- 21 - 

 

 

 

 

 

 

The other options shown in above figure have nothing to do with the IP address setting, please do not change it, or it may 

cause consequences that cannot return!   

 Note 

 

 
 
 
 

You can spot check and set IP address through key + digital tube.   

Press and hold SW6+SW7 key at the same time for 3s to enter the setting mode, as shown in below Table 3.2, the IP address 

spot checked is: 192.168.1.90. 

Table 3.2 Set IP address with key 

NO. 

 

·Press Up (SW5) or Down (SW8) to switch until it shows “IP.”.   
·In “IP.” Menu, press Select key (SW7) to enter IP setting mode.   
·After set, press Eject/Switch key (SW6) to exit.   
·Press SW7 so that the IP address becomes editable, and flashes in 1Hz. 

 

·In the menu, press Select key (SW7) so that the default IP address flashes and 

becomes editable.   

·Press Eject/Switch key (SW6) to switch flashing, change editable area. 
·Press Up (SW5) or Down (SW8) to change the IP number.   

 

·As above.

 

 

·As above.

 

 

·As above.

 

 

·Finally press Select key (SW7) to confirm, after set, press Eject/Switch key (SW6) 
to exit. 
·The display content will disappear automatically if no action within 30s. 

 

·Factory reset of the IP setting, the operation method is as follows: 

When there’s no content displayed on the digital tube, press the Down key (SW8) 
until it shows “EHcL.” For 1s and disappear to reset IP content, but please note 
that it is valid within 60s after powered on. 

 

 If you want to test the IP setting result or set the IP address again, enter the setting interface after 

entering the new IP address in the browser address bar, otherwise unable to login. 

For example:   

If change the IP address from factory setting 192.168.1.90 into 192.168.1.101, and then enter 

192.168.1.90, it will show the prompt that it cannot log in, need to enter the address of 192.168.1.101 to 

access setting interface. So after set the IP address, you can stick a label with the IP address set on it, or 

use key + digital tube to spot check IP for convenient of maintenance. 

Change IP address method 2

 

3 Configuration of Modbus Adapter

Summary of Contents for HCPC-H2M1C

Page 1: ...ange LAN WEB Login Password 26 3 1 4 Change Wireless WEB Login Password 26 3 1 5 One Key to Clear EEPROM 27 3 1 6 Remote Server IP Address Setting 27 3 1 7 Subnet Mask Setting 28 3 1 8 Gateway IP Sett...

Page 2: ...1...

Page 3: ...rofessional and general users Help you operate more easily Reference page Symbol Meaning Installation Electrical Construction Please entrust the dealer or professional installation personnel for the i...

Page 4: ...rts encounter water Do not change electrical wiring Otherwise it may cause major accidents In repair and maintenance please use solid ladder Otherwise it may overturn and cause injury Warning Warning...

Page 5: ...high temperature and cause fire or electric shock The wiring connection should be reliable If the connection is loose the wire gets hot and causes fire or electric shock Attention Turn off the power s...

Page 6: ...de service of changing the product to other use Without permission no part of this manual shall be copied If you have any question please contact the service center designated by the company Arrival i...

Page 7: ...rd format protocol for PC s secondary development and monitoring It s more convenient to achieve docking with the third party system The product also has the following functions Can concentrate to con...

Page 8: ...nection Modbus green no BACnet Flash when using Modbus TCP for communication RS 485 green Flash when using Modbus RTU for communication Screw M3 for fix the top cover Figure 1 2 Name of each part 1 Co...

Page 9: ...SW7 LED light post 6 Screw hole to fix on the wall 4 remove the rubber feet Use M3 screw to fix DSW2 DSW3 Figure 1 4 Name of parts in the Modbus adapter The default slide switch setting state shown in...

Page 10: ...ode Half duplex communication Concurrent mode Asynchronous communication Communication speed 9600bps Wiring distance Total length below 1000m Number of air conditioners to be connected The largest out...

Page 11: ...n Concurrent mode Asynchronous communication Communication speed 9600bps Wiring distance Within 1000m Table 1 5 External input and external output communication specifications Items Specifications Ext...

Page 12: ...setting method Switch content and setting method 5 Power input Matters to confirm 2 1 Installation place Please select a place which meets the following conditions for installation 1 The place where...

Page 13: ...Modbus BACnet H NET RUN POWER Figure 2 2 Installation direction 2 Remove 4 rubber feet 3 Loosen 4pcs screws which fix the top cover remove top cover as shown in Figure 2 3 2 4 4 Use M3 screw to fix o...

