POWER CABLE SPECIFICATIONS (3x380V-400V AC)
MODEL POWER
(HP/KW)
CABLE CROSS SECTION
(mm²)
MAIN FUSE
CURRENT (A)
HGS 2
3 / 2,2
4 x 2,5 mm
2
(Maksimum 25m)
10 A
HGS 3
4 / 3
4 x 2,5 mm
2
(Maksimum 25m)
10 A
HGS 4
5,5 / 4
4 x 2,5 mm
2
(Maksimum 25m)
20 A
HGS 5
7 / 5,5
4 x 4 mm
2
(Maksimum 25m)
25 A
HGS 5D
7 / 5,5
4 x 4 mm
2
(Maksimum 25m)
25 A
HGS 7
10 / 7,5
4 x 4 mm
2
(Maksimum 25m)
25 A
HGS 11
15 / 11
4 x 6 mm
2
(Maksimum 25m)
40 A
HGS 15
20 / 15
4 x 10 mm
2
(Maksimum 25m)
40 A
9
The above mentioned Cable Cross-Section and Main Fuse data are given for 380V / 400V AC
Power Supply and maximum 25m Power Cable length. If the Power Supply Voltage is different
and/or Power Cable length is longer than 25m than you may need to use different Main Fuses
and/or larger cross-section area Power Cables. In this case please apply to our Service
Department.