KS200-640 Server Cabinet Lock Series 

Installation Instructions 

 

 

 

 

 

Summary of Contents for KS200-640

Page 1: ...3085006 002 Rev 3 1 HES Inc Phoenix AZ 1 800 626 7590 www hesinnovations com KS200 640 Server Cabinet Lock Series Installation Instructions ...

Page 2: ...e Specifications Voltage 12 24 VDC 10 Power Supply not provided KS200 640 Reader Current Consumption 12 VDC 37 mA peak for Red and Green LED only 470 mA peak for Red and Green LED and Motor Drive 24 VDC 18 mA peak for Red and Green LED only 245 mA peak for Red and Green LED and Motor Drive Operating Temperature 10C to 50C Holding Force 250 lbs Handling Selector Lock Handle Mounting Plate Mounting ...

Page 3: ... cards to enable the credential capabilities of iCLASS Elite and NFC over HCE Credentials Supported 125 kHz Proximity or 13 56 MHz iCLASS iCLASS Elite iCLASS SEOS iCLASS SE ISO 15693 ICLASS ISO 14443A Mifare Mifare Plus Desfire SE Desfire EV1 and NFC over HCE System Overview The KS200 is a radio frequency identification RFID lock for server cabinet installation applications The lock is capable of ...

Page 4: ...6 or 7 pin SFIC cores 2 Preparing the Cabinet 1 LOCATE the 1 25 mm x 6 150 mm lock cutout on the door some doors may require modification 2 ENSURE power is available at the rack 3 RE USE the existing cam if possible NOTE One cam is supplied CAM CAM LENGTH CAM DEPTH CAM 1 1 1 2 38 mm 15 16 24 mm SFIC Core Cam SFIC Core 7 pin 6 pin 1 Insert Cam into SFIC Use the included Spacer with 6 pin SFICs 2 IN...

Page 5: ...al Switch 1 SPST NO Provided 2 PERFORM the following to extend the DPS Circuit a REMOVE the DPS jumper b CONNECT the included DPS extension cable c CONNECT additional normally open DPS switches as shown to monitor additional panels 3 CONNECT the female 10 position Hirose connector on the lock side interface cable to the KS200 4 ENSURE the lock side interface cable will properly protrude from the b...

Page 6: ...6 ENSURE that the lock is fully secured and flush to the mounting surface in order to depress tamper switch on back of device for correct operation NOTE If the tamper switch is not fully depressed the lock opens the Tamper DPS contact 5 ATTACH rear bracket with screws 7 IF the tamper switch is not fully closed THEN REMOVE the tamper contact AND ENSURE the lock is closed 3 INSERT and SECURE cam wit...

Page 7: ... 5 Red 6 Green 7 Orange 8 Brown 1 Gray 2 Yellow 3 Violet 4 Blue Function 12 VDC Reader Wiegand Data N A N A 12 VDC Reader Wiegand Data LED 12 24 VDC Lock Tamper DPS 12 24 VDC Lock Tamper DPS Setting NEG Data 1 N A N A POS Data 0 RED Green COM NC COM COM 1 CONNECT the Lock Side Interface Cable to the lock 2 CONNECT the Lock Side Interface Cable to the optional System Side Interface Cable see Connec...

Page 8: ...3085006 002 Rev 3 8 Connector and Cable Diagram ...

Page 9: ...3085006 002 Rev 3 9 Server Cabinet Wiring Example ...

Page 10: ...Testing the Lock with the Access Control System 1 TEST the lock with a known good credential to confirm it will open as desired when installed a PRESENT a credential known to the EAC b LIFT lever and TURN to open the cabinet ...

Page 11: ...3085006 002 Rev 3 11 This page intentionally left blank ...

Page 12: ...areil est confrome à la Partie 15 des règlements de la FCC Son fonctionnement est souimes aux deux conditions suivantes 1 cet appareil ne peut causer d interférences et 2 cet appareil doit accepter toute interference y compris des interférences qui peuvent provoquer un fonctionnement indésirable du périphérique Conformité aux normes IC Cet appareil est confrome avec Industrie Canada exempt de lice...