background image

Wiring and Configuration

Pre-Release 052917

    JUMPER PIN SETTINGS

AUXILIARY RELAY TIMER (SEE 

NOTES).

H3 

LED LIGHT INDICATORS

LED 1 - 

GREEN LIGHT, PUMP TIMER AND 

OPERATION MODE INDICATOR. 

LED 2 -

 BLUE LIGHT, PRESSURE SENSOR.

H1 EMERGENCY DISCONNECT:

 REMOVE PIN IF 

WIRED TO EMERGENCY DISCONNECT.

H2 TIMER: 

MODE:

 

AUTO -

 FAN SPEED MODULATES 

DEPENDING UPON STATIC PRESSURE.

MANUAL -

 FAN SPEED OPERATES AT TRIM 

POTS SET AIR FLOW.

H4 DELAY: 

Y/20 AND W/30 SECOND FAN DELAY.

Y AND W 30 SECOND POST PURGE.

ZONE BOARD SEVEN BUILT-IN TIMERS FOR 
SAFE & RELIABLE OPERATION

** DURING SET-UP MOMENTARILY PRESSING 
THE 

RESET

 BUTTON CLEARS THE BUILT-IN 

TIMERS. PRESSING THE 

RESET BUTTON

 FOR 7 

SECONDS WILL RESET THE CPU.

MOMENTARILY PRESSING THE 

RESET BUTTON

 CLEARS THE BUILT-IN TIMERS. 

THIS OCCURS AFTER ANY INITIAL POWER UP 
OR POWER FAILURE. PRESS THE 

RESET 

BUTTON FOR 1 SECOND TO OVERRIDE.

STARTUP DELAY TIMER -

 

 

THE PANEL WILL NOT 

ACTIVATE ANY COOLING OR HEATING 
OPERATION UNTIL THE STARTUP DELAY HAS 
EXPIRED.

* START-UP DELAY TIMER = 3 MINUTES-FIXED
* SHORT CYCLE TIMER     = 3 MINUTES-FIXED
* CHANGE OVER TIMER  = 4 MINUTES-FIXED
* OPPOSING CALL TIMER = 20 MINUTES-FIXED
* STAGING TIMER = OFF OR 7-42 MIN.-ADJ.
* SUPPLY AIR LIMIT TIMER = 3 MINUTES-FIXED
* PURGE DELAY TIMER  = 90 SECONDS-FIXED

ZONE CONTROLLER

PRE-WIRED TO 2 ZONES, 3 AND 4 IF APPLICABLE

M6 - 24VAC TO CLOSE DAMPER
M4 - 24VAC TO OPEN DAMPER
M2 - CONSTANT 24 VAC HOT
M1 - COMMON 24 VAC

NOTES:

1)

 USE THERMOSTAT FAN SWITCH TO DISABLE/ENABLE CONTINUOUS FAN.

2)

 ‘C’ TERMINAL ON THERMOSTAT (COMMON) IS NOT NEEDED FOR SOME 

THERMOSTATS CONSULT THERMOSTAT INSTRUCTIONS FOR DETAILS.

3)

 W1 AND W2 ACTIVATES AUXILIARY RELAY (A3) ON CALL AND CAN BE USED 

WITH A1 AND/OR A2 AS DRY CONTACTS, ARMED 24VAC FROM THE ‘R’ 
TERMINAL, OR ARMED 110v FROM THE ‘L’ TERMINAL.

4)

 AUXILIARY HEATING RELAY TIMER ACTIVATES CIRCUIT FOR 5 MINUTES 

EVERY 24 HOURS STARTING WHEN POWER IS APPLIED TO THE UNIT. 

5) LED 1: INDICATOR LIGHT FOR FAN SPEED OPERATION AND AUXILIARY 

RELAY OPERATION. 

SEE BELOW FOR LIGHT OPERATION SEQUENCE.

 

6)

 SEE INSTALLATION MANUAL FOR MORE DETAILED WIRING DIAGRAMS.

7)

8)

 FAILURE TO SET PROPER AIR FLOW AND/OR OPERATION OF THE SYSTEM 

MAY RESULT IN DAMAGE TO EQUIPMENT. 

9)

 FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE 

INSTALLATION COULD CAUSE PERSONAL INJURY AND/OR PROPERTY 
DAMAGE.

10)

 ENSURE THAT THE FILTER IS KEPT CLEAN AT ALL TIMES.

11)

 MOTOR HAS PERMANENT LUBE BEARINGS AND DOES  NOT REQUIRE 

OILING.

12)

 WARRANTY VOID IF FAN COIL UNIT IS USED DURING CONSTRUCTION. 

 FOR SINGLE STAGE COOLING OPERATION USE Y2, OTHERWISE THE FREEZE 

STAT WILL BE BYPASSED.

INCREASE AIR FLOW
(CLOCKWISE)

DECREASE AIR FLOW
(COUNTER CLOCKWISE)

FAN ADJUSTMENT TRIM POTS

ON: (ACTIVE) 

PUMP TIMER STATUS

ON: (INACTIVE)

OFF:

FAN OPERATION MODE

NO LIGHT

D

W

Y

G

2 SECONDS

2 SECONDS

2 SECONDS

LED 1: (GREEN LIGHT) 
PUMP TIMER/OPERATION MODE INDICATOR LIGHT SEQUENCE

LED 2: PRESSURE SENSING INDICATOR (BLUE LIGHT)
H3 JUMPER PIN: AUTO OR MANUAL MODE

AUTO MODE: LED 2 WILL SPORADICALLY FLICKER (ON/OFF)

 

TO SHOW THAT IT IS PROPERLY SENSING PRESSURE IN THE SYSTEM.

* NO LIGHT

 INDICATES TRIM POT IS ABOVE NORMAL OPERATING RANGE 

(COUNTER CLOCKWISE DECREASE).

* SOLID LIGHT

 INDICATES TRIM POT IS BELOW NORMAL OPERATING 

RANGE (CLOCKWISE, INCREASE).

MANUAL MODE: LED 2 WILL BE OFF

, ADJUST EACH OF THE AIR FLOWS TO 

DESIRED CFM/LPS OUTPUT. 

ADJUSTING TRIM POTS: ON POWER START UP, ALLOW 45 SECONDS FOR 

SYSTEM TO PRESSURIZE BEFORE MAKING ANY CHANGES. 

DO NOT ADJUST MORE THAN A ½ TURN AT A TIME, ALLOW 30 SECONDS 
BETWEEN ADJUSTMENTS FOR THE PSB TO REACH SET POINT.

REFER AND COMPLETE COMMISSIONING REPORT PRIOR TO NORMAL 

OPERATION. FOR FULL DETAILS, REPORT IS AVAILABLE IN THE INSTALLATION 
MANUAL OR ONLINE AT 

WWW.HI-VELOCITY.COM.

10

Summary of Contents for HE-Z

Page 1: ...cool Automatic Heat Cool Changeover Automatic changeover from any thermostat allowing for individual zone comfort Status LED A green STATUS LED pulses as a steady heart beat to indicate Micro processor activity and 24v power is present System LEDs Function specific colored LED s illuminate to indicate the HVAC system mode of operation and active zone identification Damper LEDs Green LEDs labelled ...

Page 2: ...C Start up Delay Timer 3 minutes fixed Short Cycle Timer 3 minutes fixed Change Over Timer 4 minutes fixed Opposing Call Timer 20 minutes fixed Staging Timer OFF or 7 42 min Adj Supply Air Limit Timer 3 minutes fixed Purge Delay Timer 90 seconds fixed Programming and Setting up your HVAC System Review each pin setting explanation of each dip switch function and choose your settings for correct ope...

Page 3: ...at to indicate proper Micro processor system status The OAS LED illuminates solid to indicate that the Outdoor Temperature has fallen below the chosen set point The OAS LED will blink rapidly to indicate a shorted or open Outdoor Air Sensor circuit The SAS LED illuminates solid to indicate that the Supply Temperature has exceeded the chosen set point on either the HIGH TEMP LIMIT or the LOW TEMP L...

Page 4: ... SWITCH GAS FAN HYDRONIC OFF SAS ON OFF 50 RULE ON OAS STAGING TIMER HC TSTATS HP HP SYSTEM OTHER DF SYSTEM CONV TIMER OAS STAGING 42 35 28 21 14 7 OFF R1 OFF 7 42 minutes or 7 42 degrees F Any Setting below 7 is OFF OFF DO NOT set to OFF when using OAS Emergency Heat Switch Isolated HVAC System Terminal Block Future Supply Air and Outdoor Air Sensor Connections 24v 4 0 amp Fuse STAGING TIMER W2 E...

Page 5: ...kage includes pre wired zone panel and 2 3 or 4 collars each w power open close dampers and actuators installed These are currently available pre installed on our HE Z Series Fan Coils Order HE Z fan coil unit from our Standard Price List and add these multi outlet tops to your order as a separate part The plenum take off outlets are 7 in height and adds to the height of the 32 fan coil The fan co...

Page 6: ...is no call for constant fan heat or cooling If one of the zones is calling for constant fan and the others are not the zones that are not calling will close In the event of a zone calling for heat or cooling the zone dampers regardless if a zone is calling for constant fan will close the non calling heat cool zones The actuators have been pre adjusted with approximately 10 bleed through this allow...

Page 7: ...UT ZONE 2 THERMOSTAT G R O B Y W E C C W Y R G O B ZONE 2 THERMOSTAT INPUT 3 2 1 M6 M4 M2 M1 ZONE 2 DAMPER 3 2 1 M6 M4 M2 M1 ZONE 3 DAMPER 3 2 1 M6 M4 M2 M1 ZONE 1 DAMPER 24V INPUT 4 0A PROTECTED R C R C G Y2 Y1 O W1 B W2 E RH RC C ZONE 1 THERMOSTAT C W Y R G O B ZONE 1 THERMOSTAT INPUT G R O B Y W E C ONE ZONE HVAC SYSTEM HI VELOCITY PSB CIRCUIT BOARD Dampers default to the OPEN position After a ...

Page 8: ... B G R Y1 W2 W1 FZ FZ Y2 C F1 AUXILIARY RELAY HEATING L L L2 L2 N L1 L1 A3 A2 A1 L N COOL HEAT FAN LED L1 J8 ON OFF H2 TIMER AUTO MAN H3 MODE ON OFF H4 DELAY J5 J7 J4 U2 J3 R8 R7 R6 G C H F 318 29 Pcbw 001sep 040 J2 N C Ri Ro H1 J9 J1 LED L2 PSB CIRCUIT BOARD 24v OUTPUT EMERGENCY DISCONNECT C 110 127 VAC 110 127 1 50 60 110 127v POWER CABLE L N Ground WH BK G LINE IN EMERGENCY DISCONNECT C 24 VAC ...

Page 9: ...LAY J5 J7 J4 U2 J3 R8 R7 R6 G C H F 318 29 Pcbw 001sep 040 J2 N C Ri Ro H1 J9 J1 LED L2 PSB CIRCUIT BOARD 24v OUTPUT EMERGENCY DISCONNECT C 1 2 3 4 5 6 7 8 9 10 11 12 L L1 N L2 U V W PE P 0 I Parameter Value WEG CONTROLLER VFD 200 240 VAC MOTOR LEADS PLUG 3 PHASE CAUTION FOR SINGLE STAGE COOLING OPERATION USE Y2 OTHERWISE THE FREEZE STAT WILL BE BYPASSED CAUTION FOR SINGLE STAGE COOLING OPERATION ...

Page 10: ... TERMINAL 4 AUXILIARY HEATING RELAY TIMER ACTIVATES CIRCUIT FOR 5 MINUTES EVERY 24 HOURS STARTING WHEN POWER IS APPLIED TO THE UNIT 5 LED 1 INDICATOR LIGHT FOR FAN SPEED OPERATION AND AUXILIARY RELAY OPERATION SEE BELOW FOR LIGHT OPERATION SEQUENCE 6 SEE INSTALLATION MANUAL FOR MORE DETAILED WIRING DIAGRAMS 7 8 FAILURE TO SET PROPER AIR FLOW AND OR OPERATION OF THE SYSTEM MAY RESULT IN DAMAGE TO E...