Table 7:
Supervisory signals in monitoring direction
INF
Description
GI.
TYPE
COT
REB500 signal configuration
<47>
General alarm
x
1
1,9
41805_Alarm (CU output)
Table 8:
Disturbance signals in monitoring direction
INF
Description
GI.
TYPE
COT
FUN
REB500 signal configuration
<68>
General trip
–
2
1
254
42305_BBP trip (CU output)
21110_TRIP (BU output)
21305_TRIP (BU output)
<69>
Trip L1
–
2
1
254
42315_BBP trip L1 (CU output)
23315_BFP TRIP L1 (BU output)
<70>
Trip L2
–
2
1
254
42320_BBP trip L2 (CU output)
23320_BFP TRIP L2 (BU output)
<71>
Trip L3
–
2
1
254
42325_BBP trip L3 (CU output)
23325_BFP TRIP L3 (BU output)
<72>
Trip L0
–
2
1
254
23340_BFP TRIP L0 (BU
output)
<85>
Breaker failure
–
2
1
254
43305_BFP trip t1 (CU output)
43310_BFP trip t2 (CU output)
23305_BFP trip t1 (BU output)
23310_BFP trip t2 (BU output)
<90>
Trip I>
–
2
1
254
45305_OCDT trip (CU output)
25105_OCDT TRIP (BU output)
25305_OCDT trip (BU output)
<92>
Trip IN>
–
2
1
254
42310_BBP trip L0 (CU output)
Table 9:
Types of function
FUN
Description
<254>
Generic
Table 10: Generic functions in monitoring direction
INF
Description
GI
TYPE
COT
<240>
Read headings of all defined groups
–
10
42,43
<241>
Read values or attributes of all entries of one
group
–
10
42,43
<242>
Not used
–
–
–
<243>
Read the directory of a single entry
–
11
42,43
<244>
Read the value or attribute of a single entry
(x)
10
1,2,9,11,12,42,43
Table 11: Generic functions in control direction
INF
Description
TYPE
COT
<240>
Read headings of all defined groups
21
42
<241>
Read values or attributes of all entries of one group
21
42
<242>
Not used
–
–
<243>
Read the directory of a single entry
21
42
<244>
Read the value or attribute of a single entry
21
42
Section 4
1MRK 511 451-UEN Rev. C
IEC 60870-5-103
14
Distributed busbar protection REB500
Communication protocol manual IEC 60870-5-103
© 2019 - 2020 Hitachi Power Grids. All rights reserved