L300P Inverter
Configur
ing Dr
iv
e
P
a
ra
met
e
rs
3–47
Note 1:
To ensure safe inverter operation in networked applications, you cannot change an
intelligent terminal assignment to/from [ROK] (option code 49) via the network.
However, you can still read an [ROK] input assignment over the network.
28
DWN
Remote Control
DOWN Function
(motorized speed pot.)
ON
Decelerates (decreases output frequency) motor from
current frequency
OFF
No change to output frequency
29
UDC
Remote Control Data
Clearing
ON
Clears the UP/DWN frequency memory by forcing it
to equal the set frequency parameter F001. Setting
C101 must be set=00 to enable this function to work.
OFF
UP/DWN frequency memory is not changed
31
OPE
Operator Control
ON
Forces the source of the output frequency setting
(A001) and the source of the RUN command (A002)
to be from the digital operator
OFF
Source of output frequency set by (A001) and source
of run command set by (A002) is used
32
SF1
Multispeed bit 1
ON
Logical 1
OFF
Logical 0
33
SF2
Multispeed bit 2
ON
Logical 1
OFF
Logical 0
34
SF3
Multispeed bit 3
ON
Logical 1
OFF
Logical 0
35
SF4
Multispeed bit 4
ON
Logical 1
OFF
Logical 0
36
SF5
Multispeed bit 5
ON
Logical 1
OFF
Logical 0
37
SF6
Multispeed bit 6
ON
Logical 1
OFF
Logical 0
38
SF7
Multispeed bit 7
ON
Logical 1
OFF
Logical 0
39
OLR
Overload restriction
ON
Selects current overload parameter set 2
(B024, B025, B026)
OFF
Selects current overload parameter set 1
(B021, B022, B023)
49
ROK
*1
Run Enable for FW/RV
(–xFU2 and –xFE2
models only)
ON
[FW] and [RV] inputs and operator Run key press
operate normally
OFF
[FW] and [RV] inputs and operator Run key press are
ignored; inverter output remains OFF
no
—
Not selected
ON
(input ignored)
OFF
(input ignored)
Input Function Summary Table
Option
Code
Terminal
Symbol
Function Name
Description