4 Start-up
X-HART 32 01
Page 42 of 58
HI 801 307 E Rev. 5.00
4.3.3
Tab: I/O Submodule HART_32_01: Channels
The
I/O Submodule HART_32_01:Channels
tab contains the following system parameters for
each HART channel.
Global variables can be assigned to the statuses and parameters with
->
and used in the user
program. The value without
->
must be directly entered.
Name
Data type R/W
Description
Channel no.
---
R
Channel number, defined by default
-> Channel OK
BOOL
R
TRUE: Faultless channel
FALSE: Faulty channel
Activate HART [BOOL] ->
BOOL
W
Activate/deactivate HART communication for this
channel
Table 26: Tab I/O Submodule HART_32_01:Channels in the Hardware Editor
4.3.4
Submodule Status [DWORD]
Coding of the variable
Submodule Status
.
Coding
Description
0x00000008
Fault detected while initializing the module
0x00000080
Chip select monitoring time
0x00020000
Warning, deviation of internal voltage measurement
0x00100000
Deviation of the HART clock to the internal 33 MHz clock
0x00200000
Deviation of the 33 MHz clock
0x00400000
Defective voltage monitoring
0x00800000
Internal voltage on 3V4 is defective
0x01000000
Internal voltage on 1V8 is defective
0x02000000
Internal voltage on 1V2 is defective
0x04000000
Internal voltage on 3V3 is defective
0x08000000
Internal voltage on GND is defective
0x10000000
Internal voltage on SI1 is defective
0x20000000
Internal voltage on SI2 is defective
0x40000000
Internal voltage on MES_WD is defective
Table 27: Submodule Status [DWORD]