L200 Inverter
Appendix B
B–33
B021
Overload restriction
operation mode
R/W Select the operating mode
during overload conditions,
three options, option codes:
00... Disabled
01... Enabled for acceleration
and constant speed
02... Enabled for constant
speed only
0092h
0, 1, 2
—
B022
Overload restriction
setting
R/W Sets the level for overload
restriction, between 20% and
150% of the rated current of
the inverter, setting resolution
is 1% of rated current
0093h
2000 to
15000
0.01%
B023
Deceleration rate at
overload restriction
R/W Sets the deceleration rate when
inverter detects overload, range
is 0.1 to 30.0, resolution is 0.1
0094h
1 to 300
0.1 sec
B031
Software lock mode
selection
R/W Prevents parameter changes, in
four options, option codes:
00... all parameters except
B031 are locked when [SFT]
terminal is ON
01... all parameters except
B031 and output frequency
F001 when [SFT] terminal is
ON
02... all parameters except
B031 are locked
03... all parameters except
B031 and output frequency
F001 setting are locked
0095h
0, 1, 2, 3
—
B032
Reactive current setting
R/W Calibrate detection of motor’s
reactive (no load) current for
current monitor, electric
thermal setting, and overload
restriction setting
00E8h
50 to
200
1%
B080
[AM] analog signal
gain
R/W Adjust of analog output at
terminal [AM],
range is 0 to 255
0096h
0 to 255
—
B082
Start frequency adjust-
ment
R/W Sets the starting frequency for
the inverter output, range is 0.5
to 9.9 Hz
0098h
5 to 99
0.1 Hz
B083
Carrier frequency
setting
R/W Sets the PWM carrier (internal
switching frequency), range is
2.0 to 14.0 kHz
0099h
20 to
140
0.1 Hz
“B” Group Fine Tuning Functions
Func.
Code
Name
R/W
Description
Network Data
Reg.
Range
Res.