3 Setting Up
3.5 Connection of signaling contact lines
36
OZD FIP G3 … Version 3.2 08/07
䊳
At the 5-pole terminal block on the upper side of the
repeater, floating contacts of a relay are provided as
a signaling contact.
If the OZD FIP G3 … is functioning correctly, the relay
picks up and the contact is opened.
If a fault or power failure occurs, the relay drops out
and the contact is closed for at least 500 ms.
䊳
The following network and repeater faults can be sig-
naled at a master station:
Supply voltage
– No voltage supply (with redundant supply: failure of
all supply voltages)
Internal device fault
Received data
– Failure of receiving data at Port 2 and/or Port 3
(e.g. cable breakage)
– not data received at Port 1 after impressing the
operating voltage resp. after a failure (the device
checks once for data receiving at Port 1 after
impressing the operating voltage resp. after failure)
– No data received at any port for over 500 ms
䊳
Limit values of relay contact
– Max. switching voltage
60 V DC; 42 V AC
– Max. switching current:
1.0 A
– Max. switching capacity:
30 W
䊳
The voltage connected to the relay must correspond
to a
safety extra-low voltage
to IEC/EN 60 950.
䊳
Always ensure that the correct assignment is provided
for the 5-pole terminal block. Make sure that the
connecting leads of the signaling contacts are ade-
quately insulated. Incorrect assignment can result in
destruction of the repeaters.
䊳
Secure the terminal block by screwing on the flange
3.5 Connection of signaling contact lines
+24 V/48 V
+24 V/48 V*
Securing
flange
Error
0 V
Fig. 11: Signaling contact - assignment of 5-pole terminal block
Fig. 10: Operating voltage supply - assignment of 5-pole terminal block
+24 V/48 V
+24 V/48 V*
Securing
flange
Error
0 V
Summary of Contents for OZD FIP G3
Page 2: ...Seite Page Page Deutsch 1 20 English 21 40 Fran ais 41 60...
Page 8: ......
Page 14: ...2 Netztopolgien 12 OZD FIP G3 Version 3 2 08 07...
Page 28: ......
Page 34: ...2 Network Topologies 32 OZD FIP G3 Version 3 2 08 07...
Page 48: ......
Page 54: ...2 Topologies de r seaux 52 OZD FIP G3 Version 3 2 08 07...