USER'S GUIDE R10 AXIAL FAN , Code: 0000, Iss: 9.07.2019

05

SPEED CONTROL

Rotation speed of a variable speed fan can be controlled by various signals:

- Linear voltage input (0-10V) or PWM input (PWM duty cycle 0-100%).
- MODBUS RTU protocol (Additional information are in documentation "Hidria EC Modbus parameters" and on www.modbus.org.

LINEAR VOLTAGE INPUT:

Linear input is factory adjusted to fit the customer’s sensor or other speed control reference. The input characteristic can be factory adjusted in 
terms of increasing input sensitivity or attenuation. 

For example: An air-cooled condenser is using a pressure sensor 0-20Bar => 0-10V, but the highest system pressure reached at maximum load 
is 16Bar => 8V. For optimal operation of the application the fan mounted on a condenser should run at max speed at 8V of input control voltage. 
In order to achieve that, we need to adjust the input characteristic in a way the picture shows. 

Linear voltage input is the most common and it is described below. The current input is also widely used, where long cables are necessary. PWM
input is used for electromagnetic noisy environments. PWM signal must be in square form with polarity the same as for linear voltage input (see
connection diagram). PWM duty cycle 0-100% correspond to 0-10V linear voltage input if the amplitude of the PWM voltage is Vp=10V.
Amplitude of PWM signal must not exceed 12Vp.

10%

1.0V

1,2V

Input voltage (0

10V)

F

a

n

 s

p

e

e

d

HYSTERESIS

100%

10%

1.2V

10V

Input voltage (0

10V)

Fan speed

CONTROL DIAGRAM

8V

adjusted

input curve

100%

10%

1.2V

10V

Input voltage (0

10V)

Fan speed

INPUT CHARACTERISTIC ADJUSTMENT

0

200

400

600

800

1000

1200

Fa

n

 r

o

ta

ti

o

n

a

sp

e

e

d

 (R

P

M

)

Input Voltage (0...10 V)

SPEED CONTROL DIAGRAM

1.2 V

10 V

5 V

In order to prevent cycling from standby to run mode or run to standby 
mode a small hysteresis is implemented. The default value is 
approximately 200mV. 
Hysteresis can be factory-adjusted in order to achieve customer 
requirements.

Speed of a fan increases linearly with input voltage. 

The fan operates in two different modes:
0-1.2 V…… Standby or stop mode
1.2-10 V….. Run mode
1.0-1.2V .....Hysteresis

Linear voltage input (0-10V DC) can be used as 0 (4)-20mA current 
input with an additional resistor of 500 Ohms between GND and 0-10V 
connection.

© Copyright  HIDRIA d.o.o., All rights reserved. Document is subject to change without prior notification.

6 / 8

Summary of Contents for R10R-50APS-ES50B-09C17

Page 1: ...06 PUTTING INTO OPERATION 07 MAINTENANCE SERVICE AND CLEANING 08 DIAGNOSTICS 09 PROTECTIVE FEATURES 10 EMC 11 TRANSPORT AND STORAGE 12 ErP AND ROHS DIRECTIVES 13 SERVICE ADDRESSES AND ADDITIONAL DATA...

Page 2: ...be safeguarded especially for the rotating parts Should there be a malfunction it must be ensured that the parts breaking off or flying away cannot cause serious damage or bodily harm Do not operate...

Page 3: ...s of water to axial fan from the rotor side This appliance is not intended to be built as a partition fan mounting in outside windows or walls unless it is built into an end application which is desig...

Page 4: ...category static Efficiency grade N 58 5 Variable speed drive INTEGRATED Power Input Pelec 317 5 W Airflow volume qV 4691 m h Pressure Increase ps 111 Pa Rotational Speed n 1110 RPM Specific ratio 1 0...

Page 5: ...diameter max 6 5mm for control circuit Fan performed with terminal box is as supplied fitted with a sealing plug in the cable glands as a preventive against ingress of water or moisture inside the ter...

Page 6: ...for electromagnetic noisy environments PWM signal must be in square form with polarity the same as for linear voltage input see connection diagram PWM duty cycle 0 100 correspond to 0 10V linear volta...

Page 7: ...carefully to avoid damage to them Never use a high pressure cleaner or water spray for cleaning Wet cleaning under voltage may lead to an electric shock Do not use any aggressive paint solvent cleanin...

Page 8: ...connection cables When unpacking fans transported in such a way grip the fan to protection grill Do not apply any force for the cable s When transporting fans mounted on final units apparatus take ca...

Reviews: