State
CBL controller and drive trays
(m/s
2
)
Tipping angle (°)
(Storage system tips over)
15° or less
(To be measured when installed on
leveling bolts.)
Altitude
State
Controller
FMD tray
Operating
(m)
3,050
(Environmental
temperature: 10°C
to 28°C)
3,050 (Environmental temperature: 10°C to 28°C)
1
950
(Environmental
temperature: 10°C
to 40°C)
950 (Environmental temperature: 10°C to 40°C)
Non-
operating
(m)
-60 to 12,000
Note:
1. Meets the highest allowable temperature conditions and complies with ASHRAE
(American Society of Heating, Refrigerating and Air-Conditioning Engineers) 2011
Thermal Guidelines Class A3. The maximum value of the ambient temperature
and the altitude is from 40ºC at an altitude of 950m (3000 feet) to 28ºC at an
altitude of 3050m (1000 feet).
The allowable ambient temperature is decreased by 1ºC for every 175m increase
in altitude above 950m.
Environmental specifications
Appendix B: System specifications
Hitachi Virtual Storage Platform G900 Hardware Reference Guide
76