background image

4. Configure settings. 
 

-1. Select the “PV Mode Set ON” setting on the Measurement Settings screen. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Settings 

Setting Description 

Solar cell rated output 
[kW] 

Enter the photovoltaic cell rated output or photovoltaic cell capacity for the solar panel being 
measured. If measuring a branch circuit, for example in order to investigate a failed string, enter the 
total rated output for the target photovoltaic cell only.

Cell temperature 
coefficient 
 
(maximum output) 

Photovoltaic cells have negative temperature characteristics, meaning that their output decreases as 
their surface temperature increases, and this coefficient expresses that relationship. This tendency is 
particularly pronounced in crystalline silicon. Enter the appropriate value after checking the 
specifications for the photovoltaic system. Following are reference values: Monocrystalline Si: -0.46; 
polycrystalline Si: -0.49; amorphous Si: -0.26; CI(G)S: -0.46 

Conditioner efficiency 

To display the AC estimated power (reference values) and AC estimated energy (reference values) on a 
PV Waveform/Values screen, consult the power conditioner specifications and enter the device’s 
conversion efficiency. The above value is subject to a larger error component in photovoltaic systems 
that boost the voltage on the power conditioner side so that it is higher than the voltage at the 
measurement point. 

Other loss coefficient 

Coefficient for the effects of factors such as wiring resistance, dirt or snow buildup on the panel 
surface, shadows, etc. A general average value of 0.07 is used by default. Change as necessary.

Pyranometer kind 
Pyranometer output rate 

Choose the pyranometer kind. Output rate initial value of the ML-01 is 20.00. Output rate initial value 
of the ML-020VM is 140.00. When Sensitivity indicated on the label of Pyranometer is A, the 
calculated value of 1000/A is set to output rate. Other pyranometer use Free Set. 

Clamp sensor range 

Select the same range as set for the CT6590 Sensor Unit. Next, press the “Monitor” key on the LR8400 
while the clamp is not applied to anything and adjust the 0ADJ knob on the CT6590 so that the “ch1-2 
current” is 0. 

PV mode initialize 

Resets the following settings to their default values: Solar cell rated output, Cell temperature 
coefficient, Conditioner efficiency, Other loss coefficient Pyranometer kind, Pyranometer output rate, 
and Clamp sensor range. (Please perform, when you initialize PV mode setup.) 

Extended channel set 

An input can be added to ch1-5 to ch1-11.Voltage, Thermo couple, and a clamp (2000A, 200A, 100A, 
20A, 10A) can be chosen from the input item of the channel which select check mark. (Please use it, 
when you increase the measurement channel in PV mode.) 

Interval 

Set the time interval at which to record data. The longer the time interval, the lower the cutoff 
frequency, increasing noise rejection effectiveness. It is recommended to increase the recording 
interval in environments that are prone to noise from inverters or other devices. 

Cont 

Set whether to perform measurement for the set time or continuously. 
OFF: Normal measurement (measurement for the specified recording time) 
ON: Continuous measurement 

Time/DIV 

Set the time per division. 

Filter 

Set to either 60 Hz or 50 Hz depending on the power supply frequency in your region. The longer the 
recording interval, the greater the noise rejection effectiveness. 

Timer 

Set when you wish to perform measurement regularly. This setting allows the instrument to perform 
measurement at a regular interval from the set start time to the set stop time. 

Auto save 

Set when you wish to save data automatically during measurement. For more information, see “Saving 
Data Automatically” in Section 6.2, “Saving Data,” of the LR8400 User Manual. 

Note 

  For photovoltaic systems that boost the voltage on the power conditioner side so that it is higher than the value at the junction box 

where the measurement is being taken, select channel number 1-1 on the Setting screen’s “CH” sheet and enter a voltage value as 
appropriate for the “Offset” setting under “Scaling” so that the voltage shown on the LR8400-23’s Monitor screen matches the 
photovoltaic system monitor’s DC voltage value. 

  The waveform data measured in "PV mode Set ON" LR8400-23 can be displayed by attached Logger Utility. However, "PV mode" 

cannot be set up by Logger Utility. 

 
 
 

5. Check measured values on the Monitor screen. 
 

-1. If you encounter any of the following displays on the Monitor screen, refer to the indicated solution. 

Display

Solution 

Erroneous voltage value

Check whether the 9322 Differential Probe switch is set to “DC.”

• 

Check whether the voltage range has been set to take into account the fact that the differential 
probe’s output ratio is 1/1,000. 

