HIDRIA 0318-4-1005 Installation & Maintenance Download Page 8

USER'S GUIDE R18 AXIAL FAN , Iss: 6.05.2021

NFC / RFID WIRELESS COMMUNICATION

Fan has integrated NFC/RFID tag, based on ISO/IEC 15693, that can be used for advanced custom fan functionality configuration. NFC/RFID tag is
located as shown in the figure below. Before using NFC/RFID, the aluminium cover must be removed. Please see Hidria Fan App manual for more
information.

08

PROTECTIVE FEATURES

Short-circuit protection:

The motor and electronic controller are protected against short-circuit by built-in fuse.

Locked-rotor protection:

As soon the rotor is blocked, the motor is switched off electronically. After de-blocking, the motor will restart automatically. 

Mains under voltage:

If mains voltage falls below the nominal value the motor will keep running with degraded performance. Below 320V, the motor will be switched off
electronically in stand-by mode. When mains voltage returns to correct value, the motor will restart automatically. 
In the specific case, the undervoltage protection may switch off the fan to stand-by mode, for example, fan running or testing at high pressure drop and
low voltage.

Over temperature protection:

Internally connected thermal protector to protect electronic and motor against over temperature.

06

PUTTING INTO OPERATION

Before first start you should check:

a. Appropriate installation and electrical connection, especially resistance of the protective-earth (PE) circuit (max. 100m

).

b. If safety equipment is in place and motor protection device is in function.

c. If the impeller can rotate freely once the unit is mounted and the right direction of rotation is assured.

Only if all dangerous situations are excluded, the fan may be put into operation!

Switch ON the power supply.

Switch ON the device via the control signal and apply the speed setting voltage/signal and check the direction of the rotation and the smoothness of
running.

© Copyright  HIDRIA d.o.o., All rights reserved. Document is subject to change without prior notification.

8 / 10

Summary of Contents for 0318-4-1005

Page 1: ... ROHS AND EMC DIRECTIVES 12 SERVICE ADDRESSES AND ADDITIONAL DATA This document contains instructions and information for the operation installation connection use and maintenance of the product Be sure to familiarize yourself with these instructions before working on this unit Not paying attention to these warnings and instructions may lead to malfunctions and failures or may seriously endanger h...

Page 2: ...arm Do not operate this appliance in an explosive atmosphere Fan must be fixed to stationary housing with appropriate screws according to this guide This appliance is not intended to be built as a partition fan The electrical connection must correspond to this installation guide and enclosed connecting diagram as desribed in chapter 4 INSTALLATION AND CONNECTION page 6 of this document Means for d...

Page 3: ...s not intended to be built as a partition fan mounting in outside windows or walls unless it is built into an end application which is designed for that purpose The fan is intended to be permanently connected to fixed wiring The fan is intended to be connected to electrical power supply system with earthed neutral e g of type TN TT The fans are only to be operated within the ranges specified on th...

Page 4: ...densing Max pressure 260 Pa ErP DATA Overall Efficiency Effes 47 8 Installation category A Efficiency category static Efficiency grade N 51 4 Variable speed drive INTEGRATED Power Input Pelec 2708 1 W Airflow volume qV 18519 m h Pressure Increase ps 250 Pa Rotational Speed n 1146 RPM Specific ratio 1 002 Airflow volume max qV 27336 m h Pressure Increase max ps 610 Pa 1 Fan type and code 2 Trade ma...

Page 5: ... possible injuries the height and the diameter of inlet cone must be appropriate dimensions To lift the device with lifting devices use the hangers provided for this purpose as shown on figure below Always use suitable lifting equipment and follow the instructions for safe work with lifting equipment Failure to follow the instructions for safe work can lead to equipment damage or may seriously end...

Page 6: ...ing plug must remain in the gland Connection box screws have to be tightened with torque of 2 0Nm 2 5Nm Secure connection cable to the fan guard grill or to the motor holder with cable fasteners so that the water flows away from the cable and cable gland Try to maintain as much distance between supply and control cable as possible recommended distance 5cm Cable end of the fan must be connected in ...

Page 7: ...V but the highest system pressure reached at maximum load is 16Bar 8V For optimal operation of the application the fan mounted on a condenser should run at max speed at 8V of input control voltage In order to achieve that we need to adjust the input characteristic in a way the picture shows 1 0V 1 2V Input voltage 0 10V Fan speed HYSTERESIS 100 1 2V 10V Input voltage 0 10V Fan speed CONTROL DIAGRA...

Page 8: ... correct value the motor will restart automatically In the specific case the undervoltage protection may switch off the fan to stand by mode for example fan running or testing at high pressure drop and low voltage Over temperature protection Internally connected thermal protector to protect electronic and motor against over temperature 06 PUTTING INTO OPERATION Before first start you should check ...

Page 9: ...n in circuit of electronics windings never try to repair the fan but replace it with new one or and return defected fan to the manufacturer for repair or replacement ALARM RELAY DIAGNOSTICS Alarm relay contact OPEN on ERROR Alarm relay contacts capability max 2A 250VAC cos fi0 6 max 3A 30VDC Errors on which alarm relay OPEN Rotor locked in duration exceeding 10s Motor winding overheating Power mod...

Page 10: ...o protection grill Do not apply any force for the cable s When transporting fans mounted on final units apparatus take care that they are properly secured and don t touch other devices which are transported near or on to Store the fans in the original packaging in a dry area protected from the weather Do not store fans in extreme heat and cold We recommend a maximum of one year of storage After a ...

Reviews: