T-CONTROL
9
45
9.10.6
Solar
NOTE: At the solar module 5 resp. 6 (only at external solar module) program numbers are available, which
are set up by the service technician. The only differences of the programs are the integration and the number
of tanks (e.g. hot water tank, buffer). The hydraulic schemes of the different modules are described in
appendix 15.2.
Navigation:
→
→
SOLAR
Screen:
By pressing the button:
the „Solar status“ menu will be displayed
the menu for the "settings" will be displayed
the menu for the "Aggregate-
Test“ will be displayed
the „solar yield“ menu will be displayed
Term
Description
Unit
Menu "Status"
Status 1
1
Collector flow
temperature
Indicates the collector flow temperature
°C
Collector back flow
temperature
Indicates the collector backflow temperature
°C
Tank 1 temperature
Indicates the temperature of tank 1
(e.g.: hot water tank, buffer)
°C
Tank 2 temperature
Indicates the temperature of tank 2
(e.g.: hot water tank, buffer) (only visible, if program 3, 4, 5 or 6 is
chosen)
°C
Collector pump
Indicates the status of the collector pump (On/Off)
-
Loading pump
Displays the condition of the backflow pump (On/Off)
-
Menu "Settings"
Settings
1
Pump trigger
Setting up the minimum collector temperature (15-70) to startup the solar
pump
°C
Summary of Contents for firematic CONDENSATION 30
Page 1: ...OPERATING INSTRUCTIONS Wood chips pellets heating system firematic CONDENSATION 30 40 ...
Page 83: ...Annex 15 83 15 ANNEX 15 1 Additional boiler module Hydraulic recommendation 1 ...
Page 84: ...15 Annex 84 Hydraulic recommendation 2 ...
Page 85: ...Annex 15 85 15 2 Solar module Program 1 ...
Page 86: ...15 Annex 86 Program 2 ...
Page 87: ...Annex 15 87 Program 3 ...
Page 88: ...15 Annex 88 Program 4 ...
Page 89: ...Annex 15 89 Program 5 ...
Page 90: ...15 Annex 90 Program 6 ...
Page 91: ...Notes 16 91 16 NOTES ...