background image

 

 

Hitachi America, Ltd. 

 

EN-060224-1

 
 

AC VARIABLE FREQUENCY INVERTER 

ENGINEERING NOTE 

 
 

TYPE Product 

Advisory 

SUBJECT 

SR/SK DIP-Switch Setting on Certain Production Dates 

AFFECTED 

MODELS 

SJ200-055xFU, L200-055xFU, SJ200-075xFU, L200-075xFU 
(x = L or H) 

 
 
In all listed models produced before January 2006 (Date Code 0601 [YYMM] and 
LOWER), the setting of the SR/SK switch (controls whether input terminals are 
source or sink type) is incorrect compared to what is documented in the manual. 
 
The correct factory default position for this switch should be “SR” (source) as 
shown in the manual. However, these units were shipped with the switch in the 
“SK” (sink) position. 
 
All other ratings of SJ200 and L200 were shipped with the switch set correctly. 
 
Customers who receive affected models will simply have to change the switch 
position to configure the unit for source inputs, per the manual. If they need sink 
inputs, obviously, they will not need to change the switch position. 
 
A Product Advisory is included in the carton of January 2006 through March 2006 
production, to help avoid confusion for any users who had received units from 
earlier production. After March, the advisory will no longer be inserted in the 
carton. 

PGC - 2/24/06 

Page 1 of 1

 