33
3
Measurement and Output
3.1 Inspection Prior to Use
Inspect the unit and sensor for any damage it may have sustained during storage
or shipment and verify that it is operating properly before use. If you find any faults,
contact your authorized Hioki distributor or reseller.
Where to check
Check item
Solution
Cables
Any cable's insulation
broken?
Do not use the cable. Have it
repaired.
Display unit
Batteries
Sufficient battery power
remaining?
• If the indicator shows
, the
batteries have run low and you
should replace them as soon as
possible.
• If the batteries are low, the unit
may switch off when the backlight
turns on or when a beep tone
sounds.
Range
Does the range correspond
to the current?
Check by switching the range with
the
[RANGE]
key.
Zero check
With the AC mode selected,
does the display read 0 A or
close to 0 A?
If it does not, contact your
authorized Hioki distributor or
reseller.
With the DC mode selected,
does the display read 0 A or
close to 0 A?
Perform zero-adjustment with
the
[0ADJ]
key. Verify that the
displayed value is close to 0 A
while not measuring anything.
Display
All LCD segments are
displayed?
Check that all of the LCD's
If any does not, have the unit
repaired.
3
Measurement and Output
10
9
8
7
6
5
4
3
2
1
Appx.
Ind.
333
Summary of Contents for CM7290
Page 2: ......
Page 36: ...32 Connecting to an External Device...
Page 58: ...54 External Interface Specifications only for CM7291...
Page 77: ......
Page 78: ......
Page 79: ......
Page 80: ......