MODBUS
29
6.3 Register Definitions
6.3.1 Binary Outputs
Address Name
Description
00001
Equalize Mode
1=Equalize Mode, 0=Float Mode
00002
Manual Timer Method
Equalize Method (see note below)
00003
Manual Equalize Method
Equalize Method (see note below)
00004
Auto-Equalize Timer Method
Equalize Method (see note below)
00005
HVDC Shutdown Enable
Enables High Voltage DC Shutdown
00006
Battery Type
0=Lead, 1=NiCd, Used for TempCo
Note: Only one equalize method can be active at a time. The equalize method cannot be
turned off. By turning on one of the equalize methods the charger will turn off the other two
equalize methods automatically.
6.3.2 Binary Inputs
Address Name
Description
10001
HVDC
High Voltage DC Alarm
10002
LVDC
Low Voltage DC Alarm
10003
DC Output Failure
Charger Failure Alarm
10004
AC Input Failure
AC Input Failure Alarm
10005
Positive Ground Fault
Positive Ground Fault Alarm
10006
Negative Ground Fault
Negative Ground Fault Alarm
10007
CAR
Summary (Common) Alarm Relay
10008
HVDC Shutdown
High Voltage DC Shutdown Enabled
10009
LVAC Shutdown
Low Voltage AC Shutdown Enabled
10010
FLS Enabled
Forced Load Share Enabled
10011
Temperature Probe Installed
Temperature Probe Installed
10012
Defective Temperature Probe
Defective Temperature Probe Alarm