(b) Indoor
Unit
Side
Field
Piping
Size
●
When a branch is located downstream of the
Switch Box
●
When a branch is not located downstream of the
Switch Box
Connected
Indoor
Unit
Capacity:
(Q)
Gas
Pipe
(D)
Liquid
Pipe
(E)
kW
mm (inch)
mm (inch)
Q
<
16.0
f
15.88 (5/8)
1
f
9.52 (3/8)
1
Q
=
16.0
f
19.05 (3/4)
f
9.52 (3/8)
1
1. Field
flarin
work
is
required.
Refer
to
Section
5.1
for
the
flarin
g
work.
Connected
Indoor
Unit
Capacity:
(Q)
Gas
Pipe
(D)
Liquid
Pipe
(E)
Remarks
kW
inch (mm)
inch (mm)
1.2
≤
Q
≤
6.3
f
12.7 (1/2)
f
6.35 (1/4)
Use
accessory
pipe
(1)
on
gas
pipe
side
and
accessory
pipe
(2)
on
liquid
pipe
side
to
decrease
the
pipe
size.
7.1
≤
Q
≤
16.0
f
15.88 (5/8)
1
f
9.52 (3/8)
1
-
Q
=
22.4
f
19.05 (3/4)
f
9.52 (3/8)
1
Use
accessory
pipe
(3)
on
gas
pipe
side
to
increase
the
pipe
size.
Q
=
28.0
f
22.2 (7/8)
f
9.52 (3/8)
1
Use
accessory
pipe
(4)
on
gas
pipe
side
to
increase
the
pipe
size.
1. Field
flarin
work
is
required.
Refer
to
Section
5.1
for
the
flarin
g
work.
NOTES:
1. When
connecting
the
Gas
Pipe
(D)
and
Liquid
Pipe
(E),
reuse
the
flar
e
nut
attached
to
the
Switch Box.
2. When
the
connected
indoor
unit
capacity
is
1.2~6.3kW
and
the
piping
length
exceeds
15m
(49ft.),
use
9.52mm
(3/8
inch)
for
the
liquid
pipe.
In case the piping connection is not used for the indoor unit side piping connection, it must be
sealed using the closed flare nut originally attached. These flare nuts have been tightened by
torque specifications shown below before shipping. Ensure that they are sealed completely.
NOTICE
18