• 

For photovoltaic systems that boost the voltage on the power conditioner side so that it is higher 
than the value at the junction box where the measurement is being taken, select channel number 
1-1 on the Setting screen’s “CH” sheet and enter a voltage value as appropriate for the “Offset” 
setting under “Scaling” so that the voltage shown on the LR8400’s Monitor screen matches the 
photovoltaic system monitor’s DC voltage value. 

• 

Check whether the solar panels are susceptible to the effects of factors such as shadow, dirt, or 
snow buildup.   

• 

There may be a wiring break on a string or a module failure.     

Erroneous current value

Check the CT6590 Sensor Unit’s range setting. 

• 

Check the LR8400’s clamp range setting. 

• 

Check the adjustment of the 0ADJ knob on the CT6590 Sensor Unit. 

• 

Check the CT6590 Sensor Unit’s remaining battery life. 

• 

Check for noise sources such as inverters in the vicinity of the system. 

• 

Check the site to see if the solar panels are susceptible to the effects of factors such as shadow, 
dirt, or snow buildup.   

• 

There may be a wiring break on a string or a module failure.

 

Erroneous insolation value

Check the wiring connections. 

• 

Check for noise sources such as inverters in the vicinity of the system.

   

 

• 

Check the kind of pyranometer and output rate to be used.

Erroneous  panel temperature 
value 

Check the installation of the thermocouple. 

Check for a broken thermocouple connection. 

* Turning on the broken connection check on the 

CH

 sheet will cause 

Burn Out

 to be 

displayed for the measurement data. However, the broken connection check function cannot be 
used if the recording interval is 10 ms.   

Significant difference between 
power and estimated power 

Check the solutions for erroneous voltage, current, insolation, and panel temperature values 
above. 

• 

Check whether the PV specification setup have been set to appropriate value. In particular, 
double-check the photovoltaic cell rated output and clamp range settings as these are easy to 
overlook. 

• 

This error is more likely to occur in climates and time zones characterized by low insolation. 
Perform measurement during a time of high insolation. 

• 

There may be a wiring break on a string or a module failure. Pinpoint the location of the failure, 
for example by using an I/V tracer. 

 

6. Start time-series recording. 

If performing time-series recording, start recording. If the auto-save setting has been activated, data will be recorded simultaneously 
to the instrument’s internal memory and the specified CF card or USB flash drive. 

-1. Start measurement with the Start key. 
-2. Stop measurement with the Stop key. 

 
Note 

The continuous operating time for the AA alkaline batteries   
in the CT6590 Sensor Unit that ships with the CT9692-90 
  (or CT9693-90) Clamp Sensor is approximately 25 hours.   
When performing time-series recording, use the optional   
9445-02 AC Adapter. 

 

7. Investigate the failed string. (See Figure 3.) 

If the power value is significantly less than the estimated   
power, a solar panel may have failed. The instrument can be   
used to look for a string with a wiring break or a module   
failure by means of the following method. 

-1. Return to Step 3, “Place the sensors,” and connect the   

9322 Differential Probe and CT9692-90 (or CT9693-90) Clamp Sensor   
to the branch circuit as shown in Figure 3. Next, change the   
photovoltaic cell rated output on the Measurement Settings   
screen to the output value for the string being measured and   
check the voltage, current, and output values on the Monitor screen.   
Perform similar measurements for the other strings. Circuits with   
relatively lower values may indicate wiring breaks or module failures. 

-2. Without changing the settings made in (-1) above, cover the solar cell that you expect may be damaged with a piece of cloth, board, 

or other material and compare the resulting voltage, current, and energy values with the corresponding values before the panel was 
covered. Strings whose measured values do not change when they are covered may have a module failure or wiring break. 

-3. The instrument can also be used as a normal data logger by using the “PV Mode Set OFF” setting. Up to 30 channels of current 

data can be recorded by purchasing additional CT9692-90 (or CT9693-90) Clamp Sensors and BNC conversion cables. Current data 
for multiple strings can be recorded simultaneously, allowing current variations to be investigated. 

 

Note 

The instrument cannot be used to search for failures or wiring breaks within individual modules. For such applications, please use a 

thermal camera or dedicated checker. 

Figure 3

 

Note: The version of the 
software until the V9.12, it was 
ML-020 only rather than 
selection of pyranometer kind. 
From V9.13, please use it to 
select "ML-01", "ML-020", and 
"Free Set" pyranometer kind 
used as shown in the figure on 
the left. (In the system screen, 
you can check the version.)

 

Reviews: