- 31 -
3.4 Single Board Constant Speed Machine Login
If connect single board constant speed machine on the communication bus, please turn bit3 of the slide switch SW11to ON
before power on, otherwise, no single board constant speed machine can be connected in the whole system. Please refer to <2.4
Slide Switch Setting Method> 2.4 Slide Switch Setting Table.
3.5 Check MAC Address
Refer to the login interface in Figure 3.3. and enter, click <Network Setting> and enter IP setting interface. <LAN MAC
Address> will be displayed, this MAC address will be considered as the final MAC address of the machine, you can also spot
check the MAC address by key + digital tube.
Press and hold SW6+SW key for 3s and enter the setting mode, as shown in below Table 3.9, firstly check MAC menu
“EHAd.”.
Table 3.9 Check or set MAC address with key
NO.
·Press Up (SW5) or Down (SW8) until it displays “
EHAd.”.
·In “
EHAd.” Menu, press Select key (SW7) and confirm to enter MAC setting
mode.
·After set, press Eject/Switch (SW6) key to exit.
·Press SW7 so that the MAC address becomes editable, flashing in 1Hz.
1
·In menu, press Select key (SW7) so that the default number flashes and becomes
editable.
·Press Eject/Switch key (SW6) to switch flashing, and change editable area.
·Press Up (SW5) or Down (SW8) to change MAC number.
·The lowest digit of the MAC address cannot be 1, after set it as 1, it will be
deemed as invalid setting.
2
·As above.
3
·As above.
4
·As above.
5
·As above.
6
·As above.
7
·Finally press Select key (SW7) to confirm, after setting, press Eject/Switch key
(SW6) to exit.
·The display content will automatically disappear if no further action within 30s.
·After set the MAC address, MCU will reset automatically to ensure successful
change of the MAC.
3 Configuration of Modbus Adapter