Page 14: ...00V power supply voltage there s obligation to do D class grounding construction grounding resistance below 100 when used above 300V low voltage circuit there s obligation to do C class grounding cons...

Page 15: ...12V or MINI USB input 2 5 6 Modbus RTU External input and output Figure 2 6 Wiring Method Table 2 1 Installation process Sequence Wiring type Specifications Wiring length Cable specification Power sup...

Page 16: ...t of Modbus adapter as shown in left figure Or use MINI USB 5V Insert MINI USB cable to the USB port of Modbus adapter as shown in left figure The other end of USB use 5V power supply Ground wire Comm...

Page 17: ...indoor unit of system NO 0 3 Output 1 OUTPUT1 Code switch SW11 bit1 is ON Running signal 4 Output 2 OUTPUT2 Code switch SW11 bit2 is ON Alarm signal Connection example Figure 2 6 Example of using Inpu...

Page 18: ...do not change bit8 OFF None OFF Please do not change DSW3 H NET bit1 ON H NET circuit terminal resistance 75 is available OFF H NET circuit terminal resistance 75 is not available OFF When terminal re...

Page 19: ...oner when the product enters normal running air conditioner RUN light flashes in 1Hz See lights status and light content at normal control normal and abnormal shown in below Table 2 5 Table 2 5 Lighti...

Page 20: ...mal communication among indoor units when the indoor unit is running Please confirm the H NET wiring connection i e 64 This product abnormal communication among outdoor units when all the indoor unit...

Page 21: ...er installation are completed and the power supply is connected 3 1 Configuration of Modbus Adapter Set up the product so that it can communicate with PC 3 1 1 IP Address Setting Modbus adapter networ...

Page 22: ...r for management connects with the product one by one the address of the product is still initial setting 192 168 1 90 it can connect if the IP address setting of computer for management is with the s...

Page 23: ...e 4 As above 5 Finally press Select key SW7 to confirm after set press Eject Switch key SW6 to exit The display content will disappear automatically if no action within 30s 6 Factory reset of the IP s...

Page 24: ...IP address for the client automatically as shown in Figure 3 4 Figure 3 4 Automatically obtain an IP address Use computer to search for WIFI signal Modbus_AP establish connection the default password...

Page 25: ...the password correctly After successfully set the WIFI password it will automatically disconnect WIFI please connect Modbus_AP again open Network and sharing center because general computer has the f...

Page 26: ...re 3 9 Manage wireless network Select Modbus_AP right click Property with the mouse Enter the changed password as shown in Figure 3 10 Figure 3 10 Enter new password window After entered new password...

Page 27: ...t Switch key SW6 to exit Press SW7 so that the number of clock becomes editable flashing in 1Hz 1 In menu press Select key SW7 so that the default clock flashes and becomes editable Press Eject Switch...

Page 28: ...the time of Modbus adapter 3 1 3 Change LAN WEB Login Password Refer to the login interface in Figure 3 3 click LAN Password it will display the LAN WEB login password change interface as shown in Fi...

Page 29: ...address is the IP address when considered Modbus as client computer for management and host computer as server based on above operation please set this IP address with the same IP address as computer...

Page 30: ...re 3 3 and enter click Network Setting and enter IP setting interface Directly set subnet mask LAN Net Mask You can also spot check and set the subnet mask through key digital tube Press SW6 SW7 key a...

Page 31: ...mode as shown in below Table 3 7 Table 3 7 Set gateway IP address with key NO Press Up SW5 or Down SW8 until it displays dG In dG Menu press Select key SW7 and confirm to enter gateway IP setting mod...

Page 32: ...shown in Table 3 8 Table 3 8 Air conditioner operating state Prompt sys 2 refers to No 2 refrigerant system addr 1 refers to No 1 address outAddr 1 refers to outdoor unit No 1 address error code 0x21...

Page 33: ...C menu EHAd Table 3 9 Check or set MAC address with key NO Press Up SW5 or Down SW8 until it displays EHAd In EHAd Menu press Select key SW7 and confirm to enter MAC setting mode After set press Eject...

Page 34: ...end fd bind fd n fd socket Figure 4 1 Modbus TCP Receiving and Sending Mechanism Modbus function code as shown in 4 1 Table 4 1 Function code Function code Name of function Function 0x03 Read hold reg...

