Port1 Modulation proportional 

1 - 20 

0.5 

21 

Port2 Modulation direction(0:10V Open;1:10V Close) 

0 - 1 

22 

Port2 Modulation minimum Signal 

0 Bit 

0-128Bit(5V/10mA) 

0.04V/Bit(0.08mA/Bit) 

23 

Port2 Modulation proportional 

1 - 20 

0.5 

24 

Port1 Floating minimum time 

1 sec. 

1 - 9 sec. 

1 sec. 

25 

Port1 Floating maximum time 

30 sec. 

10 - 300 sec. 

10 sec. 

26 

Port1 Floating minimum time 

1 sec. 

1-9 sec. 

1 sec. 

27 

Port1 Floating maximum time 

30 sec. 

10 - 300 sec. 

10 sec. 

28 

Disable / Enable bypass PID control 

( 0: Disable; 1: Enable ) 

0 - 1 

29 

Override output value when bypass PID control 

Display output value when enable PID control 

0 - 255 

30 

Override output value when bypass PID control 

Display output value when enable PID control 

0 - 255 

31 

Input signal management: 

0: Input valid 

1: Override Input: open 

2: Override Input: close 

0 - 2 

32 

Display room temperature or set-point 

0: Room temperature    1: Set-Point 

0 - 1 

33 

Configuration external sensor 

0: B = 3950; 1: B = 3450; 2: B = 3900 

3: User define (via network. default B = 3950) 

4: 5: 6: N/A

0 - 3 

34-38 

N/A 

39 

Start temperature of Low temperature protection 

5

/42

 

0-15

/42-62

 

1

/2

 

40 

Stop temperature of Low temperature protection 

7

/46

 

2-17

/46-66

 

1

/2

 

It will confirm itself 20 seconds later after setting and return to Off state. 

Switch:

 

There is a 5 poles switch on PCB. The meaning is below:

 

Location 

ON 

OFF 

120 ohm Resistance between AB wires

 

No Resistance between AB wires

 

Port 1 Modulation 0 - 20mA 

Off 

Port 1 Modulation 0 - 10VDC 

Off 

Port 2 Modulation 0 - 20mA 

Off 

Port 3 Modulation 0 - 10VDC 

Off 

Mounting: 

1. Open the back panel with 

screwdriver.

 

2. Connect the wires follow the 

diagram. 

3. Fix the base with screw.

4. Fix the front panel and finish 

the installation. 

HERZ Armaturen Ges.m.b.H.
A-1230 Wien, Richard-Strauss-Strasse 22,A-1230 Vienna, Austria

3

Summary of Contents for H7711 Series

Page 1: ...trol Remote Sensor Floating Modulation H7711A Cooling Heating H7711AN Cooling Heating H7711B Cooling Heating H7711BN Cooling Heating H7711C Cooling Heating H7711CN Cooling Heating H7711D Cooling Heating H7711DN Cooling Heating H7711E Cooling Heating H7711EN Cooling Heating H7711F Heating Cooling H7711FN Heating Cooling H7711I Cooling Heating H7711IN Cooling Heating H7711K Cooling Heating H7711N Co...

Page 2: ...it When thermostat get into Sleep function will flash press or to quit Keypad lock press and for 10 seconds till to display to activate under this function any keypad is locked Press and for 10 seconds till disappear to quit the function Set Parameters With thermostat off press for 10 seconds to enter menu to set the parameters Parameter table Paramete r Description Default Range Step 1 Power on s...

Page 3: ...erride Input close 0 0 2 32 Display room temperature or set point 0 Room temperature 1 Set Point 0 0 1 33 Configuration external sensor 0 B 3950 1 B 3450 2 B 3900 3 User define via network default B 3950 4 5 6 N A 0 0 3 34 38 N A 39 Start temperature of Low temperature protection 5 42 0 15 42 62 1 2 40 Stop temperature of Low temperature protection 7 46 2 17 46 66 1 2 It will confirm itself 20 sec...

Page 4: ...HC TR Fan Modbus A B Input Remote Sensor HO M 0 10V 4 20mA C HERZ Armaturen Ges m b H A 1230 Wien Richard Strauss Strasse 22 A 1230 Vienna Austria All specifications and information within this document are reflecting the information available at the time of going to print and meant for informational purpose only Herz Armaturen reserves the right to modify and change products as well as its technica...

Reviews: