D C I N V E R T E R C O M P R E S S O R C R I T E R I A
PAGE:7/32
5 Pressure difference between suction and discharge
In all allowable rotational speed range, the difference of pressure should be more than
0. 39MPa{4kgf/cm
2
}. But if there is no problem of noise when assembled in air conditioner,
it can also below this value.
6 Discharge pipe temperature
Discharge pipe temperature is measured at a distance 300mm from the surface of compressor
and should be less than 110℃. The tip of the thermocouple is fixed by soldering when
measuring discharge pipe temperature .Furthermore, soldering point is covered with urethane
foam to prevent the effect of wind.
7 Air leakage test pressure
The pressure should be less than 4.32MPa{42kgf/cm
2
G}.
8 Oil back and oil level
The oil should be returned continuously to the compressor and the structure of the refrigerating
system should not make oil stay in the system. The oil level in compressor should be satisfied
with chart 2.If not keep the oil level, the shortage will occur, and influence the reliability
of the compressor.(please check the oil level in the compressor with the sight glass which supplied
form SHEC.
9 Dust of compressor hermetic terminals
Compressor hermetic terminals should be mounted with specified cover in right way to prevent
dust entering, and should be used in direction which dust is hard to enter in.
10 Lead wire of compressor hermetic terminals
Measuring the temperature of hermetic terminals , lead wire should be resist to the temperature
and be clamped so as not in touch with the surface of compressor and pipe.
Summary of Contents for HIGHLY WHP08750VCDNC9AU
Page 18: ...PAGE 16 32 ...
Page 19: ...PAGE 17 32 ...
Page 20: ...PAGE 18 32 ...
Page 21: ...PAGE 19 32 ...
Page 22: ...PAGE 20 32 ...
Page 23: ...PAGE 21 32 ...
Page 24: ...PAGE 22 32 ...
Page 25: ...PAGE 23 32 ...
Page 26: ...PAGE 24 32 ...
Page 27: ...PAGE 25 32 ...
Page 30: ...PAGE 28 32 ...
Page 34: ...PAGE 32 32 ...