24
HE 5712 Operating Instructions
# 372048 | Version 1.4
Parameters
Adjustment range
Default
setting
Pre-assignment
Post-cleaning Threshold
[mbar]
The threshold is
activated when the lower
threshold is exceeded.
If the threshold is
activated and the
pressure falls below the
threshold, a post-
cleaning cycle is
triggered and the
cleaning relay is closed
for the parameterised
post-cleaning time.
OFF,
0.0 … 500.0 mbar
2.0 mbar
2.0 mbar
(at 0...35 mbar
measuring range)
5.0 mbar
(at 0...90 mbar
measuring range)
25.0 mbar
(at 0...450 mbar
measuring range)
p-Offset [mbar]
The offset is added to the
currently measured
differential pressure.
-
50.0 … 50.0 mbar
0 mbar
0 mbar
Note!
Post-cleaning is suppressed as long as precoating is activated.