F20
4 Start-Up
HI 800 143 E Rev. 1.01
Page 39 of 56
4.3.3
Pulsed Outputs for F20
The following tables present the statuses and parameters for the pulsed output module
(DO 4) in the same order as given in the Hardware Editor.
4.3.3.1
Module
Tab
The
Module
tab contains the following system parameters.
System parameter
Data
type
R/W Description
DO.Error Code
WORD
R
Error code of the TO unit as a whole:
Coding
Description
0x0001
Error of the TO unit as a whole:
Module.Error Code
WORD
R
Module error code
Coding
Description
0x0000
I/O processing, if required with errors, see
other error codes
0x0001
No I/O processing (CPU not in RUN)
0x0002
No I/O processing during the booting test
0x0004
Manufacturer interface operating
0x0010
No I/O processing: incorrect configuration
0x0020
No I/O processing: fault rate exceeded
0x0040/
0x0080
No I/O processing: configured module not
plugged in
Module.SRS
UDINT
R
Slot number (System Rack Slot)
Module.Type
UINT
R
Type of module, target value: 0x00B5 [181
dec
]
Table 30: SILworX - System Parameters for the Pulsed Outputs,
Module
Tab
4.3.3.2
DO 4: Channels
Tab
The
DO 4: Channels
tab contains the following system parameters.
System parameter
Data
type
R/W Description
Channel no.
---
R
Channel number, defined by default
-> Error Code
[BYTE]
BYTE
R
Error code of the individual digital pulsed output channels:
Coding
Description
0x01
Fault in the digital pulsed output module
Value [BOOL] ->
BOOL
W
Output value for DO channels:
1 = output energized
0 = output de-energized
Pulsed outputs must not be used as safety-related
outputs!
Table 31: SILworX - System Parameters for the Pulsed Outputs,
DO 4: Channels
Tab