7.1 Password Setting Interface
Press buttons "
" and "
" at the same time, it will enter total
parameters setting mode. Enter password setting interface, the default password is 0001.
If the password is not correct, press button "
"(U/I). Then the upper right corner will show
a warning sign. If the password is correct, press "
" to enter address setting interface.
7.2 Address Setting Interface
Enter address setting interface. The present meter address is 001.
Setting range is 1-247. The address setting should comply with the requirements of register
table. Press button "
" to confirm and enter setting interface of communication
parameters.
7.3 Communication Parameter Setting Interface
Enter communication parameter setting interface. The present
parameter of RS485 communication is "8n1". Press the button "
" to set the parameters
as "8n1", "8o1", "8e1". Press button "
" to confirm and enter baud rate setting interface.
7.4 Baud Rate Setting Interface
Enter baud rate setting interface. The present baud rate of RS485 is
9600. Press the button "
" to set the parameters as 1200, 2400, 4800 or 9600. After
completing setting, press button "
" to confirm and enter wiring mode setting interface.
7.5 Wiring Mode Setting Interface
On wiring mode setting interface, the present wiring mode is 3-phase
4-wire. It can be set as “2LL” 3-phase 4-wire and “3Ln” 3-phase 4-wire by pressing the
button "
". After setting it, press “Enter” to enter voltage ratio setting interface.