7
Remark:
1.
Primary Voltage Value = Secondary Voltage Value * Voltage Ratio
2.
Primary Current Value = Secondary Current Value * Current Ratio
3.
Primary Power Value = Secondary Power Value * Voltage Ratio * Current Ratio
6.3 Basic Setting Parameters Zone
(Function Code 06/0x10 Write; Function Code 03/04 Read)
Address
Address
Parameter Name
Default
Value Range
DEC
HEX
8192
2000
Password protection
(basic parameter
protection)
0001
0
~
9999
8193
2001
Communication
Address
1
1~247
8194
2002
RS485
Communication
0
High: 0:(N,8,1), 1:(o,8,1), 2:(e,8,1)
8195
2003
Baud Rate
3
0:1200, 1:2400, 2:4800, 3:9600,
8196
2004
Wiring Mode
0
0
:
3LN
,
1
:
2LL
8197
2005
PT
1
1
∼
9999 (Remark 1)
8198
2006
CT
1
1
~
9999 (Remark 1)
8199
2007
Energy Type
Selection of
Pulse Output
0
0: full-wave active energy pulse
1: full-wave reactive energy pulse
2: full-wave apparent energy pulse
3: fundamental wave active energy
pulse
4: fundamental wave reactive
energy pulse
5:fundamental wave apparent
energy pulse
Remark 1:
The product of voltage and current should be less than 300,000.
Remark 2
: The unit of time is 100ms
6.4 Real-time Energy Zone (Primary Value)(Function Code 03/04 Read)
Address
Address
Category
Parameter Name
Default
DEC
HEX
17664
4500
Total Real-time Energy
Total Active Energy
0
17665
4501
17666
4502
17667
4503
Import Active Energy
0
17668
4504
17669
4505