L300P Inverter
In
v
e
rt
er Mounting
and In
stallati
on
2–17
Terminal dimensions and torque specs, continued...
Note 1:
The recommended ring lug connector listing consists of wire size – screw size
format. The wire sizes are in AWG or mm
2
format. For AWG wire sizes, bolt sizes
for the ring lug centers are: #10, #12, 1/4”, 5/16”, and 1/2”. For metric wire sizes, bolt
sizes for the ring lug centers are: 6 = 6M, 8 = 8M, 10 = 10M.
Input
Voltage
Motor
Output
400V
Inverter
Models,
L300P
Length
of
power
wiring
Screw size
of terminal
Ring Lug Connector *1
Torque
HP
kW
(AWG–bolt)
(mm
2
–bolt)
ft-lbs
N-m
400V
2
1.5
–015HFU2, HFE2
—
M4
20–10
2–4
1.1
1.5
3
2.2
–022HFU2, HFE2
—
M4
18–10
2–4
1.1
1.5
5
4.0
–040HFU2, HFE2
—
M4
16–10
2–4
1.1
1.5
7.5
5.5
–055HFU2, HFE2
—
M5
14–12
2–5
1.8
2.5
10
7.5
–075HFU2, HFE2
—
M5
12–12
3.5–5
1.8
2.5
15
11
-110HFU2, HFE2
—
M6
8–1/4
5.5–6
3.6
4.9
20
15
-150HFU2, HFE2
—
M6
6–1/4
8–6
3.6
4.9
25
18.5
-185HFU2, HFE2
—
M6
6–1/4
14–6
3.6
4.9
30
22
-220HFU2, HFE2
—
M6
4–1/4
14–6
3.6
4.9
40
30
-300HFU2, HFE2
—
M6
3–1/4
22–6
3.6
4.9
50
37
-370HFU2, HFE2
—
M6
1
38–6
3.6
4.9
60
45
-450HFU2, HFE2
—
M8
1–5/16
38–8
6.5
8.8
75
55
-550HFU2, HFE2
—
M8
1/0–5/16
60–8
6.5
8.8
100
75
-750HFU2, HFE2
—
M8
2–5/16
100–8
6.5
8.8
125
90
-900HFU2, HFE2
—
M10
1–1/2
100–10
10.1
13.7
150
110
-1100HFU2, HFE2
—
M10
1/0–1/2
150–10
10.1
13.7
175
132
-1320HFU2, HFE2
—
M10
2/0–1/2
80x2–10
10.1
13.7