30
Hillphoenix Refrigeration Systems
CO
2
One Condensing Unit
Section 4: T
ranspor
t and Installation
ATTENTION: Any removal of coils from solenoid valves must take place when the equipment is
switched off. Only perform ignition after repositioning the coil on the solenoid valve.
ATTENTION: To avoid irreparable damage, do not start the compressors in vacuum conditions or
without refrigerant charged.
The service valves to which the vacuum pump must be connected include the following:
• RSD supply
• RSLIQ liquid
• RSS suction
For LT/MT machines, as shown in the figure below, a magnet must be used to open the YVO solenoid valve, with
the machine powered off.
• Remove the connector (1)
• Remove the coil (2)
• Insert the magnet (3)
Furthermore, the high pressure valve (HPV) downline of the gas cooler must be forced open, along with the
flash gas bypass valve for MT versions, by removing the valves’ stator coils and inserting and rotating a magnet
(OPTIONAL P/N: EEVMAG0000).
Refer to the VACUUM PROCEDURE MANUAL MODE instructions in
Preparation for Startup
later in this section.
Before terminating the evacuation procedure, the circuit must be loaded with 3.5 ounces of oil.
The oil in the compressor is PAG (polyglycols) 100 made by FUCHS RENISO PAG 100.
ATTENTION: Do not load any oil other than that specified by the manufacturer. For further
information, contact a Hillphoenix Field Support Engineer.