Herrmidifier Herrtronic AD Owner'S Manual Download Page 8

Herrtronic AD Series Installation, Operation and Service Manual

Supply Power

1.

 

Insure that adequate service is available to carry

125% of rated amps level. (refer to chart below).
2. Terminals are provided in the lower right hand comer
of
the electrical compartment for field connection of the
main
power supply legs (single or three phase) and a ground
wire

.

Distribution Method

Each steam cylinder requires at least one outlet for
steam via a duct distributor pipe or Room Distribution
Unit

.

Steam Distributor Pipes

Herrmidifier supplies stainless steel duct distributor
pipe(s) for use in injecting pure steam into duct. Refer to
Figures 5, 6 or 7 for proper placement. A minimum of 3'
downstream clearance before any bends or obstructions
is recommended for most applications, however differing
psychrometric conditions may require a greater or lesser
steam absorption distance. Consult your representative
or the factory if you have any questions. The duct
distributor pipes have a built-in pitch to allow condensate
drainage back into the hose. 

The rubber steam hose is

of large diameter and is meant to

 

carry steam up to

the distributor pipe and condensate back to the
steam cylinder for reuse. 

Because of this dual purpose

of the steam hose, it must be installed with a minimum
8% pitch back to the Herrtronic AD unit. Since steam
output losses are directly related to the distance from the
humidifier to the steam distributor, it is recommended:

3. Install external overcurrent protection and provide
wiring in accordance with the NEC, state and local
codes.
4. Power supply must be "clean": free of spikes, surges
and sags: +10%, -15% of nominal.
5. Check tightness of all power wiring connection -

Factory wiring: 35-45 in-lbs.
Field wiring: 35-275 in-lbs.
See Power Distribution Blocks for Exact Specification

a.  Mount the humidifier

 

as close as possible to the

steam distribution pipe.

b. Use 1 1/2" I.D. insulated copper pipe if the length of
run exceeds twenty feet.
c. Keep the total run of copper pipe under thirty feet
since the actual capacity of the humidifier can be
reduced by up to 15% and the increased static pressure
may cause problems with the fill

 

tee.

If possible, mount the steam distributor pipe to avoid low
spots in the steam hose. If you must, mount the steam
distributor pipe below the level of the humidifier, or if low
spots in the steam line are unavoidable, a condensate
separator is available from the factory (Part #EST-250)
(see Figure 8).
If it is necessary to split the output of one steam outlet
into more than one steam pipe, steam hose "Y"
connector assemblies are available from the factory
(Part #EST- 255). In this case, both ducts must be the
same static pressure for proper distribution.

• Kg/Hr = .454 x lbs./hr.
• Kw =.33 x lbs./hr.
• Amps (lPh) = Kw x

1000 ÷ Volt.

• Amps (3Ph) = Kw x

1000 ÷ (Volts x 1.732) •

Min Circuit Ampacity =

1.25 Rated Electrode
Amps (for each RDU,
add .5 Amps @ 208/
240v or add .25 Amps
@ 480v).

STEAM OUTPUT

Lbs./Hr.

5

10

15

20

25

30

40

50

60

80

100

125

Kg./Hr.

2.3

4.5

6.8

9.1

11.4

13.6

18.2

22.7

27.2

36.3

45.4

56.8

INPUT KW

1.7

3.3

5.0

6.6

8.3

10.0

13.3

16.7

20.0

26.6

33.3

41.2

Volts/Ph:

AMPS

208/1

8.0

16.0 24.0 32.0 40.0

48.1

64.1

80.1

240/1

6.9

13.8 20.8 27.6 34.7

41.7

55.6

69.4

208/3

4.6

9.2

13.9 18.5 23.1

27.8

37.0

46.3

55.5

74.0

92.6 115.7

240/3

4.0

8.0

12.0 16.0 20.0

24.1

32.1

40.1

48.1

64.2

80.2 100.2

480/3

2.0

4.0

6.0

8.0

10.0

12.0

16.0

20.0

24.0

32.1

40.1

50.1

600/3

1.6

3.2

4.8

6.4

8.0

9.6

12.8

16.0

19.2

25.6

32.1

40.1

Steam Output / Electrical Characteristics

WARNING!

