Main Switch
Main Switch
Remote
Control Switch
(Option)
Remote
Control Switch
(Option)
Remote
Control Switch
(Option)
Remote
Control Switch
(Option)
Outdoor Unit
Indoor Unit No.1
Indoor Unit No.2
Indoor Unit No.3
Indoor Unit No.4
Earth
Wiring
Remote Control
Switch Cable
(Field Supplied)
Shielded Twist-Pair Cable 0.75mm
2
x 2
This cable dose not need any polarity.
Do not apply an excessively high
voltage to this cable. (Rated Voltage: 5V)
Control Cable
Power Source Cable
Pay an attention to the phase
of power source when wiring.
Fig. 6.2 Wiring Connection
Install an ELB in the power source.
If ELB is not used, it will cause electric shock or fire
at the worst.
The tightening torque of each screw shall be as
follows.
M4:
1.0 to 1.3 N-m
M5:
2.0 to 2.5 N-m
M6:
4.0 to 5.0 N-m
M8:
9.0 to 11.0 N-m
M10:
18.0 to 23.0 N-m
Keep the above tightening torque when wiring work.
L2 L3 N
L1 L2
N
Mp
1 2 A B
Outdoor Unit
Indoor Unit No.1
Main Switch
Main Switch
Remote
Control Switch
(Option)
Remote Control
Switch Cable
(Field Supplied)
Shielded Twist-Pair Cable 0.75mm
2
x 2
This cable dose not need any polarity.
Do not apply an excessively high
voltage to this cable. (Rated Voltage: 5V)
Shielded Twist-Pair Cable 0.75mm
2
x 2
This cable dose not need any polarity.
Do not apply an excessively high
voltage to this cable. (Rated Voltage: 12V)
Control Cable
Power Source Cable
Pay an attention to the phase
of power source when wiring.
L1
Remote
Control Switch
(Option)
Earth
Wiring
L1 L2
N
Mp
1 2 A B
Indoor Unit No.2
ELB
ELB
E
1 2
L1 L2
N
Mp
1 2 A B
Indoor Unit No.3
L1 L2
N
Mp
1 2 A B
Indoor Unit No.4
Remote
Control Switch
(Option)
Remote
Control Switch
(Option)
E
E
E
E
Fig. 6.5 Wiring Connection ( 380V 3N 60Hz)
Fig. 6.4 Wiring Connection ( 380-415V 3N 50Hz)
L2 L3 N
L1 L2
N
Mp
1 2 A B
Outdoor Unit
Indoor Unit No.1
Main Switch
Main Switch
Remote
Control Switch
(Option)
Remote Control
Switch Cable
(Field Supplied)
Shielded Twist-Pair Cable 0.75mm
2
x 2
This cable dose not need any polarity.
Do not apply an excessively high
voltage to this cable. (Rated Voltage: 5V)
Shielded Twist-Pair Cable 0.75mm
2
x 2
This cable dose not need any polarity.
Do not apply an excessively high
voltage to this cable. (Rated Voltage: 12V)
Control Cable
Power Source Cable
Pay an attention to the phase
of power source when wiring.
L1
Remote
Control Switch
(Option)
Earth
Wiring
L1 L2
N
Mp
1 2 A B
Indoor Unit No.2
ELB
ELB
E
1 2
L1 L2
N
Mp
1 2 A B
Indoor Unit No.3
L1 L2
N
Mp
1 2 A B
Indoor Unit No.4
Remote
Control Switch
(Option)
Remote
Control Switch
(Option)
E
E
E
E
220-240V 50Hz)
Main Switch
Remote
Control Switch
(Option)
Remote
Control Switch
(Option)
Remote
Control Switch
(Option)
Remote
Control Switch
(Option)
Outdoor Unit
Indoor Unit No.1
Indoor Unit No.2
Indoor Unit No.3
Indoor Unit No.4
Earth
Wiring
Remote Control
Switch Cable
(Field Supplied)
Shielded Twist-Pair Cable 0.75mm
2
x 2
This cable dose not need any polarity.
Do not apply an excessively high
voltage to this cable. (Rated Voltage: 5V)
Control Cable
Power Source Cable
Pay an attention to the phase
of power source when wiring.
Main Switch
Main Switch
Remote
Control Switch
(Option)
Remote
Control Switch
(Option)
Remote
Control Switch
(Option)
Remote
Control Switch
(Option)
Outdoor Unit
Indoor Unit No.1
Indoor Unit No.2
Indoor Unit No.3
Indoor Unit No.4
Earth
Wiring
Remote Control
Switch Cable
(Field Supplied)
Shielded Twist-Pair Cable 0.75mm
2
x 2
This cable dose not need any polarity.
