Refrigerator’s two
sides or the back
heat
8.1 As condensation tube is placed here and caused the above phenomenon,
which is normal.
the cabinet surface
condensation
9.1 Air humidity is too large.
◆
The solution for the common problem.
1.Cooling is not enough good
(Many reasons might cause that cooling not enough good, as blow :)
Reason
analysis
Solutions
1) Leakage of Gas
If some gas leaked unit will work not well.
Phenomenon of failure:
a. lower pressure of liquid cycle system
b. high temperature of copper tube of
discharging gas, hand feels very hot.
C. much noise, sounds like “ZZZZZ”, comes
from outlet of capillary.
d. the temperature fell down very slowly.
First find out the point of leaking
on tube, and then sealed it,
vacuuming it, finally recharge with
Gas.
Note:
If you find oil on somewhere, it is
possible that leakage point is
there.
2) The quantity of
Gas is too much
If too much Gas was charged into the cycle
system, the extra gas will occupy some
space of evaporator, so that the area of heat
exchange becomes less, unit will work not
well.
Phenomenon of failure:
a, higher pressure of liquid cycle system
than norm.
b, higher temperature of condenser.
c, larger electric current of compressor
d, there maybe ice on the suction tube.
e, when gas is too much, some gas liquid
might goes back into compressor,
compressor will be damaged by liquid.
First stop unit for several minutes,
and then open charging tube,
discharge all of gas. Change a
new filter, and then recharge gas,
finally sealed the system.
3) There is air in the
liquid cycle system
The air in system will cause lower efficiency
of cooling.
Phenomenon of failure:
a, higher pressure of liquid cycle system
than norm, but the pressure is not over the
limit.
b, higher temperature of discharging tube.
C, much noise
First stop unit for several minutes,
and then open charging tube,
discharge all of gas. Change a
new filter, and then recharge gas,
finally sealed the system.
4)Low working
efficiency of
compressor
General when a compressor works for many
years, some parts of compressor were wear,
so that compressor discharge less gas out,
unit does not work strongly.
Phenomenon of failure:
a, lower pressure of discharging, check the
pressure of system with pressure meter to
Change a new compressor.