Do not mount the standard steam distribution pipe in a
vertical downflow duct.  The combination of static
pressure and velocity pressure may be more than the
cylinder and/or the fill tee can handle.  A special steam
distributor must be ordered when installing in a vertical
downflow duct

NOTE

Steam holes are located within 2” of mounting plate
and closed end of distribution pipe.  Use extreme
caution when applying to internally lined duct.  Consult
factory if special hole locations are required.

Summary of Contents for Herrtronic AD

Page 1: ...lation Operation Service OWNER S MANUAL The AD Series Humidifiers represent the latest in humidification technology Please read these instructions carefully for trouble free operation and to get the m...

Page 2: ...II INSTALLATION INSTRUCTIONS Mounting 7 Plumbing 7 Supply Power 8 Steam Distribution 8 9 Control Circuit Connections 10 SECTION IV OPERATING INSTRUCTIONS Start Up Instructions 11 Check List 12 Mainten...

Page 3: ...nerating humidifiers contains a plastic steam generating cylinder which is to be considered a routinely disposable part to be changed at regular maintenance intervals at the user s expense This steam...

Page 4: ...cycle time opens the fill valve to replenish the water level until the capacity set point output is achieved As the mineral concentration in the water increases the water conductivity also increases...

Page 5: ...ge 50 100 Preset at 100 Low Drain Threshold Range 50 100 Preset setting varies by unit Cycle Time Range 60 300 Sec Preset setting varies by unit Faults Overcurrent 120 of Rated Current System Shutdown...

Page 6: ...ould be no obstructions within the first three feet down steam of the humidifier as shown in Figure 2 If the blower operates intermittently Auto an air proving switch should be provided to assure blow...

Page 7: ...uency 50 60 HZ Supply Water Pressure 20 psi I 00 psi Supply Water Temperature 40 F I 00 F Supply Water Conductivity 70 1 000 micromho Four lag bolts 2 5 16 and 2 1 4 are supplied with the AD Series wh...

Page 8: ...insulated copper pipe if the length of run exceeds twenty feet c Keep the total run of copper pipe under thirty feet since the actual capacity of the humidifier can be reduced by up to 15 and the incr...

Page 9: ...Herrtronic AD Series Installation Operation and Service Manual...

Page 10: ...ircuits are to be connected to the humidifier using the 12 pole control terminal strip located in the low voltage electrical compartment The terminal strip is accessed through the front door or the el...

Page 11: ...mperage reaches the data plate maximum and the fill solenoid turns off 10 If after installing jumper wires on ADS unit or if any ADM unit fails to reach 75 of output follow instructions in Troubleshoo...

Page 12: ...resentative or the factory and the checklist has not been accurately completed additional charges will be required by the individual s representing Herrmidifier If the visit uncovers a component malfu...

Page 13: ...nder 1 Drain cylinder completely using the Manual Drain Switch 2 Turn off power to the unit Disconnect electrode power wires and cylinder full electrode wire from tank 3 Remove tank and replace with n...

Page 14: ...ew hours of operation See start up note on jumper wire installation Foaming condition exists Flush and fill that steam cylinder several times and restart If it persists you must filter or treat the wa...

Page 15: ...ctor coil from circuit and repeat If 24 VAC fuses don t blow replace contactor Remove fill solenoid from circuit If fuses remain intact replace the fill solenoid coil Main 24 VAC fuses blow after humi...

Page 16: ...duct is not forcing water down the overflow instead of allowing water to enter the cylinder Adjust the fill metering valve to regulate the water flow to the cylinder Figure 9 Unit filling slower or a...

Page 17: ...Herrtronic AD Series Installation Operation and Service Manual...

Page 18: ...Item NO Description Steam Cylinder Assemblies ADS EST 1002 4 1 Single Phase 5 62 hr EST 1002 6 1 Three Phase 5 62 hr EST 1002 6 2 Three Phase 60 125 hr Parts List Item No Description Steam Cylinder As...

Page 19: ...Herrtronic AD Series Installation Operation and Service Manual...

Page 20: ...Herrtronic AD Series Installation Operation and Service Manual...

Page 21: ...Herrtronic AD Series Installation Operation and Service Manual...

Page 22: ...Herrtronic AD Series Installation Operation and Service Manual...

Page 23: ...Herrtronic AD Series Installation Operation and Service Manual...

Page 24: ...tion and Service Manual Corporate Office 101 McNeill Road Sanford NC 27330 Phone 800 884 0002 Fax 919 777 6300 www herrmidifier com email herrsales trioninc com Part No 156573 2003 Trion Inc Effective...

Reviews: