Zoning Panel LED’s 

The 11 function specific LED’s that indicate HVAC system operation and zone damper status. 
Familiarize yourself with the LED functions and definitions, in order to accurately determine the Zoned 
HVAC system status and mode of operation. 

3

Continue: Seven Built-in Timers 

timers This occurs after any initial power up or 
power failure. Press the 

Reset

 button for 1 

second to override.

Short Cycle Timer - 

When all zone demands 

are satisfied, the panel will not resume the same 
mode of operation for a minimum of  3 minutes.

Changeover Timer - 

Prevents the system from 

rapidly switching between heating and cooling 
modes. At the end of a call, a 4 minute timer is 
started and the panel will not switch to the 
opposing mode until the timer has expired.

Opposing Call Delay -

 A 20 minute delay must 

expire, or the active zone(s) must satisfy, before 
the panel will honor a demand to changeover to 
the opposite mode of system operation.

Staging Timer/OAS - 

The STAGING TIMER 

sets the amount of continuous call time in 1st 
stage, before second stage heat or cool is 
energized. 

NOTE: 

The potentiometer also 

serves as the

 Outside Air Changeover Setting.

Purge Delay - 

The STAGING TIMER sets the 

amount of  continuous call time in 1st stage, 
before second stage heat or cool is energized. 

NOTE: 

The potentiometer also serves as the

 

Outside Air Changeover Setting

The STATUS LED pulses as a steady 
heart beat to indicate proper Micro-
processor system status.

The OAS LED illuminates solid to 
indicate that the Outdoor Temperature 
has fallen below the chosen set point.  
The OAS LED will blink rapidly to 
indicate a shorted or open Outdoor Air 
Sensor circuit.

The SAS LED illuminates solid to 
indicate that the Supply Temperature 
has exceeded the chosen set point on 
either the HIGH TEMP LIMIT or the 
LOW TEMP LIMIT.  The SAS LED will 
blink rapidly to indicate a shorted or 
open Supply Air Sensor circuit.

The ZONE 3 LED: Indicates that 
damper(s) is energized open, and the 
Zone is active.

The ZONE 2 LED: Indicates that 
damper(s) is energized open, and the 
Zone is active.

The ZONE 1 LED: Indicates that 
damper(s) is energized open, and the 
Zone is active.

STATUS

GREEN

ZONE 1

GREEN

ZONE 2

GREEN

ZONE 3

GREEN

SAS

RED

OAS

RED

The FAN LED: Indicates a demand for 
fan operation, during COOLING, 
HEATING, PURGE, or CONTINUOUS 
FAN operations.

The Y2 LED: Indicates the 2nd stage of 
DX COOLING or DX HEATING is 
energized.

The Y1 LED: Indicates the 1ST stage of 
DX COOLING or DX HEATING is 
energized. 

The W1/B LED: Indicates that the 1st 
stage of HEATING is energized in 
Gas/Hydronic mode.  The W1/B LED 
also 

‘B’ reversing 

valve is energized in HEAT PUMP 
operation. 

NOTE: In Heat Pump Operation, 

this LED will stay illuminated after the call for 
heat is completed.

The W2/E LED: Indicates 2nd or 3rd 
stage of HEATING is energized in 
GAS/HYDRONIC or HEAT PUMP 
mode. The W2/E LED also 

 EMERGENCY HEAT is energized 

in HEAT PUMP mode.

illuminates when 

illuminates 

when

W1/B

RED

FAN

GREEN

Y1

YELLOW

Y2

YELLOW

W2/E

RED

052917

Pre-Release 052917

Summary of Contents for HE-Z

Page 1: ...cool Automatic Heat Cool Changeover Automatic changeover from any thermostat allowing for individual zone comfort Status LED A green STATUS LED pulses as a steady heart beat to indicate Micro processor activity and 24v power is present System LEDs Function specific colored LED s illuminate to indicate the HVAC system mode of operation and active zone identification Damper LEDs Green LEDs labelled ...

Page 2: ...C Start up Delay Timer 3 minutes fixed Short Cycle Timer 3 minutes fixed Change Over Timer 4 minutes fixed Opposing Call Timer 20 minutes fixed Staging Timer OFF or 7 42 min Adj Supply Air Limit Timer 3 minutes fixed Purge Delay Timer 90 seconds fixed Programming and Setting up your HVAC System Review each pin setting explanation of each dip switch function and choose your settings for correct ope...

Page 3: ...at to indicate proper Micro processor system status The OAS LED illuminates solid to indicate that the Outdoor Temperature has fallen below the chosen set point The OAS LED will blink rapidly to indicate a shorted or open Outdoor Air Sensor circuit The SAS LED illuminates solid to indicate that the Supply Temperature has exceeded the chosen set point on either the HIGH TEMP LIMIT or the LOW TEMP L...

Page 4: ... SWITCH GAS FAN HYDRONIC OFF SAS ON OFF 50 RULE ON OAS STAGING TIMER HC TSTATS HP HP SYSTEM OTHER DF SYSTEM CONV TIMER OAS STAGING 42 35 28 21 14 7 OFF R1 OFF 7 42 minutes or 7 42 degrees F Any Setting below 7 is OFF OFF DO NOT set to OFF when using OAS Emergency Heat Switch Isolated HVAC System Terminal Block Future Supply Air and Outdoor Air Sensor Connections 24v 4 0 amp Fuse STAGING TIMER W2 E...

Page 5: ...kage includes pre wired zone panel and 2 3 or 4 collars each w power open close dampers and actuators installed These are currently available pre installed on our HE Z Series Fan Coils Order HE Z fan coil unit from our Standard Price List and add these multi outlet tops to your order as a separate part The plenum take off outlets are 7 in height and adds to the height of the 32 fan coil The fan co...

Page 6: ...is no call for constant fan heat or cooling If one of the zones is calling for constant fan and the others are not the zones that are not calling will close In the event of a zone calling for heat or cooling the zone dampers regardless if a zone is calling for constant fan will close the non calling heat cool zones The actuators have been pre adjusted with approximately 10 bleed through this allow...

Page 7: ...UT ZONE 2 THERMOSTAT G R O B Y W E C C W Y R G O B ZONE 2 THERMOSTAT INPUT 3 2 1 M6 M4 M2 M1 ZONE 2 DAMPER 3 2 1 M6 M4 M2 M1 ZONE 3 DAMPER 3 2 1 M6 M4 M2 M1 ZONE 1 DAMPER 24V INPUT 4 0A PROTECTED R C R C G Y2 Y1 O W1 B W2 E RH RC C ZONE 1 THERMOSTAT C W Y R G O B ZONE 1 THERMOSTAT INPUT G R O B Y W E C ONE ZONE HVAC SYSTEM HI VELOCITY PSB CIRCUIT BOARD Dampers default to the OPEN position After a ...

Page 8: ... B G R Y1 W2 W1 FZ FZ Y2 C F1 AUXILIARY RELAY HEATING L L L2 L2 N L1 L1 A3 A2 A1 L N COOL HEAT FAN LED L1 J8 ON OFF H2 TIMER AUTO MAN H3 MODE ON OFF H4 DELAY J5 J7 J4 U2 J3 R8 R7 R6 G C H F 318 29 Pcbw 001sep 040 J2 N C Ri Ro H1 J9 J1 LED L2 PSB CIRCUIT BOARD 24v OUTPUT EMERGENCY DISCONNECT C 110 127 VAC 110 127 1 50 60 110 127v POWER CABLE L N Ground WH BK G LINE IN EMERGENCY DISCONNECT C 24 VAC ...

Page 9: ...LAY J5 J7 J4 U2 J3 R8 R7 R6 G C H F 318 29 Pcbw 001sep 040 J2 N C Ri Ro H1 J9 J1 LED L2 PSB CIRCUIT BOARD 24v OUTPUT EMERGENCY DISCONNECT C 1 2 3 4 5 6 7 8 9 10 11 12 L L1 N L2 U V W PE P 0 I Parameter Value WEG CONTROLLER VFD 200 240 VAC MOTOR LEADS PLUG 3 PHASE CAUTION FOR SINGLE STAGE COOLING OPERATION USE Y2 OTHERWISE THE FREEZE STAT WILL BE BYPASSED CAUTION FOR SINGLE STAGE COOLING OPERATION ...

Page 10: ... TERMINAL 4 AUXILIARY HEATING RELAY TIMER ACTIVATES CIRCUIT FOR 5 MINUTES EVERY 24 HOURS STARTING WHEN POWER IS APPLIED TO THE UNIT 5 LED 1 INDICATOR LIGHT FOR FAN SPEED OPERATION AND AUXILIARY RELAY OPERATION SEE BELOW FOR LIGHT OPERATION SEQUENCE 6 SEE INSTALLATION MANUAL FOR MORE DETAILED WIRING DIAGRAMS 7 8 FAILURE TO SET PROPER AIR FLOW AND OR OPERATION OF THE SYSTEM MAY RESULT IN DAMAGE TO E...

Reviews: