Installation Guide
Harrington Generators International Ltd
Welf-Air Super Compact Installation 2 498-048 Issue C
Fig. 2
A
A
A
B
Fit the flexible exhaust link pipe (Item B, Fig 2)
into position using the clamps provided
ensuring a gas tight fit. If you are unsure if the
pipe has sealed completely remove the link
pipe and use exhaust sealing compound
around the joints and re assemble.
Care must be taken to make a gas tight seal
when connecting the exhaust and that it is
adequately insulated.
To protect the exhaust and prevent potential
burns to operatives, wrap the exhaust link pipe
with heat wrap and secure with clamps or wire
fastenings. HGI can supply these upon request.
4.0 Alternative Installation
As an alternative, a 500cm
2
louvre with
combined horizontal exhaust outlet can be fitted
higher up.
With this configuration the generator air outlet
duct would need to be removed and a larger air
duct would have to be fitted to channel the hot