Page 35: ...dbus RTU code Modbus adapter write error response code Additional address Function code Data CRC CHECK 32 90 01 7D CF Modbus device Function code 0x80 Modbus RTU code the first indoor unit system Data...

Page 36: ...ional address into factory default value same operation as reset default IP address please refer to Table 3 2 Set IP address No 6 When using Modbus RTU firstly need to configure it please refer to Tab...

Page 37: ...protocol start address Number of successful write hold register Modbus TCP code Modbus adapter write error response code MBAP message header Function code Data 00 01 00 00 00 03 FF 90 01 Modbus devic...

Page 38: ...ough Mapping Table For example explain with the first indoor unit communication protocol address operate 40083 address refer to the Mapping Table for others as follows Modbus RTU 32 10 9C 93 00 01 02...

Page 39: ...Mapping Table for others operation of making function selection B2 1 is as follows Modbus RTU 32 10 9C 70 00 14 28 00 20 00 00 00 00 00 80 00 00 00 00 00 00 00 80 00 00 00 00 00 00 00 00 00 00 00 00 0...

Page 40: ...ress of main indoor unit is the smallest one others are slave indoor units Wire controller prohibition includes all prohibition and partial prohibition Wire controller switch on off prohibition taking...

Page 41: ...7 00 01 02 00 01 67 8F Wire controller fan speed clear prohibited 32 10 9C 97 00 01 02 00 00 A6 4F Modbus TCP Wire controller fan speed prohibited 00 01 00 00 00 09 FF 10 9C 97 00 01 02 00 01 Wire con...

Page 42: ...connection confirmation Taking Mapping Table communication address as example operate 1000 address refer to Mapping Table for others as follows Modbus RTU Read the connection state of 64 outdoor units...

Page 43: ...by Modbus before sending next control command If do not take this as your control method please set the internal between two control command to be more than 500ms Though outdoor unit indoor unit conn...

Page 44: ...nd other information in the air conditioner group the digital tube will flash and display alarm code at this time you can turn off the digital tube display to achieve the purpose of energy saving You...

Page 45: ...on Please power on all the connected air conditioners Does H NET wiring use the designated specification cable Please use cable with cross sectional area greater than 0 75mm2 and total length within 1...

Page 46: ...firm whether the wiring connection is normal Does the RS 485 light remain on In the circumstance that there s no abnormal on the computer for management RS 485 wiring including connection then it may...

Page 47: ...lationship Is the POWER light on does the RUN light flash Have the state indicating lights H NET Modbus WIFI RS 485 been off Is the 7 segment digital tube often in off state 3 Installation and connect...

Page 48: ...nds when login the wire controller group the product will automatically choose one indoor unit as the host the benchmark is to select indoor unit with smaller refrigerant system number and address num...

Page 49: ...controller is installed and wire controller prohibition function is not set but it shows centralized control on the wire controller which leads to that the wire controller cannot be controlled please...

Page 50: ...Modbus RTU After installation the interface is as shown in Figure 7 1 Modbus RTU connection interface as shown in Figure 7 2 Modbus TCP connection interface as shown in Figure 7 3 Figure 7 1 Modbus po...

Page 51: ...18 19 20 21 22 23 24 25 26 27 28 29 30 31 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 Please record in the table the situation of indoor units which are marke...

Page 52: ...8 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 Please record in the table the situation of indoor units which are...

Page 53: ...20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 Please record in the table the situation of indoor units which are...

Page 54: ...50 51 52 53 54 55 56 57 58 59 60 61 62 63 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 Please record in the table the situation of indoor units which...

Page 55: ...53 1 Centralized Control Area Unit Group Note Registration Form 1 System No Address No Note room number etc System No Address No Note room number etc...

Page 56: ...54 2 Centralized Control Area Unit Group Note Registration Form 2 System No Address No Note room number etc System No Address No Note room number etc...

Page 57: ...55 3 Centralized Control Area Unit Group Note Registration Form 3 System No Address No Note room number etc System No Address No Note room number etc...

Page 58: ...56 4 Centralized Control Area Unit Group Note Registration Form 4 System No Address No Note room number etc System No Address No Note room number etc...

Page 59: ...57...

Page 60: ...58...

Page 61: ...icate Attached in the installation instruction manual Accessory list Attached in the installation instruction manual Hisense Corporation Add 17 Donghai Xi Road Qingdao 266071 China P00862Q 2015 11 V01...

Reviews: