
1
Chapter 1 Meter Overview
DZS100-4P is an advanced, smart single-phase DIN rail energy meter. It meters electric
parameters of single-phase current, voltage, power, energy, frequency, power factor etc.
with high accuracy. It is LCD display and also equipped with RS485 communication and
pulse output.
I
ts main functions are as follows:
◆
Measure import active energy and export active energy;
◆
Measure combination of active energy, which is equal to the sum of import active energy
and export active energy
◆
Measure all instantaneous values of electric parameters, including voltage, current,
power, energy, frequency, power factor etc.;
◆
LCD displaying voltage, current, power etc..
◆
Automatically blocking and saving the blocked energy of last 12 months
◆
Timing Records with saving last 10 times of recording moments
◆
Loading data storage with recording data such as voltage, current, power, frequency,
power factor and active energy;
◆
Compatible with DL/T645-2007, DL/T645-1997 and Modbus-RTU protocols.
Chapter 2 Specification & Technical Parameters
2.1 Specification (the following parameters are subject to marks on nameplate)
Reference Voltage: AC220V(Un)
Current Specification: 1.5(6)A, 5(40) A, 10(80) A (which can be customized)
Frequency: 50Hz
Pulse Constant: 6400/1600/800imp/kWh (in the light of marks on nameplate)
Accuracy Class: Class 1.0
2.2 Technical Parameters
Starting Current: 0.004Ib
Insulation Strength: input to output, 2.0kV/min·1mA
Power Consumption:
<
2W,10VA
Creeping: Equipped with anti-creep logic circuits, when the energy meter loads 115% of
rated voltage and there is no current in current circuit, the energy meter shouldn’t output
more than one pulse in testing within the prescribed time.
Voltage Range: 0.9
~
1.1Un; limit range: 0.8
~
1.2Un
Communication Mode: RS485
Reference Temperature: 23
℃±
2
℃
;
Reference Humidity: 40
%~
60
%
RH
Working temperature: -20
℃
~50
℃
Storage Temperature: -40
℃
~70
℃
with relative humidity less than 85% and no corrosive