Safety precautions

4

CAUTION

        which are inherently resistant to  being corroded or are suitably protected
        against being so corroded.
6-9  

 Checks to electrical devices

     Repair and maintenance to electrical components shall include initial safety
     checks and component inspection procedures. 
     If a fault exists that could compromise safety, then no electrical supply shall be
     connected to the circuit until it is satisfactorily dealt with. 
     If the fault cannot be corrected immediately but it is necessary to continue
     operation, an adequate temporary solution shall be used. 
     This shall be reported to the owner of the equipment so all parties are advised. 
     Initial safety checks shall include:

   

– 

That capacitors are discharged: this shall be done in a safe manner to avoid

         possibility of sparking;

   

– 

That there no live electrical components and wiring are exposed while

         charging, recovering or purging the system; 

   

– 

That there is continuity of earth bonding.

7.

Repairs to sealed components  

During repairs to sealed components, all electrical supplies shall be

     disconnected from the equipment being worked upon prior to any removal of
     sealed covers, etc. 
     If it is absolutely necessary to have an electrical supply to equipment during
     servicing, then a permanently operating form of leak detection shall be located
     at the most critical point to warn of a potentially hazardous situation. 
     Particular attention shall be paid to the following to ensure that by working on
     electrical components, the casing is not altered in such a way that the level of
     protection is affected. 
     This shall include damage to cables, excessive number of connections,
     terminals not made to original specification, damage to seals, incorrect fitting
     of glands, etc.  
     Ensure that apparatus is mounted securely.
     Ensure that seals or sealing materials have not degraded such that they no
     longer serve the purpose of preventing the ingress of flammable atmospheres.
     Replacement parts shall be in accordance with the manufacturer's
     specifications.
     NOTE: 
     The use of silicon sealant may inhibit the effectiveness of some types of
     leak detection equipment. Intrinsically safe components do not have to be
     isolated prior to working on them.  
8.

Repair to intrinsically safe components

     Do not apply any permanent inductive or capacitance loads to the circuit
     without ensuring that this will not exceed the permissible voltage and current
     permitted for the equipment in use.
     Intrinsically safe components are the only types that can be worked on while

Summary of Contents for HPA27C

Page 1: ...ation instructions carefully before installing and using this appliance and keep this manual for future reference Model HPA27C HPA30C Hisense Guangdong Air Conditioning Co Ltd No 8 Hisense Road Advanc...

Page 2: ...or similarly qualified persons in order to avoid a hazard The appliance shall be installed in accordance with national wiring regulations The range of external static pressures is 0 2Pa to 0 2Pa Keep...

Page 3: ...e area Prior to beginning work on systems containing flammable refrigerants safety checks are necessary to ensure that the risk of ignition is minimised For repair to the refrigerating system the foll...

Page 4: ...into the system or conducting any hot work A degree of ventilation shall continue during the period that the work is carried out The ventilation should safely disperse any released refrigerant and pre...

Page 5: ...absolutely necessary to have an electrical supply to equipment during servicing then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially...

Page 6: ...shall be calibrated in a refrigerant free area Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used Leak detection equipment shall be set at a perce...

Page 7: ...ements shall be followed Ensure that contamination of different refrigerants does not occur when using charging equipment Hoses or lines shall be as short as possible to minimise the amount of refrige...

Page 8: ...isolation valves on the equipment are closed off k Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked 15 Labelling Equipment shall be l...

Page 9: ...tric heating to the compressor body shall be employed to accelerate this process When oil is drained from a system it shall be carried out safely CAUTION When moving or relocating the air conditioner...

Page 10: ...gas regulations The maximum refrigerant charge amount is 0 936 kg Mechanical connectors used indoors shall comply with ISO 14903 When mechanical connectors are reused indoors sealing parts shall be r...

Page 11: ...cted Control panel Cool air outlet Signal receptor Remote control Transport handle Air outlet hose Evaporator air intake Secondary drain port Primary drain port Front Back Condenser air intake Power s...

Page 12: ...cted Control panel Cool air outlet Signal receptor Remote control Transport handle Air outlet hose Evaporator air intake Secondary drain port Primary drain port Front Back Condenser air intake Power s...

Page 13: ...cted Front Back Cool air outlet Signal receptor Remote control Control panel Evaporator air intake Transport handle Secondary drain port Air outlet hose Condenser air intake Primary drain port Power s...

Page 14: ...cted Front Back Cool air outlet Signal receptor Remote control Control panel Evaporator air intake Transport handle Secondary drain port Air outlet hose Condenser air intake Primary drain port Power s...

Page 15: ...ary to pull back the battery cells and get rid of them safety for recycling reasons When you need to disposal of the unit consult our dealer If pipes are removed incorrectly refrigerant may blow out a...

Page 16: ...ditioners are designed as supplemental cooling to local areas within a room NOTES To ensure proper ventilation keep the required distance from the return air outlet to the wall or other obstacles at l...

Page 17: ...the window slider kit for either the vertical or horizontal installation NOTES The holes in the window slider kit are positioned for attaching the rain cover for vertical or horizontal installation In...

Page 18: ...er section C Outer slider section 7 Close the window onto the window slider kit to secure A To air conditioner B Outdoors C Rain cover portable D Window slider kit E Window exhaust adapter F Flexible...

Page 19: ...the window in place A Upper window sash B Window lock bracket 4 Insert the foam seal behind the top of the lower window sash and against the glass of the upper window A Top of lower window sash B Foa...

Page 20: ...If a button is pressed during this time the compressor will not restart fo another 3 to 5 minutes In Cooling or Dry mode the compressor and condenser fan will stop when the room temperature reaches t...

Page 21: ...s the room The air conditioner automatically selects the temperature The fan runs on Low speed only Cooling Cools the room Press FAN to select High Mid or Low Press the Plus or Minus button to adjust...

Page 22: ...air conditioner aim the remote controller to the signal receptor The remote control will operate the air conditioner at a distance of up to 23 7m when pointing at signal receptor of the air conditione...

Page 23: ...SMART DIMMER Timer On TIMER ON Timer Off TIMER OFF CLOCK DIMMER IFEEL Power On or Off Press ON OFF button to turn on or off the unit NOTE Changing modes during operating Sometimes the unit Wait 3 min...

Page 24: ...comfortable 2 C NOTE With Heater models Cooling only models SUPER SUPER button is used to start or stop fast cooling or heating 1 Press SUPER button The air conditioner automatically sets the fan spee...

Page 25: ...same SLEEP Fan speed is automatically set at low speed NOTE The air conditioner will return to previous settings after Sleep control is turned off 4 To turn off Sleep control press SLEEP MODE FAN ON...

Page 26: ...t cycle Vibrations or noise due to poor wall or window construction A high pitched hum or pulsating noise caused by the modern high efficiency compressor cycling on and off the desired time 4 After yo...

Page 27: ...ase connect the drain hose on heating mode or the unit will stop running after the water the water reaches warning level 1 Uncover the primary drain port 2 Attach the drain hose to the primary drain h...

Page 28: ...t time only but room is not cool Set temperature is close to room temperature Lower set temperature See P Air Conditioner Use ortable The air conditioner is in a heavily occupied room or heat producin...

Page 29: ...f your portable air conditioner Portable air conditioners are designed as supplemental cooling to local areas within a room The filter is dirty or obstructed by debris Clean the filter There is excess...

Page 30: ...Version No 2012256 02...

Page 31: ......

Reviews: