2 hours NOTES 1 In the case that the lamp yellow does not turn ON the controls may not have reached the receiver Send the commands again 2 2 In the case of RPK model TIMER lamp is turned ON without flashing 5 Adjust the angle of the air lou...

Reviews: