HE 5411 Operating Instructions
#340411 | version 1.7
33
Parameter
Adjustment range
Factory Setting
Unit
Lower limit value
See chapter 7.1
Off, Sensor
Min…Sensor Max
Off / 1% of
Base measuring range end
The lower limit value is
deactivated by default
for sensors with a
unidirectional basic
measuring range.
mbar, Pa,
inH2O, psi
Lower hysteresis limit value
See chapter 7.1
75% of
basic measuring range end
Pick-up delay
0.0…999.9
0
s
Dropout delay
0.0…999.9
0
s
Fail-Safe Relay
When the “Fail-Safe
Relay” parameter is
active, the relay is
energised in a non-active
state. If the upper or
lower limit value is
overshot or underrun, the
relay is de-energised
(see
Inactive, Active
Inactive
Creep flow suppression ‘Step’
None
Step (threshold = 10)