Do not apply an excessively high
voltage to this cable. (Rated Voltage: 5V)
Shielded Twist-Pair Cable 0.75mm
2
x 2
This cable dose not need any polarity.
Do not apply an excessively high
voltage to this cable. (Rated Voltage: 12V)
Control Cable
Power Source Cable
Pay an attention to the phase
of power source when wiring.
Main Switch
Remote
Control Switch
(Option)
Remote
Control Switch
(Option)
Remote
Control Switch
(Option)
Remote
Control Switch
(Option)
Outdoor Unit
Indoor Unit No.1
Indoor Unit No.2
Indoor Unit No.3
Indoor Unit No.4
Earth
Wiring
Remote Control
Switch Cable
(Field Supplied)
Shielded Twist-Pair Cable 0.75mm
2
x 2
This cable dose not need any polarity.
Do not apply an excessively high
voltage to this cable. (Rated Voltage: 5V)
Shielded Twist-Pair Cable 0.75mm
2
x 2
This cable dose not need any polarity.
Do not apply an excessively high
voltage to this cable. (Rated Voltage: 12V)
Control Cable
Power Source Cable
Pay an attention to the phase
of power source when wiring.
Fig. 6.3 Wiring Connection 220V 60Hz)
Shielded Twist-Pair Cable 0.75mm x 2
This cable dose not need any polarity.
Do not apply an excessively high
voltage to this cable. (Rated Voltage: 12V)
Shielded Twist-Pair Cable 0.75mm x 2
This cable dose not need any polarity.
Do not apply an excessively high
voltage to this cable. (Rated Voltage: 12V)
~
~
~
~
FUSE
Switch
FUSE
Switch
FUSE
Switch
FUSE
Switch
220-240V~/50HZ
220-240V~/50HZ
220V~/60HZ
220V~/60HZ
220-240V~/50HZ
220V~/60HZ
380-415V 3N ~/50HZ
380V 3N~/60HZ
Install an ELB in the power source.
If ELB is not used, it will cause electric shock or fire
at the worst.
The tightening torque of each screw shall be as
follows.
M4:
1.0 to 1.3 N-m
M5:
2.0 to 2.5 N-m
M6:
4.0 to 5.0 N-m
M8:
9.0 to 11.0 N-m
M10:
18.0 to 23.0 N-m
Keep the above tightening torque when wiring work.
Install an ELB in the power source.
If ELB is not used, it will cause electric shock or fire
at the worst.
The tightening torque of each screw shall be as
follows.
M4:
1.0 to 1.3 N-m
M5:
2.0 to 2.5 N-m
M6:
4.0 to 5.0 N-m
M8:
9.0 to 11.0 N-m
M10:
18.0 to 23.0 N-m
Keep the above tightening torque when wiring work.
Install an ELB in the power source.
If ELB is not used, it will cause electric shock or fire
at the worst.
The tightening torque of each screw shall be as
follows.
M4:
1.0 to 1.3 N-m
M5:
2.0 to 2.5 N-m
M6:
4.0 to 5.0 N-m
M8:
9.0 to 11.0 N-m
M10:
18.0 to 23.0 N-m
Keep the above tightening torque when wiring work.
Install an ELB in the power source.
If ELB is not used, it will cause electric shock or fire
at the worst.
The tightening torque of each screw shall be as
follows.
M4:
1.0 to 1.3 N-m
M5:
2.0 to 2.5 N-m
M6:
4.0 to 5.0 N-m
M8:
9.0 to 11.0 N-m
M10:
18.0 to 23.0 N-m
Keep the above tightening torque when wiring work.
Install an ELB in the power source.
If ELB is not used, it will cause electric shock or fire
at the worst.
The tightening torque of each screw shall be as
follows.
M5:
2.0 to 2.5 N-m
M6:
4.0 to 5.0 N-m
M8:
9.0 to 11.0 N-m
M10:
18.0 to 23.0 N-m
Keep the above tightening torque when wiring work.
Install an ELB in the power source.
If ELB is not used, it will cause electric shock or fire
at the worst.
The tightening torque of each screw shall be as
follows.
M5:
2.0 to 2.5 N-m
M6:
4.0 to 5.0 N-m
M8:
9.0 to 11.0 N-m
M10:
18.0 to 23.0 N-m
Keep the above tightening torque when wiring work.
Install an ELB in the power source.
If ELB is not used, it will cause electric shock or fire
at the worst.
The tightening torque of each screw shall be as
follows.
M5:
2.0 to 2.5 N-m
M6:
4.0 to 5.0 N-m
M8:
9.0 to 11.0 N-m
M10:
18.0 to 23.0 N-m
Keep the above tightening torque when wiring work.
.
.
.
.
.