background image

3

INSTALLATION OF REMOTE CONTROL SWITCH <PC-2H2>

3

Ë

Connect the cable to the PCB connector (yellow) of
the controller, run the cable through the groove at
the backside of the casing and draw out the cable
from the casing.

Fig. 6  PCB connector

Ì

Attaching Procedures

Upper side

Lower side

Fig. 7  Attaching Procedures

Step 1:  Insert the hooks of the controller to the holes on the top of the holding

bracket.

Step 2: Push the lower part toward the holding bracket.
Step 3: When the click sound is heard, the controller is attached to the holding

bracket and the mounting work is finished. Check to ensure that the 4
hooks at the position * are correctly inserted.

B. When Using Switch Box.

É

Field-Supplied JIS Box (JIS 8336 - 1998)

Fig. 8 Running the cable through the conduit tube in the wall

Ê

Fix the holding bracket to the switch box

Fig. 9  Fixing the holding bracket

Ë

Mounting procedures.

Step 1:  Insert the hooks of the controller to the

holes on the top of the holding bracket.

Step 2: Push the lower part toward the holding

bracket.

Step 3: When the click sound is heard, the

controller is attached to the holding
bracket and the mounting work is
finished.

Fig. 10  Mounting procedures

 CAUTION:

Pay attention so that the cable may not be slack. If the
cable is slack as shown in the above figure, the cable
cord (especially the naked part) may be clamped at the
hole and it may cause a faulty operation.

1.4.

 

WIRING SYSTEM FOR REMOTE CONTROL
SWITCH (PC-2H2)

1.4.1.

 

LENGTH OF WIRE CABLE FOR REMOTE

CONTROL SWITCH

Length of the standard wire cable for the optional remote
control switch is 8 meters.
Extension up to 500 meters (with 0.75mm

2

 CVS wire) is

available.
Indoor Unit:  

1 set

Remote Control Switch:  1 set

Fig. 11  Length of Wire Cable for Remote Control Switch

1.4.2.

 

ELECTRICAL WIRING

Attach the Ring Core (black) (accessory) when installing the
unit.

§

 

Insert the remote control cable into the ring core 2 turns as
shown below before connecting to the PCB. Fix the cable by
using the band (accessory).

Fig. 12  Electrical  Wiring

M4 Screw
(Field-Supplied)

Yellow

White

Attach the stopper to the cable
at the inside of the draw-out
hole.

The following 5 types are available.
1. Switch Box for 1 Controller (without Cover)
2. Switch Box for 2 Controllers (without Cover)
3. Switch Box for 1 Controller (with Cover)
4. Switch Box for 2 Controllers (with Cover)
5. Outlet Box (with Cover)

Approx. 30 mm

Band

Indoor PCB

Remote Control Cable

Ring Core

CN13 (blue)

Connector

Insert

Remote controller

Summary of Contents for PC-2H2

Page 1: ...onsultazioni Leia e compreenda este manual antes de operar este ar condicionado Guarde este manual para futura referencia De bor laese og forsta denne vejledning for de tager dette dlimaanlaeg i brug Opbervar vejledningen til senere reference Lees deze hadleiding aandachtig door alvorens de airconditioning in gebruik te nemen Läs och första denna manual innan Du sätter igang luftkonditioneraren Fö...

Page 2: ......

Page 3: ...run any cable for transmission and signal along the power line 220 240V 380 415V DO NOT run any cable for transmission and signal along other cables for transmission and signal If the cables are required to be run along keep a distance more than 30 cm between each cables or insert the cables for each transmission system into the metal conduit tube and ground one end of the conduit tube n Location ...

Page 4: ...f the holding bracket push and turn the screwdriver and remove the controller from the holding bracket as shown in the figure below Fig 2 Installation Procedure Fig 3 Installation Procedure 2 Attach the controller to the holding bracket as follows A In case of exposing Remote Control Cable É Fix the holding bracket onto the wall as shown below Fig 4 Attach the controller Ê Make the hole for drawin...

Page 5: ...nting work is finished Fig 10 Mounting procedures CAUTION Pay attention so that the cable may not be slack If the cable is slack as shown in the above figure the cable cord especially the naked part may be clamped at the hole and it may cause a faulty operation 1 4 WIRING SYSTEM FOR REMOTE CONTROL SWITCH PC 2H2 1 4 1 LENGTH OF WIRE CABLE FOR REMOTE CONTROL SWITCH Length of the standard wire cable ...

Page 6: ...wires B After checking the color of the wires connect each wire of the same color by soldering C Insulate the soldered parts and the wires with insulation tape D The maximum total cable length of the remote control switch cable and the bridge cable s is 200 meters 0 3mm2 wire or 500 meters 0 75mm2 wire 3 Separate the cable more than approximately 30cm from any wires which are utilized for wires hi...

Page 7: ... Bridge Cable 9 Contact of Connectors of Bridge Cable Ë Back to É after checking Ì Select TEST RUN MODE by depressing MODE Switch COOL OR HEAT Í Depress RUN STOP switch a The TEST RUN operation will be started The TEST RUN operation will be finished after 2 hours unit operation or by depressing the RUN STOP switch again b IF the unit do not start or the operation lamp on the remote control switch ...

Page 8: ...pressor Heat Pump Twin 11 Thermistor Abnormality for inlet Air Temperature All Models 12 Thermistor Abnormality for outlet Air Temperature Heat Pump Twin 13 Thermistor Abnormality for Freezing Temperature All Models 20 Thermistor Abnormality for Compressor Top Temperature Heat Pump Twin 22 Thermistor Abnormality for Outdoor Air Temperature Heat Pump Twin 24 Thermistor Abnormality for Outdoor Evapo...

Page 9: ...etting temperature is turned OFF b At the condition of the above item a press the TEMP switch or the TEMP switch of the remote control switch and the indoor unit for which the optional function is to be set can be changed NOTES The indoor unit can be selected among the indoor units connected to the remote control switch In case that both the indications of the address and the refrigerant cycle num...

Page 10: ...0 01 Not Available Available b4 Change of Filter Cleaning Time 00 01 02 03 04 Standard 100 hours 1200 hours 2500 hours Not Indication b5 Fixing of Operation Mode 00 01 Not Available Available b6 Fixing of Setting Temperature 00 01 Not Available Available b7 Fixing of Operation as Exclusive Cooling Unit 00 01 Not Available Available b8 Automatic COOL HEAT 00 01 Not Available Available b9 Fixing of ...

Page 11: ......

Page 12: ...PMML0041B 12 01 Printed in Spain ...