HE 5712 Operating Instructions
# 372048 | Version 1.4
23
6.2
Parameter Table
Parameters
Adjustment range
Default
setting
Pre-assignment
Password
3-digit number that must
be entered before
parameters can be
changed.
0 = no password protection
0 … 999
000
001
Pulse time
0.01 … 9.99 s
0.10 s
0.10 s
Break time
0.1 … 999 s
5.0 s
5.0 s
Number of valves
1 … 8
8
8
Post-cleaning cycles
OFF, 1 … 20
1
1
Type of cleaning
part/overall cycles
0 … 9
0
0
p-mesuring range
0
… 35 mbar
5.0 …35 mbar
35 mbar
35 mbar
0
… 90 mbar
5.0 …90 mbar
35 mbar
90 mbar
0
… 450 mbar
5.0 … 450 mbar
35 mbar
450 mbar
High alarm [mbar]
Threshold for the high
alarm message.
If exceeded, the relay
contact is closed
OFF,
0.0
… 500.0 mbar
30.0 mbar
30.0 mbar
(at 0...35 mbar
measuring range)
80.0 mbar
(at 0...90 mbar
measuring range)
390.0 mbar
(at 0...450 mbar
measuring range)
Upper threshold [mbar]
If this is exceeded,
p -
dependent cleaning
starts.
Start of the
p-cycle
0.0 … 500.0 mbar
15.0 mbar
15.0 mbar
40.0 mbar
(at 0...90 mbar
measuring range)
190.0 mbar
(at 0...450 mbar
measuring range)
Lower threshold [mbar]
The
p -dependent
cleaning stops if the
temperature falls below
this value.
End of the
p cycle
OFF,
0.0 … 500.0 mbar
10.0 mbar
10.0 mbar
(at 0...35 mbar
measuring range)
25.0 mbar
(at 0...90 mbar
measuring range)
130.0 mbar
(at 0...450 mbar
measuring range)
Low-alarm [mbar]
Threshold for the low
alarm message.
If the value falls below
this value, the relay
contact is closed if the
value does not fall below
the post-cleaning
threshold within the low-
alarm delay.
OFF,
-
5.0 … 500.0 mbar
OFF
OFF
(at 0...35 mbar
measuring range)
OFF
(at 0...90 mbar
measuring range)
OFF
(at 0...450 mbar
measuring range)