background image

Refrigerator’s two 

sides or the back 

heat 

8.1 As condensation tube is placed here and caused the above phenomenon, 

which is normal. 

the cabinet surface 

condensation 

9.1 Air humidity is too large. 

 

 The solution for the common problem. 

 

1.Cooling is not enough good 

(Many reasons might cause that cooling not enough good, as blow :) 

Reason 

analysis 

Solutions 

1) Leakage of Gas 

If some gas leaked unit will work not well. 

Phenomenon of failure: 

a. lower pressure of liquid cycle system 

b. high temperature of copper tube of 

discharging gas, hand feels very hot. 

C. much noise, sounds like “ZZZZZ”, comes 

from outlet of capillary. 

d. the temperature fell down very slowly. 

First find out the point of leaking 

on tube, and then sealed it, 

vacuuming it, finally recharge with 

Gas. 

Note: 

If you find oil on somewhere, it is 

possible that leakage point is 

there. 

2)  The quantity of 

Gas is too much 

If too much Gas was charged into the cycle 

system, the extra gas will occupy some 

space of evaporator, so that the area of heat 

exchange becomes less, unit will work not 

well. 

Phenomenon of failure: 

a, higher pressure of liquid cycle system 

than norm. 

b, higher temperature of condenser. 

c, larger electric current of compressor 

d, there maybe ice on the suction tube. 

e, when gas is too much, some gas liquid 

might goes back into compressor, 

compressor will be damaged by liquid. 

First stop unit for several minutes, 

and then open charging tube, 

discharge all of gas. Change a 

new filter, and then recharge gas, 

finally sealed the system. 

 

3) There is air in the 

liquid cycle system 

The air in system will cause lower efficiency 

of cooling. 

Phenomenon of failure: 

a, higher pressure of liquid cycle system 

than norm, but the pressure is not over the 

limit. 

b, higher temperature of discharging tube. 

C, much noise 

First stop unit for several minutes, 

and then open charging tube, 

discharge all of gas. Change a 

new filter, and then recharge gas, 

finally sealed the system. 

4)Low working 

efficiency of 

compressor 

General when a compressor works for many 

years, some parts of compressor were wear, 

so that compressor discharge less gas out, 

unit does not work strongly. 

Phenomenon of failure: 

a, lower pressure of discharging, check the 

pressure of system with pressure meter to 

Change a new compressor. 

Summary of Contents for RS-09DC4S Series

Page 1: ...REFRIGERATOR Service manual MODEL RS 09DC4S BD 65 NOTE This is a basic model the shape and specification of refrigerator is subject to change ...

Page 2: ...PARTS INENTIFICATION NOTE This figure is only a sketch Of the Refrigerator and the actual Products may differ from it CIRCUIT DIAGRAM COOLING DIAGRAM ...

Page 3: ...e guide for Disassembly Common parts of Refrigerator The instruction of replacing thermostat The location of the thermostat remove screws of top cover Capillary Compressor Dry filter Condenser Evaporator ...

Page 4: ...ire Take out the thermostat The instruction of replacing PTC Starting relay and Overload protector Take down Spring tap and Cover Unplug the connecting wire Take out the PTC Starting relay and Overload protector Door Reversal ...

Page 5: ...TROUBLESHOOTING The common problem judging method ...

Page 6: ...opriate 4 2 Is there multi moisture food and too close to the back wall of the refrigerator 4 3 Is the ambient temperature too low 4 4 Is the electric parts on good condition specially the thermostat wich will cause the unit non stopping Abnormal noise 5 1 Is the refrigerator stably placed 5 2 Does the refrigerator bump other objects 5 3 Whether the internal accessory of the refrigerator is in the...

Page 7: ...nit will work not well Phenomenon of failure a higher pressure of liquid cycle system than norm b higher temperature of condenser c larger electric current of compressor d there maybe ice on the suction tube e when gas is too much some gas liquid might goes back into compressor compressor will be damaged by liquid First stop unit for several minutes and then open charging tube discharge all of gas...

Page 8: ...int is there 2 There is some thing that blocked the liquid cycle system A Ice blocking Sometime because unknown reason water comes into liquid cycle system the capillary will be blocked by water after unit runs for period of time Phenomenon of failure The unit works well in the inception after period of time the ice appears in the capillary and becomes more and more till blocks the hole of capilla...

Page 9: ... Please put the food properly 5 Wind door is broken Replace wind door 6 Fan motor is broken Replace fan motor Note Before doing these operations above disconnect the main power supply Failure to do so could result in electrical shock or personal injury In case of any detailed technical information please check with the technical specifications announcements of Maintenance operation safety In order...

Page 10: ...oper maintenance tools Improper use tools may cause bad contact or fastening rickety and accidents 6 Wire connection Reconnecting first must weld or use connected terminals and insulation tape sealing ensure good contacts 7 Insulation testing after the maintenance assembly the insulation resistance testing must use a multimeter to confirm insulation resistance up to 1 M Ω above can electrify opera...

Reviews: