3 Product Description
X-HART 32 01
Page 14 of 58
HI 801 307 E Rev. 5.00
The LEDs indicate the operating state of the module.
The LEDs on the module are divided into three groups:
Module status indicators (Run, Error, Stop, Init)
System bus indicators (A, B)
I/O indicators (channel 1...32, field, WP 1...32)
When the supply voltage is switched on, a LED test is performed and all LEDs briefly flash
simultaneously.
Definition of Blinking Frequencies
The following table defines the blinking frequencies of the LEDs:
Name
Blinking Frequencies
Blinking1
Long (approx. 600 ms) on, long (approx. 600 ms) off
Blinking2
Short (approx. 200 ms) on, short (approx. 200 ms) off, short (approx. 200
ms) on, long (approx. 600 ms) off
Blinking-x
Ethernet communication: Flashing in sync with data transfer
Table 3: Blinking Frequencies of LEDs
3.4.3
Module Status Indicators
These LEDs are located on the front plate, on the upper part of the module.
LED
Color
Status
Description
Run
Green
On
Module in RUN, normal operation
Blinking1
Module state:
STOP/OS_DOWNLOAD or
OPERATE (only with processor modules)
Off
Module not in RUN,
observe the other status LEDs
Error
Red
On/Blinking1 Internal module faults detected by self-tests, e.g.,
hardware, software or voltage supply.
Fault while loading the operating system
Off
Normal operation
Stop
Yellow
On
Module state:
STOP / VALID CONFIGURATION
Blinking1
Module state:
STOP / INVALID CONFIGURATION or
STOP / OS_DOWNLOAD
Off
Module not in STOP, observe the other status LEDs
Init
Yellow
On
Module state: INIT, observe the other status LEDs
Blinking1
Module state: LOCKED, observe to the other status
LEDs
Off
Module state: neither INIT nor LOCKED, observe
the other status LEDs
Table 4: Module Status Indicators